Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-13 Cont ID  
Sent By jduprey Date 2019-03-13 Time 10:29 Rev Time 0.00
Received By jduprey Date 2019-03-13 Time 10:29 Sent To  
Notes
2019-03-13 10:32:07PER OUR RECORDS BOTH TENANT SPACES ARE OCCUPANCY B. PER
 TABLE 508.4 OF FBC 2017 NO SEPARATION IS REQUIRED
 BETWEEN OCCUPANCIES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-31 Cont ID  
Sent By jduprey Date 2019-01-31 Time 10:34 Rev Time 0.00
Received By jduprey Date 2019-01-31 Time 09:43 Sent To  
Notes
2019-01-31 10:34:28BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE SUBMITTED DESIGN LETTER BY STEVE SIEBERT
 ARCHITECTURE IS A COPY OF THE ORIGINAL. MUST HAVE THE
 ORIGINAL SIGNATURE BY THE DESIGNER. PLEASE PROVIDE THE
 DESIGN LETTER WITH ORIGINAL SIGNATURE. FBC 107.2.1 ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5)
 AND F.S. 481.229.
  
 2. PER OUR RECORDS BOTH TENAT SPACES ARE OCUPPANCY B.
 IS A CHANGE IN OCCUPANCY OCURRING TO ANY OF THE TENANT
 SPACES? PLEASE PROVIDE MORE INFORMATION WHY THE
 ASSEMBLY-RATING WANT TO BE ADDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-24 Cont ID  
Sent By J.Walker Date 2019-01-24 Time   Rev Time 0.00
Received By   Date 2019-01-24 Time   Sent To B
Notes
2019-01-24 12:42:35EXISTING WINDOW WILL BE REQUIRED TO BE REMOVED OR
 RATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-13 Cont ID  
Sent By jduprey Date 2019-03-13 Time 10:35 Rev Time 0.00
Received By jduprey Date 2019-03-13 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-31 Cont ID  
Sent By jduprey Date 2019-01-31 Time 10:34 Rev Time 0.00
Received By jduprey Date 2019-01-22 Time 13:19 Sent To  
Notes
2019-01-23 13:19:17ROUTED TO FIRE INBOX