| Plan Review Stops For Permit 19010673 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-02-22 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-02-22 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-02-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-02-04 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-02-04 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2019-02-04 08:34:05 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF GENERATOR PAD CONSTRUCTION | | | DETAILS WITH GENERATOR TO PAD ANCHORING DETAILS. FBC-R | | | 301.2.1 | | | | | | 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE GENERATOR IS REQUIRED TO BE LOCATED AT OR | | | ABOVE THE SAME ELEVATION AS THE FINISH FLOOR OF THE | | | RESIDENCE. FBC-R322.1.6 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-02-22 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-02-22 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-02-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-02-07 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-02-07 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2019-02-07 17:26:22 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE FOR WORK SHOWN IS TOO LOW. PLEASE SUBMIT A SIGNED | | | CONTRACT WITH THE CUSTOMER FOR REVIEW. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-02-22 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-02-22 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-02-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-02-08 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-02-08 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2019-02-08 14:52:23 | GAS PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE TOTAL BTU'S OF ALL EXISTING GAS APPLIANCES. | | | R G2413.3 | | | 2. VALUE APPEARS LOW FOR SCOPE OF WORK (SOW). FBC 109.3 | | | BUILDING PERMIT VALUATIONS. | | | 3. PROVIDE DISTANCE FROM GAS METER TO FARTHEST GAS | | | APPLIANCE.R G2413.4.1 | | | 4. SHOW LOCATION OF GENERATOR ON SITE PLAN / SURVEY. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 5. SHOW LOCATION OF POOL HEATER ON SITE PLAN / SURVEY. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-02-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-02-22 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-02-15 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2019-02-19 13:36:37 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-02-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-02-08 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-01-17 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2019-02-08 10:52:56 | TO CT DESK | | | | | 2019-01-18 11:37:10 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-02-20 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-02-20 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-02-20 |
Time |
12:38 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-01-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-01-23 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-01-23 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2019-01-23 12:44:40 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY?S ADDRESS AND LEGAL DESCRIPTION. | | | 2) INDICATE SETBACK DIMENSION FROM GENERATOR TO SIDE | | | PROPERTY INE. | | | | | | NOTE: PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIPMENT | | | MAY NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER | | | THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO | | | SCHEDULE AN APPOINTMENT. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|