Plan Review Details - Permit 19010899
Plan Review Stops For Permit 19010899
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-02-05 Cont ID  
Sent By rmcdouga Date 2019-02-05 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2019-02-05 Time 06:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By jleahy Date 2019-02-25 Time 16:18 Rev Time 0.00
Received By jleahy Date 2019-02-25 Time 16:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-04 Cont ID  
Sent By jleahy Date 2019-02-04 Time 11:51 Rev Time 0.00
Received By jleahy Date 2019-02-04 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-25 Cont ID  
Sent By jleahy Date 2019-02-25 Time 16:18 Rev Time 0.00
Received By jleahy Date 2019-02-15 Time 13:51 Sent To  
Notes
2019-02-19 13:51:12RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-08 Cont ID  
Sent By rmcdouga Date 2019-02-08 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2019-01-22 Time 10:53 Sent To  
Notes
2019-01-23 10:53:38ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By rmcdouga Date 2019-02-25 Time 08:19 Rev Time 0.00
Received By rmcdouga Date 2019-02-25 Time 06:47 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By rmcdouga Date 2019-02-08 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2019-02-08 Time 16:44 Sent To I
Notes
2019-02-08 17:55:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE POOL PUMP. FBC 107.2.1
  
 2) PROVIDE TWO SETS OF TOTAL DYNAMIC HEAD CALCULATIONS
 FOR THIS POOL. FBC-R4501.6.3
  
 3) THE PUMP CURVE ON THE PLANS SHOWS THE FLOW RATE AS
 98 GPM WITH A TDH OF 38 FT AT 3450 RPM. THE ANSI 15
 CHART SHOWS THE HIGH SPEED FLOW RATE AS 98 GPM WITH A
 TDH OF 20 FT. PLEASE CLARIFY. FBC 107.2.1