| 2019-01-22 07:41:05 | |
| | |
| | 1ST REVIEW: 19010610 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE INDICATE WHICH MODELS ARE BEING USED FOR THE |
| | GENERATOR AND POLL HEATER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHOW DISTANCE OF TANKLESS WATER HEATER FROM ANY |
| | OPENINGS IN THE BUILDING PROVIDE MANUFACTURE |
| | INSTALLATION GUIDE TO VERIFY DISTANCE. PER WPB AMEND TO |
| | FBC |
| | |
| | 3. PE PIPING TO BBQ GRILL IS RUNNING UNDER THE |
| | STRUCTURE THIS IS PROHIBITED. PER FBC FG 404.17.1 |
| | |
| | 4. LABEL THE TYPE OF PIPING ON TH RISER, SHOW THE |
| | LENGTH OF EACH SECTION. PIPE PER 2017 FBC-FUEL GAS, |
| | SECS. 402.4.1, 402.4.2. OR 2017 FBC-R SEC. G2413.4.1, |
| | G2413.4.2. WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. PROVIDE THE TOTAL LONGEST LENGTH FROM METER TO COOK |
| | TOP WHEN I ROUGHLY SCALED IT I CAME UP WITH 240' AT |
| | THIS LENGTH THE FIRST SECTION OF PIPE SHALL BE 1' PER |
| | FBC FG TABLE 402.4(22) |
| | |
| | 6. PROVIDE A REVISED SHEET SP1 THE ONE IN THE SUBMITTAL |
| | SHOWS THE ADDITION OF THE MASTER BEDROOM THE APPROVED |
| | PLANS HAVE THE ADDITION REMOVED. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 7. ALL REVISED PLAN SHEETS SHALL BE SIGNED AND SEALED |
| | BY DESIGNER OF RECORD. PER |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |