Plan Review Details - Permit 19010721
Plan Review Stops For Permit 19010721
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 12:39 Rev Time 0.00
Received By cthroop Date 2019-01-25 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By cthroop Date 2019-01-22 Time 13:33 Rev Time 0.00
Received By cthroop Date 2019-01-22 Time 10:02 Sent To  
Notes
2019-01-22 14:37:19BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE SQUARE FOOTAGE AND ESTIMATED OCCUPANT
 LOAD, THIS STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS
 OF FS 553,79 "THRESHOLD BUILDINGS:.PLEAS SEE COMMENTS
 UNDER THRESHOLD REVIEW.
  
 2. THRESHOLD BUILDING
 CONFORMING TO CHAPTER 553 FLORIDA STATUTES,
 CHAPTER 468, PART XII, FLORIDA STATUTES
 AND THE FLORIDA BUILDING CODE AS AMENDED BY CITY OF
 WEST PALM BEACH
  
 3. PROVIDE A LIFE SAFETY PLAN.
 A) STATE OCCUPANT LOAD.
 B) IDENTIFY MEANS OF EGRESS.
 C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO EXIT.
 NOTE: AN ADDITIONAL EXIT MAY BE REQUIRED. THIS EXIT
 SHALL COMPLY WITH THE REQUIREMENTS OF AN ACCESSIBLE
 EGRESS EXIT.
  
 4. ) IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN. IDENTIFY
 PATH OF TRAVEL FROM DROP-OFF AREA TO ACCESSIBLE
 ENTRANCE ON SITE PLAN.
  
 5. PROVIDE DETAIL OF FLOORING TO BE USED.
  
 6. PROVIDE DETAIL OF ACCESSIBLE RAMP. RAMPS SHALL
 COMPLY WITH FBC ACCESSIBLITY SECTION 405.
  
 7. PLUMBING FIXTURES SHALL COMPLY WITH FBC TABLE
 2902.1.
 7A. BASED ON THE ESTIMATED OCCUPANT LOAD OF 422 SEATS
 THERE SHALL BE 3 WATER CLOSETS FOR THE MEN'S ROOM AND 6
 WATER CLOSETS FOR THE WOMENS ROOM.
  
 8. ACCESSIBLE RESTROOMS SHALL COMPLY WITH FBC
 ACCESSIBILITY CODE SECTION 213.3.1 AND SHALL ALSO
 COMPLY WITH SECTION 604.2 (WHEEL CHAIR ACCESSIBLE
 COMPARTMENTS).
 8A. BASED ON THE INDIVIDUAL NUMBER OF FIXTURES FOR THE
 MEN'S AND WOMEN'S ROOMS THERE SHALL BE ONE ACCESSIBLE
 COMPARTMENT FOR THE MEN AND ONE ACCESSIBLE COMPARTMENT
 FOR THE WOMEN. THESE COMPARTMENTS SHALL ALSO COMPLY
 WITH SECTION 604.2.
 8B. WE HAVE REVIEWED THE REQUIREMENTS FOR ACCESSIBLE
 FACILITIES BASED ON FBC P CHPT. 403.1.3 (POTTY PARITY)
 AND FOUND NO ADDITIONAL FIXTURES ARE REQUIRED FOR THE
 WOMEN'S RESTROOM.
  
 TEMPORARY MEMBRANE STRUCTURES
 (TENTS) FBC CHPT. 31
  
 3103.1 CONFORMANCE.
 1. PROVIDE STATEMENT FOR DATE OF ASSEMBLY AND DATE OF
 REMOVAL.
 2. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED
 STRUCTURE AND DISTANCE TO PROPERTY LINES AND OTHER
 STRUCTURES PER FBC CHPT. 6, SEC. 602.
 3. CONFORMANCE REQUIREMENTS PER SEC. 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? SUPPLIER TO
 PROVIDE CERTIFIED REPORT.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701.
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED.
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
  A) STATE OCCUPANT LOAD.
  B) IDENTIFY MEANS OF EGRESS.
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT.
  D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN
  E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
  F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203
  G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES
 ON SITE PLAN
  2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-22 Cont ID  
Sent By scaldero Date 2019-01-22 Time 10:06 Rev Time 0.00
Received By scaldero Date 2019-01-18 Time 14:53 Sent To  
Notes
2019-01-22 10:06:41PERMIT # 19010721
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 A FINAL FIRE INSPECTION MAY BE REQUIRED PRIOR TO THE
 EVENT DATE TO ENSURE COMPLIANCE WITH ALL APPLICABLE
 FIRE CODES.
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 2) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 3) DUE TO THE MAIN EVENT TENT EXCEEDING 1,200 SQUARE
 FEET, THE TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL
 TYPE, OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT
 SIGNS ARE REQUIRED.
  
 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 6) THE ASSEMBLY TENT SHALL HAVE THE SEATING ARRANGED IN
 A MANNER THAT COMPLIES WITH THE AISLE AND AISLEWAY
 REQUIREMENTS AS LISTED UNDER NFPA 101: 12.2.5
 (ARRANGEMENT OF MEANS OF EGRESS).
  
 7) THE OCCUPANT LOAD FOR THE ASSEMBLY TENT SHALL COMPLY
 WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101:
 CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY
 USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15
 SQ FT/PERSON.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-22 Cont ID  
Sent By cthroop Date 2019-01-22 Time 14:45 Rev Time  
Received By cthroop Date 2019-01-17 Time   Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 12:39 Rev Time 0.00
Received By cthroop Date 2019-01-25 Time 12:39 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By cthroop Date 2019-01-22 Time 14:37 Rev Time 0.00
Received By cthroop Date 2019-01-22 Time 13:33 Sent To  
Notes
2019-01-22 14:45:03BUILDING PLAN REVIEW - THRESHOLD BUILDINGS
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THRESHOLD BUILDING
 CONFORMING TO CHAPTER 553 FLORIDA STATUTES,
 CHAPTER 468, PART XII, FLORIDA STATUTES
 AND THE FLORIDA BUILDING CODE AS AMENDED BY CITY OF
 WEST PALM BEACH, CHAPTER 1, SECTION 110.8
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; A COPY OF THE CURRENT SPECIAL
 INSPECTOR AGREEMENT HAS BEEN INCLUDED IN THE E-MAIL
 NOTIFICATION OF REVIEW RESULTS.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. THRESHOLD STATEMENT REQUIRED BY FS553.79(7)(D) -
 ENGINEER, REVISE THE STATEMENT SO IT IS CLEAR THAT IT
 IS FOR COMPLIANCE WITH THE STATUTORY REQUIREMENT.
 SUGGESTED:
  
 REQUIRED FOR ALL
  
 "PER FS553.79, TO THE BEST OF THE ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633."
  
  
 110.8 THRESHOLD BUILDING.
 110.8.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLANS IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS. THE SPECIAL
 INSPECTOR MAY NOT SERVE AS A SURROGATE IN CARRYING OUT
 THE RESPONSIBILITIES OF THE BUILDING OFFICIAL, THE
 ARCHITECT OR THE ENGINEER OF RECORD. THE CONTRACTOR'S
 CONTRACTUAL OR STATUTORY OBLIGATIONS ARE NOT RELIEVED
 BY ANY ACTION OF THE SPECIAL INSPECTOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  