Plan Review Details - Permit 19010927
Plan Review Stops For Permit 19010927
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By fgiaquin Date 2019-02-14 Time 07:21 Rev Time 0.00
Received By fgiaquin Date 2019-02-14 Time 06:50 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-30 Cont ID  
Sent By fgiaquin Date 2019-01-30 Time 06:47 Rev Time 0.00
Received By fgiaquin Date 2019-01-30 Time 06:33 Sent To M
Notes
2019-01-30 06:47:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PHYSICAL WET SIGNATURE ON PLANS BY
 ELECTRICAL CONTRACTOR QUALIFIER. PLAN PROVIDED IS A
 COPY FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2.PROVIDE ACCURATE LOAD CALCULATION SHOWING ALL NEW
 LOADS. NEC 220
  
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 4.PROVIDE CONDUIT SIZES AND WIRE SIZES OF NEW CIRCUITS
 AND EXISTING WIRE AND CONDUIT TO BE REPLACED. FBC
 107.2.1
  
 5. PROVIDE DISCONNECT SIZE AND OCP SIZE OF DISCONNECTS
 TO BE REPLACED. FBC 107.2.1
  
 6. PROVIDE LOCATION OF PANEL WHERE NEW CIRCUITS ARE TO
 BE FED FROM ON PLAN. FBC 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-14 Cont ID  
Sent By fgiaquin Date 2019-02-14 Time 07:21 Rev Time 0.00
Received By fgiaquin Date 2019-02-08 Time 11:44 Sent To  
Notes
2019-02-11 11:44:42RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-06 Cont ID  
Sent By hmoser Date 2019-02-06 Time 08:38 Rev Time 0.00
Received By hmoser Date 2019-01-22 Time 13:07 Sent To  
Notes
2019-01-23 13:07:36ROUTED TO ELECTRICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-02-06 Cont ID  
Sent By hmoser Date 2019-02-06 Time 08:37 Rev Time 0.00
Received By hmoser Date 2019-02-06 Time 08:37 Sent To I
Notes
***NONE***