 |
Plan Review Details - Permit 19010578
| Plan Review Stops For Permit 19010578 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-09-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-09-19 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-09-19 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-09-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-09-06 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-09-06 07:17:35 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19010578 | | | ADD: 2717 POINSETTIA AVE. | | | CONT: PA TWIN MANAGEMENT/ CGC1525857 | | | TEL: 561-345-9054 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: FRI. SEPT. 06, 2019 | | | | | | ACTION: BUILDING PROVISOS | | | | | | 1) PROVISO: PLEASE NOTE THAT THAT THE BIRTHING CENTER | | | SHALL COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR | | | BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND | | | PROGRAMMATIC PROVISIONS, THE AGENCY OF HEALTH CARE | | | ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES. | | | FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES | | | THAT THE AGENCY (AHCA) MAY ENFORCE THE | | | SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING | | | CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY | | | ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA | | | BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO | | | ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL- | | | OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF | | | THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE | | | ACCESSIBILITY CODE. | | | PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE | | | 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE | | | DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE | | | COMPLIANCE. | | | | | | 2) PROVISO: A SEPARATE PERMIT IS REQUIRED FOR FIRE | | | SPRINKLERS. IN THE 2017 EXISTING BUILDING CODE FOR | | | CHANGE OF OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. | | | SECTION 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER | | | SYSTEM IN THE PORTION OF THE BUILDING THAT REQUIRES A | | | FIRE SPRINKLER SYSTEM, WHEN SEPARATION (HORIZONTAL) IS | | | INSTALLED BY OTHER REQUIREMENTS IN THE CODE. SECTION | | | 1004 E. B. C. FIRE PROTECTION IS REQUIRED IN CHAPTER 9 | | | OF THE FBC-B. SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA | | | 13R SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN | | | GROUP R OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN | | | HEIGHT IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) | | | IN HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE | | | INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R. | | | | | | AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP | | | TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS | | | NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE | | | PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN | | | ACCORDANCE WITH NFPA 13R. | | | | | | 3) PROVISO: SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR | | | SHOWS A TABLE AND CHAIRS LISTED AS 120, AND LISTED | | | STAFF AREA, WILL ANY OF THE CUSTOMERS AND OR RELATIVE | | | EVER BE ABLE TO USE THIS AREA FOR EITHER SNACKS OR | | | MEALS? IF SO THEN COMPLIANCE WILL BE REQUIRED WITH THE | | | 2017 ACCESSIBILITY CODE SECTIONS: | | | | | | 3)(A) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. | | | EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES, | | | STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY | | | CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL | | | GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA | | | SCOPING PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 3)(B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 3)(C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 3(D) NEW COMMENT) SHEET A1.2 SHOWS A MICROWAVE OVER THE | | | STOVE, HEIGHT NOT GIVEN BUT MUST COMPLY WITH THE | | | ACCESSIBILITY CODE | | | 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1 | | | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE | | | REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH | | | REACH. | | | | | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES | | | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL | | | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT | | | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE | | | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS | | | (22.2 N) MAXIMUM. | | | | | | 4) PROVISO: REVISION REQUIRED. SHEET A7.01 HAS A WINDOW | | | AND DOOR SCHEDULE. THE WINDOW SCHEDULE INDICATES SEE | | | STRUCTURAL SHEETS FOR WIND DESIGN & PRESSURES. THE DOOR | | | SCHEDULE INDICATES SEE ELEVATIONS FOR WIND DESIGN AND | | | ASSOCIATED PRESSURES. A REVISION IS REQUIRED SHOWING | | | THE REQUIRED WIND DESIGN CRITERIA AND ASSOCIATED | | | PRESSURES, PLUS PRODUCT APPROVALS FOR ALL NEW WINDOWS, | | | EXTERIOR DOORS AND NEW ROOFING. | | | | | | 4A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. | | | | | | 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS , | | | (B) WINDOWS | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-05-28 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-05-24 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2019-05-28 09:48:54 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19010578 | | | ADD: 2717 POINSETTIA AVE. | | | CONT: PA TWIN MANAGEMENT/ CGC1525857 | | | TEL: 561-345-9054 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. MAY 28, 2019 | | | | | | ACTION: FAILED | | | | | | 1) THE ONE SET OF PLANS HAS 2 SETS OF ARCHITECTURAL | | | SHEETS IN THE SET OF PLANS (REMOVE ONE SET), AND | | | MISSING SHEETS S1-S5. TE FULL SET OF PLANS THE S-SHEETS | | | ARE NOT SIGNED AND SEALED. | | | | | | 2) THE MECHANICAL SHEETS DOES NOT SHOW RADIENT FIRE | | | DAMPERS IN THE 2 HOUR FIRE RATED CEILING OF THE FIRST | | | FLOOR UNDER THE R2 RESIDENCY ABOVE. | | | 2017 FBC-B 717.6.2 MEMBRANE PENETRATIONS. DUCTS AND AIR | | | TRANSFER OPENINGS CONSTRUCTED OF APPROVED MATERIALS IN | | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL | | | THAT PENETRATE THE CEILING MEMBRANE OF A | | | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING | | | ASSEMBLY SHALL BE PROTECTED WITH ONE OF THE FOLLOWING: | | | 1.A SHAFT ENCLOSURE IN ACCORDANCE WITH SECTION 713. | | | | | | 2.A LISTED CEILING RADIATION DAMPER INSTALLED AT THE | | | CEILING LINE WHERE A DUCT PENETRATES THE CEILING OF A | | | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING | | | ASSEMBLY. | | | | | | 3) MISSING THE WALL DAMPER TO PROTECT THE DUCTWORK | | | WHERE THE 2ND STORY WALL IS LOCATED. 717.5.6 EXTERIOR | | | WALLS. (OLD EXTERIOR WALL) DUCTS AND AIR TRANSFER | | | OPENINGS IN FIRE-RESISTANCE-RATED EXTERIOR WALLS | | | REQUIRED TO HAVE PROTECTED OPENINGS IN ACCORDANCE WITH | | | SECTION 705.10 SHALL BE PROTECTED WITH LISTED FIRE | | | DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. | | | | | | | | | | | | BUILDING PROVISOS | | | | | | 1) PROVISO: PLEASE NOTE THAT THAT THE BIRTHING CENTER | | | SHALL COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR | | | BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND | | | PROGRAMMATIC PROVISIONS, THE AGENCY OF HEALTH CARE | | | ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES. | | | FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES | | | THAT THE AGENCY (AHCA) MAY ENFORCE THE | | | SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING | | | CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY | | | ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA | | | BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO | | | ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL- | | | OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF | | | THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE | | | ACCESSIBILITY CODE. | | | PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE | | | 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE | | | DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE | | | COMPLIANCE. | | | | | | 2) PROVISO: A SEPARATE PERMIT IS REQUIRED FOR FIRE | | | SPRINKLERS. IN THE 2017 EXISTING BUILDING CODE FOR | | | CHANGE OF OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. | | | SECTION 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER | | | SYSTEM IN THE PORTION OF THE BUILDING THAT REQUIRES A | | | FIRE SPRINKLER SYSTEM, WHEN SEPARATION (HORIZONTAL) IS | | | INSTALLED BY OTHER REQUIREMENTS IN THE CODE. SECTION | | | 1004 E. B. C. FIRE PROTECTION IS REQUIRED IN CHAPTER 9 | | | OF THE FBC-B. SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA | | | 13R SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN | | | GROUP R OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN | | | HEIGHT IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) | | | IN HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE | | | INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R. | | | | | | AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP | | | TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS | | | NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE | | | PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN | | | ACCORDANCE WITH NFPA 13R. | | | | | | 3) PROVISO: SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR | | | SHOWS A TABLE AND CHAIRS LISTED AS 120, AND LISTED | | | STAFF AREA, WILL ANY OF THE CUSTOMERS AND OR RELATIVE | | | EVER BE ABLE TO USE THIS AREA FOR EITHER SNACKS OR | | | MEALS? IF SO THEN COMPLIANCE WILL BE REQUIRED WITH THE | | | 2017 ACCESSIBILITY CODE SECTIONS: | | | | | | 3)(A) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. | | | EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES, | | | STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY | | | CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL | | | GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA | | | SCOPING PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 3)(B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 3)(C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 3(D) NEW COMMENT) SHEET A1.2 SHOWS A MICROWAVE OVER THE | | | STOVE, HEIGHT NOT GIVEN BUT MUST COMPLY WITH THE | | | ACCESSIBILITY CODE | | | 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1 | | | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE | | | REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH | | | REACH. | | | | | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES | | | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL | | | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT | | | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE | | | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS | | | (22.2 N) MAXIMUM. | | | | | | 4) PROVISO: REVISION REQUIRED. SHEET A7.01 HAS A WINDOW | | | AND DOOR SCHEDULE. THE WINDOW SCHEDULE INDICATES SEE | | | STRUCTURAL SHEETS FOR WIND DESIGN & PRESSURES. THE DOOR | | | SCHEDULE INDICATES SEE ELEVATIONS FOR WIND DESIGN AND | | | ASSOCIATED PRESSURES. A REVISION IS REQUIRED SHOWING | | | THE REQUIRED WIND DESIGN CRITERIA AND ASSOCIATED | | | PRESSURES, PLUS PRODUCT APPROVALS FOR ALL NEW WINDOWS, | | | EXTERIOR DOORS AND NEW ROOFING. | | | 4A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. | | | 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS , | | | (B) WINDOWS | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-02-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-02-11 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-02-05 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2019-02-11 08:30:12 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19010578 | | | ADD: 2717 POINSETTIA AVE. | | | CONT: PA TWIN MANAGEMENT/ CGC1525857 | | | TEL: 561-345-9054 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. FEB. 11/2019 | | | ACTION: DENIED | | | | | | 1) ARCHITECTURAL SHEETS IN THE ARCHITECTS TITLE BLOCK | | | IS MISSING: (6) THE PRINTED NAME AND THE | | | LICENSE/REGISTRATION NUMBER OF THE PERSON SEALING THE | | | DOCUMENT. | | | 61G1-16.004 TITLE BLOCK. ARCHITECT. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED | | | AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN | | | THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION | | | NUMBER OF THE PERSON SEALING THE DOCUMENT. | | | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE | | | REVISED | | | | | | 2) THE COVERSHEET LIST THE OCCUPANCY TYPE AS AN R3 | | | OCCUPANCY AND LIST THE CODE SECTION 310.5 OF THE 2017 | | | FBC-B AND QUOTING THE SECTION ON CARE FACILITIES THAT | | | PROVIDE ACCOMMODATIONS FOR FIVE OR FEWER PERSONS | | | RECEIVING CARE. WHAT THE DESIGNER HAS OVERLOOKED IS IN | | | THE CODE SECTION 310.5 THE RELEVANT WORDING PRIMARILY | | | PERMANENT IN NATURE. THE 2015 IBC COMMENTARY ON THE | | | SUBJECT OF CARE FACILITIES, THE INTENT IS TO ALLOW | | | PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR HOME, | | | ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER THAT | | | IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME, THIS IS | | | TO BE CONSIDERED LONG TERM. | | | | | | IN THE 2017 FBC-B SECTION 308.4.2 INSTITUTIONAL GROUP | | | I-2. FIVE OR FEWER PERSONS RECEIVING MEDICAL CARE. | | | A FACILITY WITH FIVE OR FEWER PERSONS RECEIVING MEDICAL | | | CARE SHALL BE CLASSIFIED AS GROUP R-3 OR SHALL COMPLY | | | WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED AN | | | AUTOMATIC SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE | | | WITH SECTION 903.3.1. THE COMMENTARY AGAIN DECLARES IT | | | TO ALLOW PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR | | | HOME, ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER | | | THAT IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME, | | | THIS IS TO BE CONSIDERED LONG TERM. | | | THE USE OF THE SPACE (FIRST & SECOND FLOOR) IS GOING TO | | | BE HOW WE REVIEW WHAT CODE REQUIREMENTS AN OCCUPANCY | | | CAN BE DECLARED. I HAVE MET WITH THE BUILDING OFFICIAL | | | ROBERT BROWN, ASSISTANT BUILDING OFFICIAL STEVEN | | | KENNEDY AND WITH SAMANTHA HILL THE CHIEF PLANS EXAMINER | | | ON THIS MATTER. AS DISCUSSED FOR THIS REVIEW WE ARE | | | LOOKING AT THE 1ST FLOOR AS A BUSINESS OCCUPANCY | | | OFFERING SERVICES SUCH AS A DOCTOR?S OFFICE AND OR | | | DENTIST WITH STATE REQUIREMENTS F. S. 383.309 REQUIRING | | | US TO ALSO LOOK INTO THE SPECIAL OCCUPANCY PROVISIONS | | | FOR BIRTHING CENTERS FOUND IN THE 2017 FBC-B CHAPTER 4 | | | AND SECTION 452 FOR BIRTHING CENTERS. | | | THIS REVIEW WILL ALSO LOOK AT THE BUILDING AS A MIXED | | | USE BUILDING. THE 2ND FLOOR AS A R2 OCCUPANCY SINCE THE | | | PLANS INDICATE THE KITCHEN ON THE 1ST FLOOR AS PART OF | | | THE BUSINESS OCCUPANCY, EVEN THOUGH THE PLANS STATE A | | | CARETAKERS QUARTERS AS PRIMARILY PERMANENT IN NATURE. | | | THE 1ST FLOOR AS A BUSINESS OCCUPANCY, SPECIAL | | | OCCUPANCY, SECTION 452 FOR BIRTHING CENTERS. | | | DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE, | | | INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS, | | | INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING, | | | EATING, COOKING AND SANITATION. | | | SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP, | | | WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING, | | | EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT | | | NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A | | | DWELLING UNIT ARE NOT SLEEPING UNITS. | | | | | | 2A) SHEET A1.02. IN A MIXED USE BUILDING THERE NEEDS TO | | | BE A HORIZONTAL FIRE BARRIER BETWEEN THE R2 OCCUPANCY | | | UPSTAIRS AND THE BUSINESS OCCUPANCY DOWNSTAIRS. SEE | | | FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES | | | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR | | | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME | | | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR | | | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO | | | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS | | | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. | | | 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL | | | ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT | | | FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE | | | RATING OF NOT LESS THAN THAT REQUIRED BY SECTION | | | 707.3.10. | | | 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL | | | ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT | | | FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE | | | RATING OF NOT LESS THAN THAT REQUIRED BY SECTION | | | 707.3.10. TABLE 707.3.10 WILL REQUIRE A 2 HOUR FIRE | | | BARRIER BETWEEN THE R2 OCCUPANCY ABOVE AND THE PORTION | | | OF THE BUSINESS OCCUPANCY DIRECTLY BELOW THE R2 | | | OCCUPANCY AS WELL AS BENEATH THE STAIR, 1ST FLOOR | | | SHOWER CEILING. | | | | | | 2B) SHEET A1.02. THE NEW STAIRWAY ADDITION WILL NEED TO | | | BE SEPARATED VERTICALLY AS WELL AS HORIZONTALLY, THE | | | VESTIBULE 2 BOTH HORIZONTALLY AS WELL AS VERTICALLY | | | TABLE 508.4 WITH A 2 HOUR FIRE BARRIER. | | | | | | 707.3.9 SEPARATED OCCUPANCIES. WHERE THE PROVISIONS OF | | | SECTION 508.4 ARE APPLICABLE, THE FIRE BARRIER | | | SEPARATING MIXED OCCUPANCIES SHALL HAVE A | | | FIRE-RESISTANCE RATING OF NOT LESS THAN THAT INDICATED | | | IN TABLE 508.4 BASED ON THE OCCUPANCIES BEING | | | SEPARATED. | | | | | | 2C) SHEET A1.02. VESTIBULE 2 ALSO SHOWS THE STAIR | | | WINDERS AT THE BOTTOM OF THE STAIRWELL. PLEASE INDICATE | | | BETWEEN STAIR 1 AND 2 IT APPEARS THE WINDER STAIR GOES | | | TO A POINT, THERE IS A DASHED LINE THAT COULD BE THE | | | HEADER ABOVE, PLEASE CLARIFY FOR CODE COMPLIANCE WITH | | | FBC-B 1011.4. THE 12-INCH (305 MM) DIMENSION SHALL BE | | | MEASURED FROM THE WIDEST POINT OF THE CLEAR STAIR WIDTH | | | AT THE WALKING SURFACE OF THE WINDER. WHERE WINDERS ARE | | | ADJACENT WITHIN THE FLIGHT, THE POINT OF THE WIDEST | | | CLEAR STAIR WIDTH OF THE ADJACENT WINDERS SHALL BE | | | USED. | | | | | | 3) PLEASE NOTE THAT THE DESIGNER OF RECORD CANNOT USE | | | NONSEPARATED OCCUPANCIES BETWEEN THE R2 OCCUPANCY AND | | | BUSINESS OCCUPANCY ON THE 1ST FLOOR, SECTION | | | 508.2.4.(2) TAKES YOU TO SECTION 420 SPECIAL | | | OCCUPANCIES FOR GROUPS I-1, R-1,R-2, R-3 AND R-4. | | | SECTION 420.2 AND 420.3 SEPARATION WALLS AND HORIZONTAL | | | SEPARATION BETWEEN DWELLING UNITS/ SLEEPING UNITS AND | | | OTHER OCCUPANCIES. | | | | | | 4) PLEASE ALSO REVIEW FLORIDA STATUTE 383.308 (B) FOR | | | FOOD SERVICES, IF JUST LIGHT SNACKS OR IF A FOOD | | | SERVICE IS PROVIDED, SPECIAL REQUIREMENTS SHALL BE MET | | | AS DEFINED IN RULES PROMULGATED PURSUANT TO CHAPTER | | | 381.0072 FOOD SERVICES PROTECTION. | | | | | | 5) PLEASE NOTE THAT THAT THE BIRTHING CENTER SHALL | | | COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR | | | BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND | | | PROGRAMMATIC PROVISIONS MAY APPLY. SEE AGENCY OF HEALTH | | | CARE ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES. | | | FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES | | | THAT THE AGENCY (AHCA) MAY ENFORCE THE | | | SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING | | | CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY | | | ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA | | | BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO | | | ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL- | | | OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF | | | THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE | | | ACCESSIBILITY CODE. | | | PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE | | | 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE | | | DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE | | | COMPLIANCE. | | | | | | 5.1) PLEASE SHOW COMPLIANCE WITH SECTIONS: FBC-B | | | 452.2.2.1. BIRTH ROOMS SHALL BE LOCATED TO PROVIDE | | | UNIMPEDED, RAPID ACCESS TO AN EXIT OF THE BUILDING | | | WHICH WILL ACCOMMODATE EMERGENCY TRANSPORTATION | | | VEHICLES. | | | | | | 5.2) 452.2.6 HALLWAYS AND DOORS PROVIDING ACCESS AND | | | ENTRY INTO THE BIRTH CENTER AND BIRTH ROOM SHALL BE OF | | | ADEQUATE WIDTH AND CONFORMATION TO ACCOMMODATE | | | MANEUVERING OF AMBULANCE STRETCHERS AND WHEELCHAIRS. | | | THE STRETCHER REQUIREMENTS ARE AMBULANCE STRETCHER 24 | | | INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS | | | THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL | | | POSITION. PLEASE SHOW THE STRETCHER GOING DOWN THE | | | CORRIDOR, THROUGH THE DOORWAY AND INTO THE BIRTHING | | | ROOMS FOR BOTH BIRTHING ROOMS. | | | | | | 6) PLEASE ALSO BE AWARE THAT THE KITCHEN BEING LOCATED | | | ON THE 1ST FLOOR, THE BUSINESS OCCUPANCY, COMPLIANCE | | | WITH SECTION 904.2.2 OF THE 2017 FBC-B FOR COMMERCIAL | | | HOOD AND DUCT SYSTEMS AND 904.3 THE INSTALLATION OF AN | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS TO BE INSTALLED IN | | | ACCORDANCE WITH THIS SECTION. | | | | | | 7) IN THE 2017 EXISTING BUILDING CODE FOR CHANGE OF | | | OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. SECTION | | | 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER SYSTEM IN THE | | | PORTION OF THE BUILDING THAT REQUIRES A FIRE SPRINKLER | | | SYSTEM, WHEN SEPARATION (HORIZONTAL) IS INSTALLED BY | | | OTHER REQUIREMENTS IN THE CODE. SECTION 1004 E. B. C. | | | FIRE PROTECTION IS REQUIRED IN CHAPTER 9 OF THE FBC-B. | | | SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA 13R SPRINKLER | | | SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN GROUP R | | | OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN HEIGHT | | | IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) IN | | | HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE | | | INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R. | | | | | | AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP | | | TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS | | | NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE | | | PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN | | | ACCORDANCE WITH NFPA 13R. | | | 8) IN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY PLAN, | | | JUST A FLOOR PLAN A1.02. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED. | | | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED | | | (SEE SECTION 503). | | | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | | SCHEMATIC FIRE SPRINKLERS | | | PRE-ENGINEERED SYSTEMS | | | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | OCCUPANCY LOAD | | | OCCUPANT LOAD AND EGRESS CAPACITIES | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION | | | DOORS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE | | | FOLLOWING: | | | SITE REQUIREMENTS | | | ACCESSIBLE ROUTE | | | VERTICAL ACCESSIBILITY | | | TOILET AND BATHING FACILITIES | | | DRINKING FOUNTAINS | | | | | | 9) PLEASE PROVIDE AN ITEMIZED LETTER FROM EITHER THE | | | DESIGNER OF RECORD OR THE CONTRACTOR ON THEIR | | | LETTERHEAD WHERE 20% OF THEIR BUDGET OR $30,000.00 | | | DOLLARS WILL BE SPENT IN MAKING ACCESSIBLE UPGRADES TO | | | THE 1ST FLOOR. PLEASE REVIEW THE FOLLOWING CODE SECTION | | | IN WHAT ORDER THESE FUNDS ARE TO BE SPENT. | | | | | | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.2 ACCESSIBLE | | | FEATURES IN THE EVENT OF DISPROPORTIONALITY. | | | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH | | | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS | | | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, | | | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE | | | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING | | | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE | | | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE | | | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE | | | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN | | | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST | | | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX | | | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE | | | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL | | | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND | | | ALARMS. | | | | | | 9A) PLEASE NOTE CURRENTLY THERE IS NO ACCESSIBLE | | | ENTRANCE. GOGGLE STREET VIEW SHOWS STEPS AND LANDING TO | | | THE FRONT DOOR. | | | | | | 9B) THE PLANS DO NOT SHOW TRAVEL DISTANCES AND IF A 2ND | | | EGRESS IS REQUIRED ON THE 1ST FLOOR AND THE VESTIBULE 2 | | | IS GOING TO BE USED AS THE 2ND REQUIRED EGRESS PLEASE | | | SHOW ACCOMMODATIONS FOR MANEUVERING OF AMBULANCE | | | STRETCHERS TO THE EXTERIOR OF THE BUILDING. | | | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF | | | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE | | | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 | | | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL | | | BUILDING CODE (2003 EDITION). | | | | | | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS | | | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY | | | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE | | | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. | | | | | | 9C) SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR SHOWS A | | | TABLE AND CHAIRS LISTED AS 120, AND LISTED STAFF AREA, | | | WILL ANY OF THE CUSTOMERS AND OR RELATIVE EVER BE ABLE | | | TO USE THIS AREA FOR EITHER SNACKS OR MEALS? IF SO THEN | | | COMPLIANCE WILL BE REQUIRED WITH THE 2017 ACCESSIBILITY | | | CODE SECTIONS: | | | 9C)(1) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. | | | EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES, | | | STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY | | | CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL | | | GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA | | | SCOPING PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 9C)(2) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 9C)(3) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 10) IMPACT FEES- PAPER SUBMITTALS | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 | | | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM | | | | | | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | 2019-02-05 16:54:46 | NOTES IN ERROR DELETED PV |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-09-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-09-18 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-09-18 |
Time |
14:48 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-09-11 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-09-11 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-09-11 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2019-09-11 07:56:28 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. GENERATOR NOW SHOWN AS FUTURE, WIRE SIZE | | | WILL BE REQUIRED AT TIME OF SUBMITTAL FOR GENERATOR | | | PERMIT. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. CORRECTED. | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. CORRECTED. | | | 17. CORRECTED. | | | 18. CORRECTED. | | | 19. CORRECTED. | | | 20. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 21. PLAN SETS ARE NOT IDENTICAL, SEVERAL SHEETS ARE | | | MISSING FROM ONE SET. THE OTHER SET HAS DUPLICATE | | | SHEETS BECAUSE THE OLD SHEETS WERE NOT REMOVED. PROVIDE | | | 2 IDENTICAL PLAN SETS FOR REVIEW WITH ALL CORRECTIONS. | | | WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-21 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-21 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2019-05-21 08:08:41 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | 2. CORRECTED. | | | 3. CORRECTED. GENERATOR NOW SHOWN AS FUTURE, WIRE SIZE | | | WILL BE REQUIRED AT TIME OF SUBMITTAL FOR GENERATOR | | | PERMIT. | | | 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | GENERATORS, SIGNS, AND SITE LIGHTING(WHERE APPLICABLE) | | | ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS | | | PRESENT. WPB FBC 105.1, 107.2.1 (NOTE NOT PROVIDED.) | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. CORRECTED. | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. CORRECTED. | | | 17. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 18. NOW THAT GENERATOR IS SHOWN AS FUTURE, HOW WILL THE | | | ESSENTIAL ELECTRICAL BE MAINTAINED? NEC 517.45 | | | 19. TRANSFER SWITCH IS NOW ALSO SHOWN AS FUTURE. WILL | | | THIS BE INSTALLED AT TIME OF GENERATOR INSTALLATION, OR | | | WILL THIS BE INSTALLED AS PART OF THE SERVICE? PROVIDE | | | CLARIFICATION. WPB FBC 107.2.1 | | | 20. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-02-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-14 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-14 |
Time |
07:00 |
Sent To |
I |
|
| Notes |
| 2019-02-14 12:43:07 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | 2. RISER NOTE 3 SHOWS 1/0 CONDUCTORS AS SERVICE | | | CONDUCTORS AND FEEDER TO PANEL A. THIS WIRE SIZE IS NOT | | | RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC | | | 310.15(B)(16) | | | 3. RISER NOTE 7 SHOWS 1/0 CONDUCTORS FROM GENERATOR TO | | | TRANSFER SWITCH. THIS WIRE IS NOT RATED TO HANDLE THE | | | CALCULATED LOAD, OR THE OUTPUT OF THE GENERATOR. | | | PROVIDE CORRECTION. NEC 310.15(B)(16) | | | 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | GENERATORS, SIGNS, AND SITE LIGHTING(WHERE APPLICABLE) | | | ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS | | | PRESENT. WPB FBC 105.1, 107.2.1 | | | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. SHOW ON PLAN. NEC 250.94 | | | 6. ELECTRICAL SPECIFICATION 2.C STATES THAT NM CABLE | | | SHALL NOT BE USED. HOWEVER, THE PLAN STATES THAT 2ND | | | FLOOR CIRCUITS WILL BE RE-USED. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. WPB FBC 107.2.1 | | | 7. PROVIDE DETAIL FOR WIRING METHODS IN PATIENT CARE | | | AREAS. IDENTIFY ON PLAN WHICH AREAS WILL BE REQUIRED TO | | | MEET THESE WIRING METHODS. WPB FBC 107.2.1; NEC 517 | | | 8. LOAD CALCULATION PROVIDED IS THE TYPE USED FOR A | | | DWELLING UNIT. THIS WILL NOT BE A DWELLING UNIT. | | | PROVIDE ACCURATE LOAD CALCULATION. NEC 220 | | | 9. ALL RECEPTACLE OUTLETS IN LAUNDRY THAT ARE WITHIN 6 | | | FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE | | | CORRECTION. NEC 210.8 | | | 10. PROVIDE LOCATION OF PANEL B ON PLAN TO CONFIRM CODE | | | COMPLIANCE. WPB FBC 107.2.1 | | | 11. BIRTH ROOM 1, RECEPTACLE OUTLETS THAT ARE WITHIN 6 | | | FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE | | | CORRECTION. NEC 210.8 | | | 12. BIRTH ROOM 1 SHOWS A RECEPTACLE OUTLET LOCATED IN | | | THE DOORWAY. PROVIDE CLARIFICATION AND/OR CORRECTION. | | | WPB FBC 107.2.1 | | | 13. CONSULTATION ROOM 2, RECEPTACLE OUTLETS THAT ARE | | | WITHIN 6 FEET OF THE SINK REQUIRE GFCI PROTECTION. | | | PROVIDE CORRECTION. NEC 210.8 | | | 14. EXAM ROOM, RECEPTACLE OUTLETS THAT ARE WITHIN 6 | | | FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE | | | CORRECTION. NEC 210.8 | | | 15. KITCHEN, RECEPTACLE OUTLETS THAT ARE WITHIN 6 FEET | | | OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE | | | CORRECTION. NEC 210.8 | | | 16. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | 17. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2019-09-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-09-19 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2019-09-19 12:07:07 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ONE PLAN SET DOES NOT HAVE SHEET ES1.01 ATTACHED. | | | | | | IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS | | | DEFICIENCY WAS PROVISOED. | | | | | | PLEASE REVIEW AND PROVIDE SHEET AS APPLICABLE FOR CONST | | | SET. | | | | | | | | | 2) SHEET ES1.01 - THERE ARE INDICATIONS OF FUTURE WORK. | | | | | | THE PROPOSED DOMESTIC FIRE SPRINKLER SYSTEM. EMERGENCY | | | GENERATOR AND FIRE PIT SHALL ALL BE DONE UNDER SEPARATE | | | PERMITS AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND ENSURE FUTURE COMPLIANCE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-08-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-08-20 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2019-08-20 14:37:32 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ONE PLAN SET DOES NOT HAVE SHEET ES1.01 ATTACHED. | | | | | | IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS | | | DEFICIENCY WAS PROVISOED. | | | | | | PLEASE REVIEW AND PROVIDE SHEET AS APPLICABLE FOR CONST | | | SET. | | | | | | | | | 2) SHEET ES1.01 - THERE ARE INDICATIONS OF FUTURE WORK. | | | | | | THE PROPOSED DOMESTIC FIRE SPRINKLER SYSTEM. EMERGENCY | | | GENERATOR AND FIRE PIT SHALL ALL BE DONE UNDER SEPARATE | | | PERMITS AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND ENSURE FUTURE COMPLIANCE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-21 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2019-05-21 10:56:41 | 5/21/19 | | | | | | THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONTIORED. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-01-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-01-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-01-25 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2019-01-25 11:29:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) FRONT SHEET: THERE IS AN INDICATION OF A BUILDING | | | CODE OCCUPANCY CLASSIFICATION; HOWEVER, THERE IS NO | | | INDICATION OF FLORIDA FIRE PREVENTION CODE | | | CLASSIFICATION. | | | | | | PLEASE PROVIDE A CLEAR NARRATIVE EXPLAINING WHAT OCCURS | | | AT THIS FACILTY AND HOW MANY PATIENTS/OCCUPANTS. | | | | | | PLEASE PROVIDE THE OCCUPANY CLASSIFICATION PER THE | | | FFPC. | | | | | | ENSURE THAT THE SUBMITTED PLANS ARE COMPLIANT WITH THAT | | | OCCUPANCY. | | | | | | | | | | | | 2) FRONT SHEET: THERE IS AN INDICATION OF A FIRE | | | SPRINKER SYSTEM. | | | | | | FOR CLARIFICATION PURPOSES; IS A FIRE SPRINKLER SYSTEM | | | BEING PROVIDED FOR THIS FACILTIY ? | | | | | | IF SO, F.A.C. DOCUMENTS ARE REQUIRED TO BE SUBMITTED | | | WITH THIS MASTER PERMIT. | | | | | | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING | | | DOCUMENTS. | | | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF | | | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR | | | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING | | | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S | | | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, | | | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING | | | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: | | | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS | | | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A | | | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND | | | EXPERIENCE. | | | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY | | | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH | | | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS | | | ARE INTENDED TO CONFORM TO. | | | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF | | | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF | | | THE SYSTEM. | | | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT | | | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING | | | DOCUMENTS. | | | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY | | | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE | | | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE | | | STATED PURPOSE OF THESE RESPONSIBILITY RULES. | | | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND | | | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING | | | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR | | | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE | | | OF SUCH DOCUMENTS. | | | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN | | | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR | | | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO | | | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER | | | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS | | | RESPONSIBILITY. | | | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY | | | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST | | | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. | | | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY | | | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN | | | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC | | | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND | | | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE | | | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES | | | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE | | | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A | | | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR | | | AGENCY APPROVAL ACTION ON THE SAME PROJECT. | | | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW | | | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW | | | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-09-10 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-09-10 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-09-05 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2019-09-10 13:49:30 | GAS COMMENTS: APPROVED W/PROVISO | | | | | | 1. ONE (1) EACH STAMPED AND SEALED PLAN SHEET ES1.01 | | | SHALL BE PROVIDED FOR REVIEWERS? NOTATIONS AS | | | APPLICABLE INTO SET OF PLANS WHICH WAS MISSING THIS | | | PAGE. | | | 2. FUTURE GENERATOR AND ASSOCIATED GAS PIPING SHOWN ON | | | PLAN SHEET ES1.01 IS NOT PART OF THIS PROJECT AND SHALL | | | REQUIRE A SEPARATE PERMIT. | | | 3. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA | | | SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE FIRE | | | PIT INDICATING 50 MBTU. THE DOCUMENTS SHALL BE | | | SUBMITTED, APPROVED AND ON SITE PRIOR TO THE FIRST GAS | | | ROUGH INSPECTION. | | | 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA | | | SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE | | | TANKLESS WATER HEATERS.INDICATING 199 MBTU EACH. THE | | | DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON SITE | | | PRIOR TO THE FIRST GAS ROUGH INSPECTION. | | | 5. SEE PLAN SHEET ES1.01 FOR LOCATION OF FPU GAS METER. | | | 6. RE: PLAN SHEET P1.02; PRIOR TO FINAL INSPECTION, A | | | RECORD DRAWING SHALL BE PROVIDED NOTING THE FIRE PIT AS | | | 50 MBTU. | | | 7. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR | | | MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL | | | GAS INSPECTION. | | | CALL 561-805-6692 FOR FURTHER INFORMATION. | | | 8. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-05-30 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-05-28 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2019-05-30 15:11:44 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 30A | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | | | | 2ND REVIEW | | | GAS COMMENTS: DENIED | | | 1. EMERGENCY GENERATOR IS INDICATED FUTURE. PLEASE | | | CLARIFY AS THIS PRESENTS LOGISTICAL COMPLICATIONS FOR A | | | COMPLETED PROJECT AS WELL AS THE PERMITTING PROCESS. | | | 2. SUBMIT ON THE ISOMETRIC DRAWING THAT WHICH CLEARLY | | | SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC FG | | | SECS. 402.4.1, 402.4.2. | | | 3. PER WPB FBC 107.2.1, PROVIDE A SCHEDULE INDICATING | | | GAS TYPE AND CALCULATIONS EACH FOR THE 2 LB. SYSTEM AND | | | THE .5 LB. SYSTEM. LIST APPLIANCES WITH BTU LOAD WITH | | | BTU TOTAL AND PROVIDE DISTANCE FROM POINT OF DELIVERY | | | TO THE MOST REMOTE OUTLET IN THE SYSTEM AND SIZE | | | ACCORDINGLY USING THE APPROPRIATE TABLES. ALTHOUGH THE | | | SIZING SHOWN WAS PROBABLY DONE CORRECTLY IT NEEDS TO BE | | | CLEARLY NOTED ON THE PLANS. IT WOULD BE HELPFUL TO | | | INCLUDE COPIES OF THE TABLES REFERENCED TO HELP THE | | | REVIEW PROCESS. | | | 4. WILL THE DOWNSTREAM MANIFOLD AT THE GAS METER AND | | | THE PIPING BETWEEN APPLIANCE VALVES AND APPLIANCE | | | REGULATORS BE GALVANIZED? IF SO, PLEASE INCLUDE IN 2 | | | LB. CALCULATIONS REFERENCING THE PROPER TABLE AND | | | INDICATE ON THE PLANS. BE SURE TO USE THE FURTHEST | | | POINT MEASUREMENT WHEN CALCULATING. INDICATE ALL | | | GALVANIZED PIPING ON THE GAS RISER. | | | 5. THE GAS RISER SHOWS 1? TO THE WATER HEATERS, | | | BRANCHING TO ?? TO EACH OF THE TWO APPLIANCES AS NOTED | | | IN THE RESPONSE LETTER. HOWEVER THE TANKLESS HOT WATER | | | SYSTEM DETAIL SHOWS ?? TO THE BRANCHES. PER WPB FBC | | | 107.2.1, PLEASE RECONCILE DETAIL WITH THE GAS RISER. | | | 6. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR ALL GAS APPLIANCES AND EQUIPMENT PER WPB FPC | | | 107.2.1. | | | 7. PER WPB FBC 107.2.1, INDICATE ON P1.01 THE DISTANCE | | | FROM THE INTERSECTION OF THE BRANCH TO THE FIRE PIT TO | | | FPU METER. ARCHITECT SHALL LOCATE THE FPU METER ON | | | A0.02. AN APPROVED PLUMBING REVIEW WILL DEPEND UPON | | | THIS REQUIREMENT BEING MET. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19010578 2717 POINSETTIA AVE | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-02-12 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-12 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-12 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2019-02-12 15:16:31 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1. SHOW THE LOCATION FOR THE EMERGENCY GENERATOR AND | | | FPU METER PER WPB FBC 107.2.1. | | | 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS | | | APPLIANCES AND EQUIPMENT PER WPB FPC 107.2.1. | | | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE | | | KITCHEN RANGE PER FBC FG304.1. | | | 4. SUBMIT MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON | | | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR PER | | | FBC FG 410.1. | | | 5. PROVIDE TRANSITION COMPATIBLE WITH GAS TYPE AS | | | REQUIRED BY FBC FG 403.11 (3) FROM PE PIPING IN THE | | | GROUND TO GALVANIZED PIPING ABOVE GROUND ON THE | | | HIGH-PRESSURE SIDE OF THE REGULATOR TO COMPLY WITH FBC | | | FG 404.17.1 OR PROVIDE MANUFACTURER?S SPECIFICATION AND | | | INSTALLATION INSTRUCTIONS FOR FUEL GAS SERVICE HEAD | | | ADAPTER RISER TO REGULATOR TO COMPLY WITH FBC FG | | | 404.17.1 EXCEPTION 1. | | | 6. NOTE MATERIAL TYPE (SCHEDULE 40 GALVANIZED OR FUEL | | | GAS SERVICE HEAD RISER ADAPTER), SIZE AND APPLICABLE | | | SIZING TABLE FOR ABOVE GROUND PIPING ON LOW PRESSURE | | | SIDE OF THE REGULATOR. | | | 7. INDICATE SIZE OF LOW PRESSURE PIPING TO EMERGENCY | | | GENERATOR PER WPB FBC 107.2.1. | | | 8. DETAIL ON P2.01 FOR TANKLESS WATER HEATERS INDICATES | | | 3/4" LOW PRESSURE PIPING TO THE TWO HEATERS AS OPPOSED | | | TO 1" ON THE GAS RISER. PLEASE CLARIFY AND CORRECT PER | | | WPB FBC 107.2.1. | | | 9. PLEASE NOTE ON THE PLANS THE TYPE OF GAS PROVIDED | | | PER WPB FBC 107.2.1. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, | | | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW | | | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-09-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-09-19 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-09-17 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2019-09-18 14:13:46 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-09-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-15 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-05-30 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-05-30 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2019-05-28 13:10:22 | TO J.SMITH DESK | | | | | | | | 2019-05-20 14:31:02 | B07 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-22 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2019-01-22 14:36:05 | B06 | | 2019-01-22 11:43:38 | APPLICATION COMPLETE THIS DATE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-09-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-09-27 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-09-27 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2019-09-27 11:18:23 | MU 2019 029591 $4,632.87 PAID | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-02-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-02-11 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-02-11 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2019-02-11 08:31:56 | IMPACT FEES- PAPER SUBMITTALS | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 | | | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM | | 2019-01-22 12:22:47 | THIS WILL REQUIRE PBC IMPACT FEE REVIEW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-09-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-09-12 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-09-12 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-05-21 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-05-21 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2019-05-21 14:52:35 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19010578 | | | 5/21/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS A1.02 & M1.01: THE REVISED PLANS INDICATE A | | | 2HR. FIRE-RATED CEILING ASSEMBLY BETWEEN THE 1ST AND | | | 2ND STORY OF THE TWO-STORY SECTION OF THE BUILDING. | | | LISTED CEILING RADIATION DAMPERS ARE REQUIRED FOR THE | | | DUCTS AND DIFFUSERS PENETRATING THE ASSEMBLY- SECTION | | | 607.2 FBC M. | | | | | | 2) A1.02 & M1.01: THE 6X6" AND 6" ROUND AC DUCTS | | | PENETRATING INTO THE VESTIBULE AND INTERIOR EXIT | | | STAIRWAY ARE PROHIBITED IN ACCORDANCE WITH SECTIONS | | | 1023.5 AND 1023.6 FBC B. | | | | | | 3) A1.02 & M1.01: THE DRYER AND BATH EXHAUST DUCTS | | | SHALL NOT PENETRATE INTO THE FIRE-RATED INTERIOR EXIST | | | STAIRWAY WALL PER SECTION 1023.5 FBC B. | | | | | | 4) M1.01: BECAUSE THE NEW BIRTHING CENTER IS A CHANGE | | | OF OCCUPANCY FROM R-3 TO B, THE AIR HANDLER (AH-1) IS | | | NO LONGER ALLOWED TO BE INSTALLED IN THE ATTIC- SEE | | | SECTION C403.2.9.6 FBC EC AND RELOCATE THE UNIT. | | | | | | 5) M1.01: THE REQUESTED AC COOLING AND HEATING | | | CALCULATIONS WERE NOT PROVIDED (SEE 1ST REVIEW COMMENT | | | #2). THE ENGINEER'S NARRATIVE RESPONSE STATES THAT THE | | | SYSTEMS ARE LIKE FOR LIKE CHANGEOUTS HOWEVER THERE IS A | | | PARTIAL MANUAL J HEAT LOAD CALCULATION SHOWN ON THE | | | PLAN. PLEASE NOTE THAT ACCA MANUAL J CALCULATIONS ARE | | | FOR SIZING SYSTEMS IN RESIDENTIAL OCCUPANCIES UNDER 3 | | | STORIES. BECAUSE OF THE CHANGE OF OCCUPANCY AND | | | INCREASED HEAT LOAD FORM LIGHTING, EQUIPMENT, PEOPLE | | | ETC, IT IS NECESSARY TO PROVIDE SIZING CALCULATIONS | | | USING MANUAL N FOR THE BIRTHING CENTER, AND MANUAL J | | | FOR THE 2ND FLOOR APARTMENT- REFER TO SECTIONS C403.2.1 | | | AND R403.6.1. AS PREVIOUSLY NOTED IN THE 1ST REVIEW | | | COMMENT, THE 5-TON SYSTEM AH-2 APPEARS TO BE OVERSIZED | | | FOR THE APPROXIMATE 778 SF. APARTMENT. | | | | | | 6) M1.01: 2ND REQUEST FOR A DUCT SMOKE DETECTOR TO BE | | | INSTALLED IN THE SUPPLY AIR SYSTEM OF AH-2 PER SECTION | | | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED | | | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE | | | SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF | | | SUPPLY AIR | | | | | | 7) M1.01: THE NEW KITCHEN EXHAUST HOOD SHALL BE FOR | | | DOMESTIC USE PER SECTION 505.4 FBC M. PLEASE SUBMIT | | | MANUFACTURER'S SPECIFICATIONS AND NOTE THAT MAKEUP AIR | | | MAY BE REQUIRED PER SECTION 505.2 FBC M. | | | | | | 8) M1.01: 2ND REQUEST FOR MANUFACTURER'S SPECIFICATIONS | | | FOR THE CLOTHES DRYER- SECTION 504.1 FBC M. PLEASE NOTE | | | THAT MAKEUP AIR SHALL BE PROVIDED IF THE APPLIANCE HAS | | | AN EXHAUST CAPACITY EXCEEDING 200 CFMS- SECTION 504.6 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-02-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-02-11 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-02-11 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2019-02-11 17:14:46 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19010578 | | | 2/11/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) DESIGN CRITERIA: PLEASE PROVIDE A LIST OF CURRENT | | | CODES AND STANDARDS USED IN THE DESIGN OF THE NEW | | | BIRTHING CENTER. THE PROPOSED CENTER IS CLASSIFIED AS A | | | CHANGE OF OCCUPANCY PER SECTION 202 FBC EX. PLEASE | | | REFER TO SECTION 301.1 FBC EX AND INDICATE WHICH | | | COMPLIANCE METHOD WILL BE USED, AND INCLUDE THE CODE | | | AND COMPLIANCE INFORMATION WITH THE NOTES SHOWN ON THE | | | COVER SHEET. THE FOLLOWING REVIEW COMMENTS ARE BASED ON | | | THE CURRENT PLANS WHICH MAY BE SUBJECT TO CHANGE BASED | | | ON THE COMPLIANCE METHOD CHOSEN, AND BASED ON REQUIRED | | | CHANGES PER THE BUILDING REVIEW COMMENTS. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. | | | PLEASE NOTE THAT AC-2 APPEARS TO BE OVERSIZED FOR THE | | | PROPOSED 2ND FLOOR ROOMS AND SPACES. | | | | | | 3) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTIONS C505.1 | | | AND C101.5 FBC EC. | | | | | | 4) MINIMUM VENTILATION RATES FOR THE FACILITY SHALL BE | | | IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M, AND THE | | | FOLLOWING SECTIONS FROM THE FBC B. PLEASE COMPLY BY | | | PROVIDING A VENTILATION SCHEDULE ON THE PLAN SHOWING | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR AND AND | | | EXHAUST AIR. | | | 452.2.8.2 | | | WHEN MECHANICAL VENTILATION OR COOLING SYSTEMS ARE | | | EMPLOYED, THE SYSTEM SHALL BE PROPERLY MAINTAINED AND | | | KEPT CLEAN. INTAKE AIR DUCTS SHALL BE DESIGNED AND | | | INSTALLED SO THAT DUST OR FILTERS CAN BE READILY | | | REMOVED. IN RESIDENCE AREAS AND SEGREGATION ROOMS WITH | | | SOLID DOORS, MECHANICAL VENTILATION SYSTEMS SHALL | | | PROVIDE A MINIMUM OF 10 CUBIC FEET (0.3 M3) OF FRESH OR | | | FILTERED RECIRCULATED AIR PER MINUTE FOR EACH CLIENT | | | OCCUPYING THE AREA. | | | 452.2.9 | | | ADEQUATE HEATING AND COOLING FACILITIES SHALL BE | | | PROVIDED TO MAINTAIN A MINIMUM TEMPERATURE OF 68 | | | DEGRESS F (20 DEGREES C) AND MAXIMUM TEMPERATURE OF 78 | | | DEGREES F (26 DEGREES C) AT A POINT 20 INCHES (508 MM) | | | ABOVE THE FLOOR. | | | 452.2.10 | | | ALL HEATING DEVICES SHALL COMPLY WITH FIRE PREVENTION | | | PROVISIONS FOUND IN RULE 69A-3, FIRE PREVENTION, | | | GENERAL PROVISION, FLORIDA ADMINISTRATIVE CODE. | | | | | | 5) SHEET M1.01: EXHAUST VENTILATION AT A RATE OF 1.0 | | | CFMS PER SF. IS REQUIRED FOR THE LAB AND RECIRCULATION | | | OF AIR IS PROHIBITED, OR LIMITED TO A MAXIMUM OF 10 | | | PERCENT OF AIR RECIRCULATED FROM THE ROOM- TABLE | | | 403.3.1.1 FOOTNOTE G. | | | | | | 6) M1.01: A DUCT SMOKE DETECTOR IS REQUIRED IN THE | | | SUPPLY AIR SYSTEM OF AH-2 PER SECTION 606.2.1. PLEASE | | | NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | 7) M1.01: NO REFLECTIVE CEILING PLAN HAS BEEN | | | SUBMITTED, BUT AH-1 AND DH-1 APPEAR TO BE ABOVE HARD | | | CEILINGS. CLARIFY HOW ACCESS WILL BE PROVIDED FOR | | | SERVICE AND REPLACEMENT OF THE UNITS- SECTION 306.1 FBC | | | M. | | | | | | 8) M1.01: NO ROOMS HAVE BEEN DESIGNATED FOR STORAGE OF | | | MEDICAL GASES. WILL ANESTHESIA BE PROVIDED TO PATIENTS, | | | AND IF SO, HOW WILL IT BE ADMINISTERED AND STORED AT | | | THE FACILITY? | | | | | | 9) M1.01: EXHAUST VENTILATION IS REQUIRED FOR THE | | | KITCHEN PER TABLE 403.3.1.1 FBC M, AND AN EXHAUST HOOD | | | IS REQUIRED OVER THE RANGE IN ACCORDANCE WITH EITHER | | | SECTION 507.1 OR 507.1.2 DEPENDING ON WHETHER A | | | COMMERCIAL OR DOMESTIC COOKING APPLIANCE IS BEING | | | INSTALLED. | | | | | | 10) M1.01: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE | | | NEW AIR HANDLERS. SHOW THE TYPE AND SIZE OF CONDENSATE | | | PIPING, THE PIPING RUNS, AND DISPOSAL LOCATIONS- | | | SECTION 307.2 FBC M. | | | | | | 11) M1.01: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | CLOTHES DRYER- SECTION 504.1 FBC M. PLEASE NOTE THAT | | | MAKEUP AIR SHALL BE PROVIDED IF THE APPLIANCE HAS AN | | | EXHAUST CAPACITY EXCEEDING 200 CFMS- SECTION 504.6 | | | | | | 12) PROVIDE ENGINEERING FOR INSTALLATION OF THE OUTDOOR | | | AC CONDENSERS- SECTION 301.15 FBC M. | | | | | | 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS | | | RANGE- SECTION 623.1 FBC FG. | | | | | | 14) SHOW THE LOCATION FOR THE EMERGENCY GENERATOR AND | | | SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 616.1 FBC | | | FG. PROVIDE A NARRATIVE INDICATING WHICH ESSENTIAL | | | SYSTEMS WILL BE POWERED BY THE SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-09-05 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-09-05 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-09-05 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2019-09-05 16:43:35 | PLUMBING COMMEMTS:APPROVED WITH PROVISO | | | 1. RE: OCCUPANT LOAD. AS DIRECTED BY ROBERT BROWN, | | | BUILDING OFFICIAL, CITY OF WEST PALM BEACH, IN | | | CONVERSATION WITH ROBERT BROWN, JIM WHITMER AND JERALD | | | SMITH, ASSIGN THREE (3) EACH CUSTOMERS TO EACH OF THE | | | TWO (2) BIRTHING ROOMS. DEDUCT SQUARE FOOTAGE OF THE | | | TWO ROOMS, INCLUDING BATHROOMS (551.5 SQ. FT.) FROM THE | | | TOTAL SQUARE FOOTAGE (2035.75 SQ. FT.) LEAVING A TOTAL | | | OF 1480 SQ. FT./100=15 OCCUPANTS | | | 2. ROOMS 122, 123 AND 126 SHALL COMPLY WITH FBC ACC | | | 212.3, HAVING CLEAR FLOOR SPACE (FBC ACC 606.2)AND | | | PROVIDE A MAXIMUM HEIGHT OF 34? TO TOP OF COUNTER OR | | | SINK RIM, WHICHEVER IS HIGHER (FBC ACC 606.3), OR THE | | | OWNER SHALL PROVIDE A LETTER, SIGNED AND DATED STATING | | | THAT IF ANY EMPLOYEE OR POTENTIAL EMPLOYEE SHOULD | | | REQUIRE ACCESSIBILITY TO PERFORM THEIR DUTIES IN ANY OF | | | THE STATED ROOMS THAT THE OWNER SHALL BRING SAID ROOMS | | | INTO COMPLIANCE. | | | 3. A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW | | | PREVENTOR. PROVIDE CERTIFICATION DOCUMENTS AT FINAL | | | INSPECTION. | | | 4. PROVIDE SPECIFICATION SHEETS FOR TANKLESS WATER | | | HEATERS SHOWING INTEGRAL RECIRCULATING PUMPS. SUBMITTAL | | | SHALL BE SUBMITTED, APPROVED AND IN PLACE PRIOR TO | | | FINAL INSPECTION. | | | 5. RE: P2.02; WATER RISER DIAGRAM. PROVIDE FULL OPEN | | | ACCESSIBLE VALVE ON EACH DOWNFEED PIPE PER FBC PL | | | 606.1(5) AND 606.3. VALVES SHALL BE IDENTIFIED PER FBC | | | PL 606.4 | | | 6. PROVIDE ANTI-SCALD SHOWER CONTROL VALVE FOR SECOND | | | FLOOR SHOWER PER FBC PL 424.3. | | | 7. PROVIDE TEMPERATURE LIMITING DEVICE FOR P-6 THERAPY | | | TUBS ON GROUND FLOOR AND FOR THE SECOND FLOOR BATHTUB | | | PER FBC PL 423.5 | | | 8. WASHING MACHINE SHUT OFF VALVES SHALL BE ACCESSIBLE | | | PER FBC PL 606.3. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-05-30 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-05-28 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2019-06-04 10:28:35 | ADDED COMMENTS EMAILED 6/4/2019 TO AUSTIN DUFFY OF PA | | | TWIN MANAGEMENT | | | REGARDING THE BIRTHING CENTER AT 2717 POINSIATTIA AVE; | | | PERMIT #19010578 | | | PLEASE NOTE THAT I PERFORMED A COMPREHENSIVE REVIEW OF | | | THE PLUMBING ON 5/30/2019. AFTER ADDITIONAL | | | CONSIDERATION I WANT TO BRING SOME ADDITIONAL POTENTIAL | | | ISSUES TO LIGHT THAT SHOULD BE CONSIDERED BY THE | | | DESIGNERS OF RECORD. PLEASE FORWARD TO THOSE DESIGN | | | PROFESSIONALS FOR THEIR CONSIDERATION IN PREPARING THE | | | NEXT SUBMITTAL. | | | ITEM 1: PLEASE NOTE THE FOLLOWING SECTIONS OF THE | | | FLORIDA BUILDING CODE. | | | ? 452.1SCOPE. | | | ALL BIRTHING CENTERS SHALL COMPLY WITH THE FOLLOWING | | | DESIGN AND CONSTRUCTION STANDARDS AS DESCRIBED HEREIN. | | | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS | | | MAY APPLY. SEE AGENCY OF HEALTH CARE ADMINISTRATION | | | [AHCA] RULE 59A-11, FLORIDA ADMINISTRATIVE CODE AND | | | CHAPTER 383, FLORIDA STATUTES. | | | | | | ? FBC 452.2.2.3 | | | A SEPARATE SPACE FOR A CLEAN AREA AND A CONTAMINATED | | | AREA; IF IT IS NOT FEASIBLE TO PROVIDE SUCH SEPARATE | | | AREAS, SPECIAL PROCEDURES SHALL BE ESTABLISHED FOR THE | | | DISPOSAL OF INFECTIOUS WASTE. SANITARY WASTE | | | CONTAINERS, SOILED LINEN CONTAINERS, STORAGE CABINETS | | | AND AN AUTOCLAVE, PRESSURE COOKER OR OTHER EFFECTIVE | | | STERILIZATION EQUIPMENT SHALL BE AVAILABLE. | | | ? 452.2.11LAUNDRY. | | | 452.2.11.1 | | | WHERE LAUNDRY FACILITIES ARE PROVIDED, LAUNDRY | | | FACILITIES SHALL BE OF SOUND CONSTRUCTION AND SHALL BE | | | IN GOOD REPAIR AND CLEAN. ADEQUATE SPACE SHALL BE | | | PROVIDED AND AREAS SHALL BE DESIGNATED FOR THE | | | SEPARATION OF CLEAN AND SOILED CLOTHING, LINEN AND | | | TOWELS. | | | | | | PLEASE REVIEW THE PLANS TO INSURE COMPLIANCE WITH THESE | | | SECTIONS. IF SPECIAL PROCEDURES FOR DISPOSAL OF | | | INFECTIOUS WASTE ARE TO BE EMPLOYED, THEN PLEASE STATE | | | THE SAME ON THE PLANS TO SHOW COMPLIANCE. | | | DISCHARGES FROM AUTOCLAVES AND OTHER STERILIZERS TO THE | | | SANITARY SYSTEM SHALL COMPLY WITH FBC PL CHAPTER 8 AND | | | SECTION 713. | | | | | | ITEM 2: BIRTHING TUB DRAINAGE | | | ? 452.2.3.4 | | | ALL FLOOR SURFACES, WALL SURFACES, WATER CLOSETS, | | | LAVATORIES, TUBS, SHOWERS, SHALL BE KEPT CLEAN, AND ALL | | | APPURTENANCES OF THE STRUCTURES SHALL BE OF SOUND | | | CONSTRUCTION, PROPERLY MAINTAINED, IN GOOD REPAIR AND | | | FREE FROM SAFETY HAZARDS. | | | REGARDING THE BIRTHING TUBS, THE ELIMINATION OF THE | | | OVERFLOW WAS DONE TO ELIMINATE BACTERIA FORMING IN THAT | | | SPACE. HOWEVER, THE TUB WASTE IS A DIRECT CONNECTION TO | | | THE SANITARY WHICH CAN ALLOW A STOPPAGE TO BACK UP INTO | | | THE TUB POTENTIALLY INTRODUCING HAZARDOUS BACTERIA INTO | | | THE VESSEL. THIS CONDITION CAN BE ELIMINATED BY | | | DISCHARGING THE TUB DRAIN INTO A TRAPPED AND VENTED | | | INDIRECT WASTE RECEPTOR WITH AN AIR GAP. IF THE TRAPPED | | | AND VENTED DIRECT CONNECTION TO THE SANITARY CONTINUES | | | TO BE THE CHOICE BY THE DESIGN ENGINEER THEN IT MUST BE | | | INSTALLED IN A MANNER THAT DOES NOT ALLOW THE FIXTURE | | | DRAIN TO CONNECT TO THE VENT BELOW THE TRAP. | | | | | 2019-05-30 13:53:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 30A | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | PLEASE NOTE THAT THE LETTER SIGNED AND SEALED, DATED | | | 5/21/2019, PROVIDED BY STUDIO SR ARCHITECTURE AND | | | DESIGN REQUESTING THAT OVERFLOWS NOT BE REQUIRED FOR | | | THE BIRTHING TUB(S) HAS BEEN REVIEWED BY THIS | | | DEPARTMENT AND THE TUB(S) ARE APPROVED AS NOTED ON THE | | | SUBMITTALS. | | | | | | PLUMBING COMMEMTS: DENIED | | | | | | 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL | | | PLANS. THE FOLLOWING COMMENTS ARE OFFERED AS A GUIDE | | | BUT MAY NOT BE ALL INCLUSIVE. ALL REQUIREMENTS MUST BE | | | SATISFACTORILY ADDRESSED ON THE PLANS PRIOR TO A | | | PLUMBING REVIEW APPROVAL. | | | A. 212.3 SINKS. WHERE SINKS ARE PROVIDED, AT LEAST 5 | | | PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED | | | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. | | | B. PROVIDE PLAN VIEW DETAILS OF KITCHEN CONFORMING TO | | | FBC ACC 804.3.1 | | | C. PROVIDE ELEVATION DETAILS OF KITCHEN CONFORMING TO | | | FBC ACC 804.3.2 | | | D. ALL OPERABLE PARTS SHALL MEET THE REQUIREMENTS OF | | | FBC ACC 309. | | | E. SHOW ALL REQUIRED CLEAR FLOOR SPACES AND TURNING | | | RADIUS AS REQUIRED BY FBC ACC 305. | | | F. PROVIDE DETAILS (PLAN AND ELEVATION) OF ALL | | | COMPLIANT FIXTURES SHOWING COMPLIANCE WITH FBC ACC | | | CHAPTER 3 AND CHAPTER 6. INCLUDE ALL GRAB BARS, SHOWER | | | SEATS, CONTROLS, TOILET ROOM ACCESSORIES AND RELATED | | | MILLWORK. | | | G. SEE FBC ACC 604.8.1.2. TOILET ROOM DOORS SHALL BE | | | LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL OR | | | PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED | | | IN THE FRONT PARTITION, THE DOOR OPENING SHALL BE 4 | | | INCHES (100 MM) MAXIMUM FROM THE SIDE WALL FARTHEST | | | FROM THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL | | | OR PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 | | | MM) MAXIMUM FROM THE FRONT PARTITION. TOILET | | | COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM | | | REQUIRED COMPARTMENT AREA. | | | H. TOILET ROOM(S) ACCESSIBLE TO THE WAITING AREA SHALL | | | MEET THE REQUIREMENTS OF FBC ACC 213 | | | 2. PER FBC PL 403.1, 403.2 AND TABLE 403.1, BASED UPON | | | THE OCCUPANT LOAD, SEPARATE TOILET ROOM FACILITIES ARE | | | REQUIRED FOR EACH SEX AND MUST BE ACCESSIBLE FROM THE | | | WAITING ROOM. THE DESIGN CRITERIA FOR THE PROJECT | | | INCLUDED 2017 EXISTING BUILDING CODE CHAPTER 801, | | | SECTION 801.3. PLEASE NOTE CHAPTER 810 CONCERNING | | | PLUMBING WHICH MAY ALLOW AN EXCEPTION TO THE SEPARATE | | | FACILITIES REQUIREMENT. | | | 3. PER FBC PL 403.1 AND TABLE 403.1, BASED UPON THE | | | OCCUPANT LOAD, A DRINKING FOUNTAIN IS REQUIRED; SAID | | | DRINKING FOUNTAIN SHALL MEET THE REQUIREMENTS OF 410.1 | | | AND 410.3 (MINIMUM TWO REQUIRED, ONE FOR WHEELCHAIR AND | | | ONE FOR STANDING, OR SINGLE BI-LEVEL), AS WELL AS | | | MEETING THE REQUIREMENTS OF FBC ACC 211.2 AND 602. | | | 4. SINKS FROM LAB RM #126 AND CONSULTATION 2 RM #123 | | | SHALL NOT CONNECT TO THE WET VENT SERVICING BATH #2 RM | | | #113 PER FBC PL 912.1 AND FBC RES P3108.1. CONNECT TO | | | BRANCH DOWNSTREAM OF BATHROOM FIXTURES AHEAD OF BRANCH | | | SERVICING BATH 1 RM #105 AND BIRTH RM 1 RM #112. MAKE | | | CORRECTION ON P1.01 AND P2.01 PER WPB FBC 107.2.1. | | | 5. RE: P2.01 SANITARY ISOMETRIC; A SINK IS SHOWN | | | CONNECTING TO BRANCH BETWEEN BATH #2 AND BIRTH #1 | | | TUB/BATH #1. THIS SINK DOES NOT APPEAR ON P1.01 OR | | | A102.1 FLOOR PLANS. PLEASE CLARIFY PER WPB FBC 107.2.1. | | | 6. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING | | | INFORMATION: | | | A. IDENTIFY GAS TANKLESS WATER HEATERS ON P1.01 FLOOR | | | PLAN AND INTEGRATE WITH WATER DISTRIBUTION. | | | B. ON P2.01 TANKLESS HOT WATER SYSTEM DETAIL, PROVIDE | | | ADDITIONAL DETAIL INTEGRATING THE POTABLE WATER SERVICE | | | WITH THE HOT WATER SYSTEM AND TO HOUSE DISTRIBUTION. | | | C. PROVIDE SCHEDULE, DETAIL AND SPECIFICATION FOR HOT | | | WATER RECIRCULATING PUMP; INCLUDE ELECTRICAL | | | CHARACTERISTICS AND CONTROLS. COMPLY WITH THE | | | REQUIREMENTS OF FBC EC C404 AND FBC PL 607. | | | 7. REGARDING THE SIZING OF THE WATER DISTRIBUTION | | | SYSTEM, PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR | | | SIZING OF THE SYSTEM. IDENTIFY FIXTURE, QUANTITY AND | | | WSFU/ GPM FOR EACH FIXTURE WITH TOTALS FOR COLD AND HOT | | | WATER. | | | 8. REGARDING ?PLUMBING SPECIFICATIONS? ON P2.01, PER | | | WPB FBC 107.2.1, MAKE THE FOLLOWING CHANGES: | | | A. SECTION 2-CODES AND STANDARDS; REPLACE ?STANDARD | | | PLUMBING CODE (SBCCI)? WITH ?FLORIDA PLUMBING CODE 2017 | | | 6TH EDITION? | | | B. SECTION 5, -MATERIALS, ITEM F ; REPLACE ?AIR CHAMBER | | | OR SHOCK ABSORBERS? WITH ?WATER HAMMER ARRESTORS | | | CONFORMING TO ASSE 1010?. ADD AT THE END OF NOTE ?AND | | | AT DISHWASHER, ICE LINE AND CLOTHES WASHER.? | | | C. SECTION 5 -MATERIALS, ADD SPECIFICATION FOR | | | INSULATION OF THE HOT WATER CONFORMING TO THE | | | REQUIREMENTS OF FBC EC C404. | | | 9. REGARDING THE WATER DISTRIBUTION SYSTEM, PER WPB FBC | | | 107.2.1, PROVIDE FULL OPEN VALVE ON EACH DOWN FEED PIPE | | | PER FBC PL 606.1(5) AND SHOW ON THE WATER DISTRIBUTION | | | ISOMETRIC. VALVES SHALL BE ACCESSIBLE PER FBC PL 606.3. | | | VALVES SHALL BE IDENTIFIED AS REQUIRED BY FBC PL 606.4. | | | 10. REGARDING THE WATER DISTRIBUTION SYSTEM, PER WPB | | | FBC 107.2.1, PROVIDE FULL OPEN VALVE AT THE BASE OF | | | SUPPLY TO SECOND FLOOR PER FBC PL 606.1(4) EFFECTIVELY | | | PREVENTING IMPACT OF THE FIRST FLOOR SYSTEM AND SHOW ON | | | THE WATER DISTRIBUTION ISOMETRIC. THE HOT WATER RETURN | | | SHOULD BE MODIFIED TO NEGATE ANY IMPACT ON THE FIRST | | | FLOOR. VALVES SHALL BE ACCESSIBLE PER FBC PL 606.3. | | | VALVES SHALL BE IDENTIFIED AS REQUIRED BY FBC PL 606.4. | | | 11. PER WPB CCCM SECTION C PARA III AND IV, A LEAD FREE | | | BACKFLOW PREVENTER IS REQUIRED. INDICATE ON P1.01, THE | | | LOCATION, SIZE AND TYPE. SHOW ON P2.02 WATER | | | DISTRIBUTION ISOMETRIC. INDICATE EXISTING OR NEW. TYPE | | | SHALL BE AS REQUIRED BY THE CITY OF WEST PALM BEACH | | | UTILITIES (561-822-2244) MEETING THE REQUIREMENTS OF | | | WPB CCCM AND FBC PL 608. UP TO DATE CERTIFICATION OF | | | THE DEVICE WILL BE REQUIRED FOR FINAL INSPECTION. | | | 12. PER WPB FBC 107.2.1, NOTE ON THE PLUMBING FIXTURE | | | SCHEDULE THE REQUIRED TEMPERATURE LIMITING DEVICES TO | | | BE EMPLOYED AT THE FIRST FLOOR LAVATORIES; SHOW | | | COMPLIANCE WITH FBC PL 416.5 AND CONFORM TO ASSE 1070 | | | OR CSA B125.3. | | | 13. PER WPB FBC 107.2.1, NOTE ON THE PLUMBING FIXTURE | | | SCHEDULE THE REQUIRED TEMPERATURE LIMITING DEVICES TO | | | BE EMPLOYED AT THE BATHTUBS AND SHOWERS; SHOW | | | COMPLIANCE WITH FBC PL 424.5. | | | 14. REMOVE DUPLICATE ARCHITECTURAL PAGES PER WPB FBC | | | 107.2.1. | | | 15. PER WPB FBC 107.2.1, ARCHITECT SHALL LOCATE THE | | | WATER METER AND BACKFLOW PREVENTER ON A0.02. AN | | | APPROVED PLUMBING REVIEW WILL DEPEND UPON THIS | | | REQUIREMENT BEING MET. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19010578 2717 POINSETTIA AVE | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-02-12 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-12 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-12 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2019-02-12 14:03:51 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW; DENIED | | | PLUMBING COMMENTS | | | | | | 1. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | HAVE NOT BEEN DETERMINED. PLEASE, PROVIDE SO THAT THE | | | MINIMUM PLUMBING FACILITIES REQUIREMENTS CAN BE | | | DETERMINED AND PLANS CAN BE REVIEWED FOR COMPLIANCE PER | | | WPB FBC 107.3.5.1.3 (1). | | | 2. SINKS FROM LAB RM #126 AND CONSULTATION 2 RM #123 | | | SHALL NOT CONNECT TO THE WET VENT SERVICING BATH 1 RM | | | #105 AND BIRTH RM 1 RM #112 PER FBC PL 912.1 AND FBC | | | RES P3108.1. CONNECT DOWNSTREAM OF TUB. MAKE CORRECTION | | | ON P1.01 AND P2.01 PER WPB FBC 107.2.1. | | | 3. P1.01 SECOND FLOOR PLAN INDICATES TWO (2) | | | LAVATORIES, ONE (1) WATER CLOSET, ONE (1) SHOWER AND | | | ONE (1) TUB. P2.01 SECOND FLOOR SANITARY ISO INDICATES | | | TWO (2) LAVATORIES, TWO (2) WATER CLOSETS AND ONE (1) | | | SHOWER. PLEASE CLARIFY PER WPB FBC 107.2.1. | | | 4. PROVIDE WATER DISTRIBUTION ISO INDICATING SIZING, | | | VALVING, REQUIRED BACKFLOW PREVENTERS AND OTHER | | | APPURTENANCES REQUIRED IN THE SYSTEM PER WPB FBC | | | 107.3.5.1.3 (3).PROVIDE WATER DISTRIBUTION LAYOUT ON | | | PLUMBING FLOOR PLAN CORRESPONDING TO THE ISO PER WPB | | | FBC 107.2.1. | | | 5. PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING THE | | | FIXTURE TYPE, WATER REQUIREMENTS, WASTE, REQUIRED | | | TEMPERATURE LIMITING DEVICES TO BE EMPLOYED WHERE | | | APPLICABLE AND TYPE OF BACKFLOW PREVENTION REQUIRED | | | WHERE APPLICABLE PER FWPNB FBC 107.2.1.. | | | 6. PROVIDE A DETAIL OF THE BIRTHING ROOM TUBS SHOWING | | | HOW WATER SOURCE IS TO BE APPLIED PER WPB FBC 107.2.1. | | | | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, | | | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW | | | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-08-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-08-29 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-08-30 14:24:12 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | | | 1.) CLASSIFIED MEDICAL OFFICE. NO OVERNIGHT STAYS | | | PERMITTED. | | | | | | 2.) SEPARATE PERMITS REQUIRED FOR: HARDSCAPES AND | | | PARKING AND LANDSCAPING. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-05-24 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-05-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-05-24 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2019-05-24 08:54:07 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE USE. | | | ACCORDING TO BUSINESS TAX #0000048302 (BLISS BIRTH AND | | | WELLNESS CENTER), THE PROPOSED USE AT THIS ADDRESS IS | | | AN OUTPATIENT MEDICAL OFFICE. THIS MEANS THAT PATIENTS | | | ARE NOT PERMITTED TO STAY AT THE FACILITY MORE THAN 24 | | | HOURS. PLEASE CLARIFY. [1/30/19 REPEAT COMMENT: A | | | WRITTEN STATEMENT SHALL BE PROVIDED IN THE PLANS AND/OR | | | IN A RESPONSE LETTER TO PROVIDE ASSURANCE TO ZONING | | | STAFF] | | | | | | 2.) THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($92,443) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. [1/30/19 REPEAT | | | COMMENT: A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED | | | PRIOR TO ZONING SIGN-OFF OF THIS PERMIT. THE LANDSCAPE | | | PLAN MUST DEMONSTRATE THAT THE PROJECT MEETS THE | | | MINIMUM LANDSCAPE REQUIREMENTS TO THE GREATEST EXTENT | | | POSSIBLE FOR A SINGLE-FAMILY DWELLING AND LANDSCAPING | | | FOR THE PARKING. CONTACT RAY CARANCI, THE CITY'S | | | LANDSCAPE PLANNER, @ 561-855-1462 IF THERE ARE ANY | | | QUESTIONS.] | | | | | | | | | NOTES: | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: CMUD - EDGE SUBDISTRICT | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-01-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-01-30 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2019-01-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-01-30 11:14:14 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE USE. | | | ACCORDING TO BUSINESS TAX #0000048302 (BLISS BIRTH AND | | | WELLNESS CENTER), THE PROPOSED USE AT THIS ADDRESS IS | | | AN OUTPATIENT MEDICAL OFFICE. THIS MEANS THAT PATIENTS | | | ARE NOT PERMITTED TO STAY AT THE FACILITY MORE THAN 24 | | | HOURS. PLEASE CLARIFY. | | | | | | 2.) THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($92,443) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | | | | NOTES: | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: CMUD - EDGE SUBDISTRICT | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |