Plan Review Details - Permit 19010898
Plan Review Stops For Permit 19010898
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-05 Cont ID  
Sent By dbattles Date 2019-04-05 Time 14:03 Rev Time 0.00
Received By dbattles Date 2019-04-05 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-14 Cont ID  
Sent By dbattles Date 2019-03-14 Time 10:42 Rev Time 0.00
Received By dbattles Date 2019-03-14 Time 08:19 Sent To  
Notes
2019-03-14 10:42:44****CORRECTIONS****
 W.P.B. PERMIT: 19010898
 2ND REVIEW: MARCH 14, 2019
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 109.3 FBC[AMENDED] THE VALUE APPEARS LOW FOR THE
 AMOUNT OF WORK BEING PERFORMED.
  PLEASE PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO
 SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT
 APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL COST OF
 WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY ADJUSTED
 PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL.
  
 NO PROPOSASL WAS PROVIDED AND THE VALUE OF THIS PERMIT
 SHOULD INCLUDE ALL TRADES AS IT WILL HAVE NO FEE SUB
 PERMITS.
 PLEASE PROVIDE PROPOSAL VIA E-MAIL, OR CALL TO DISCUSS.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-06 Cont ID  
Sent By dbattles Date 2019-02-06 Time 14:02 Rev Time 0.00
Received By dbattles Date 2019-02-05 Time 15:43 Sent To  
Notes
2019-02-06 14:03:05****CORRECTIONS****
 W.P.B. PERMIT: 19010898
 REVIEWED: FEBRUARY 5, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 109.3 FBC[AMENDED] THE VALUE APPEARS LOW FOR THE
 AMOUNT OF WORK BEING PERFORMED.
  PLEASE PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO
 SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT
 APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL COST OF
 WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY ADJUSTED
 PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL.
  
 2. R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS:
  
 R314.3 FBC[R] LOCATION. SMOKE ALARMS SHALL BE INSTALLED
 IN THE FOLLOWING LOCATIONS:
 A. IN EACH SLEEPING ROOM.
 B. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 C. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 NOTE: WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-04-05 Time 14:09 Rev Time 0.00
Received By jpearson Date 2019-04-05 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-15 Cont ID  
Sent By jpearson Date 2019-03-15 Time 11:21 Rev Time 0.00
Received By jpearson Date 2019-03-15 Time 10:55 Sent To  
Notes
2019-03-15 11:21:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 15:33 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 15:33 Sent To  
Notes
2019-02-05 15:33:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-16 Cont ID  
Sent By cmontell Date 2019-03-16 Time 07:05 Rev Time 0.00
Received By cmontell Date 2019-03-16 Time 07:05 Sent To  
Notes
2019-03-07 16:25:55R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 14:21 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 14:21 Sent To  
Notes
2019-01-23 11:43:52R07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-03-16 Cont ID  
Sent By cmontell Date 2019-03-16 Time 07:04 Rev Time 0.00
Received By cmontell Date 2019-03-16 Time 07:04 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 14:20 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 14:20 Sent To I
Notes
2019-02-15 14:20:51NEED MECHANICAL PLAN

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 07:30 Rev Time 0.00
Received By thunt Date 2019-03-11 Time 07:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By jesmith Date 2019-01-29 Time 10:39 Rev Time 0.00
Received By jesmith Date 2019-01-29 Time 10:37 Sent To  
Notes
2019-01-29 10:39:24DENIED
 APPROVAL ON HOLD PENDING A SIGNED SET OF PLANS; ONE
 COPY SIGNED AND SEALED, THE OTHER IS NOT
 PLANS ARE CODE COMPLIANT
 CALLED THE ARCHITECT TO ADVISE AT 561-248-8809 FERNANDO
 R. PRIETO-ARCHITECT
 PLANS ARE BACK IN BIN R07
  
  