Plan Review Details - Permit 19010578
Plan Review Stops For Permit 19010578
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-09-19 Cont ID  
Sent By shill Date 2019-09-19 Time 13:41 Rev Time 0.00
Received By shill Date 2019-09-19 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-06 Cont ID  
Sent By jwitmer Date 2019-09-06 Time 07:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2019-09-06 07:17:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010578
 ADD: 2717 POINSETTIA AVE.
 CONT: PA TWIN MANAGEMENT/ CGC1525857
 TEL: 561-345-9054
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. SEPT. 06, 2019
  
 ACTION: BUILDING PROVISOS
  
 1) PROVISO: PLEASE NOTE THAT THAT THE BIRTHING CENTER
 SHALL COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR
 BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS, THE AGENCY OF HEALTH CARE
 ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES.
 FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES
 THAT THE AGENCY (AHCA) MAY ENFORCE THE
 SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING
 CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY
 ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA
 BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO
 ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL-
 OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF
 THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE
 ACCESSIBILITY CODE.
 PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE
 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE
 DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE
 COMPLIANCE.
  
 2) PROVISO: A SEPARATE PERMIT IS REQUIRED FOR FIRE
 SPRINKLERS. IN THE 2017 EXISTING BUILDING CODE FOR
 CHANGE OF OCCUPANCY CHAPTER 10 OF THE EXISTING B. C.
 SECTION 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER
 SYSTEM IN THE PORTION OF THE BUILDING THAT REQUIRES A
 FIRE SPRINKLER SYSTEM, WHEN SEPARATION (HORIZONTAL) IS
 INSTALLED BY OTHER REQUIREMENTS IN THE CODE. SECTION
 1004 E. B. C. FIRE PROTECTION IS REQUIRED IN CHAPTER 9
 OF THE FBC-B. SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA
 13R SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN
 GROUP R OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN
 HEIGHT IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM)
 IN HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE
 INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R.
  
 AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP
 TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS
 NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE
 PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13R.
  
 3) PROVISO: SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR
 SHOWS A TABLE AND CHAIRS LISTED AS 120, AND LISTED
 STAFF AREA, WILL ANY OF THE CUSTOMERS AND OR RELATIVE
 EVER BE ABLE TO USE THIS AREA FOR EITHER SNACKS OR
 MEALS? IF SO THEN COMPLIANCE WILL BE REQUIRED WITH THE
 2017 ACCESSIBILITY CODE SECTIONS:
  
 3)(A) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 3)(B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3)(C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3(D) NEW COMMENT) SHEET A1.2 SHOWS A MICROWAVE OVER THE
 STOVE, HEIGHT NOT GIVEN BUT MUST COMPLY WITH THE
 ACCESSIBILITY CODE
 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 4) PROVISO: REVISION REQUIRED. SHEET A7.01 HAS A WINDOW
 AND DOOR SCHEDULE. THE WINDOW SCHEDULE INDICATES SEE
 STRUCTURAL SHEETS FOR WIND DESIGN & PRESSURES. THE DOOR
 SCHEDULE INDICATES SEE ELEVATIONS FOR WIND DESIGN AND
 ASSOCIATED PRESSURES. A REVISION IS REQUIRED SHOWING
 THE REQUIRED WIND DESIGN CRITERIA AND ASSOCIATED
 PRESSURES, PLUS PRODUCT APPROVALS FOR ALL NEW WINDOWS,
 EXTERIOR DOORS AND NEW ROOFING.
  
 4A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,
 (B) WINDOWS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-28 Cont ID  
Sent By jwitmer Date 2019-05-28 Time 09:48 Rev Time 0.00
Received By jwitmer Date 2019-05-24 Time 12:38 Sent To  
Notes
2019-05-28 09:48:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010578
 ADD: 2717 POINSETTIA AVE.
 CONT: PA TWIN MANAGEMENT/ CGC1525857
 TEL: 561-345-9054
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 28, 2019
  
 ACTION: FAILED
  
 1) THE ONE SET OF PLANS HAS 2 SETS OF ARCHITECTURAL
 SHEETS IN THE SET OF PLANS (REMOVE ONE SET), AND
 MISSING SHEETS S1-S5. TE FULL SET OF PLANS THE S-SHEETS
 ARE NOT SIGNED AND SEALED.
  
 2) THE MECHANICAL SHEETS DOES NOT SHOW RADIENT FIRE
 DAMPERS IN THE 2 HOUR FIRE RATED CEILING OF THE FIRST
 FLOOR UNDER THE R2 RESIDENCY ABOVE.
 2017 FBC-B 717.6.2 MEMBRANE PENETRATIONS. DUCTS AND AIR
 TRANSFER OPENINGS CONSTRUCTED OF APPROVED MATERIALS IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL
 THAT PENETRATE THE CEILING MEMBRANE OF A
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY SHALL BE PROTECTED WITH ONE OF THE FOLLOWING:
 1.A SHAFT ENCLOSURE IN ACCORDANCE WITH SECTION 713.
  
 2.A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DUCT PENETRATES THE CEILING OF A
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY.
  
 3) MISSING THE WALL DAMPER TO PROTECT THE DUCTWORK
 WHERE THE 2ND STORY WALL IS LOCATED. 717.5.6 EXTERIOR
 WALLS. (OLD EXTERIOR WALL) DUCTS AND AIR TRANSFER
 OPENINGS IN FIRE-RESISTANCE-RATED EXTERIOR WALLS
 REQUIRED TO HAVE PROTECTED OPENINGS IN ACCORDANCE WITH
 SECTION 705.10 SHALL BE PROTECTED WITH LISTED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING.
  
  
  
 BUILDING PROVISOS
  
 1) PROVISO: PLEASE NOTE THAT THAT THE BIRTHING CENTER
 SHALL COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR
 BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS, THE AGENCY OF HEALTH CARE
 ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES.
 FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES
 THAT THE AGENCY (AHCA) MAY ENFORCE THE
 SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING
 CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY
 ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA
 BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO
 ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL-
 OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF
 THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE
 ACCESSIBILITY CODE.
 PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE
 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE
 DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE
 COMPLIANCE.
  
 2) PROVISO: A SEPARATE PERMIT IS REQUIRED FOR FIRE
 SPRINKLERS. IN THE 2017 EXISTING BUILDING CODE FOR
 CHANGE OF OCCUPANCY CHAPTER 10 OF THE EXISTING B. C.
 SECTION 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER
 SYSTEM IN THE PORTION OF THE BUILDING THAT REQUIRES A
 FIRE SPRINKLER SYSTEM, WHEN SEPARATION (HORIZONTAL) IS
 INSTALLED BY OTHER REQUIREMENTS IN THE CODE. SECTION
 1004 E. B. C. FIRE PROTECTION IS REQUIRED IN CHAPTER 9
 OF THE FBC-B. SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA
 13R SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN
 GROUP R OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN
 HEIGHT IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM)
 IN HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE
 INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R.
  
 AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP
 TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS
 NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE
 PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13R.
  
 3) PROVISO: SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR
 SHOWS A TABLE AND CHAIRS LISTED AS 120, AND LISTED
 STAFF AREA, WILL ANY OF THE CUSTOMERS AND OR RELATIVE
 EVER BE ABLE TO USE THIS AREA FOR EITHER SNACKS OR
 MEALS? IF SO THEN COMPLIANCE WILL BE REQUIRED WITH THE
 2017 ACCESSIBILITY CODE SECTIONS:
  
 3)(A) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 3)(B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3)(C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3(D) NEW COMMENT) SHEET A1.2 SHOWS A MICROWAVE OVER THE
 STOVE, HEIGHT NOT GIVEN BUT MUST COMPLY WITH THE
 ACCESSIBILITY CODE
 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 4) PROVISO: REVISION REQUIRED. SHEET A7.01 HAS A WINDOW
 AND DOOR SCHEDULE. THE WINDOW SCHEDULE INDICATES SEE
 STRUCTURAL SHEETS FOR WIND DESIGN & PRESSURES. THE DOOR
 SCHEDULE INDICATES SEE ELEVATIONS FOR WIND DESIGN AND
 ASSOCIATED PRESSURES. A REVISION IS REQUIRED SHOWING
 THE REQUIRED WIND DESIGN CRITERIA AND ASSOCIATED
 PRESSURES, PLUS PRODUCT APPROVALS FOR ALL NEW WINDOWS,
 EXTERIOR DOORS AND NEW ROOFING.
 4A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,
 (B) WINDOWS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By pvalenti Date 2019-02-11 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2019-02-05 Time 16:50 Sent To  
Notes
2019-02-11 08:30:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010578
 ADD: 2717 POINSETTIA AVE.
 CONT: PA TWIN MANAGEMENT/ CGC1525857
 TEL: 561-345-9054
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 11/2019
 ACTION: DENIED
  
 1) ARCHITECTURAL SHEETS IN THE ARCHITECTS TITLE BLOCK
 IS MISSING: (6) THE PRINTED NAME AND THE
 LICENSE/REGISTRATION NUMBER OF THE PERSON SEALING THE
 DOCUMENT.
 61G1-16.004 TITLE BLOCK. ARCHITECT.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED
  
 2) THE COVERSHEET LIST THE OCCUPANCY TYPE AS AN R3
 OCCUPANCY AND LIST THE CODE SECTION 310.5 OF THE 2017
 FBC-B AND QUOTING THE SECTION ON CARE FACILITIES THAT
 PROVIDE ACCOMMODATIONS FOR FIVE OR FEWER PERSONS
 RECEIVING CARE. WHAT THE DESIGNER HAS OVERLOOKED IS IN
 THE CODE SECTION 310.5 THE RELEVANT WORDING PRIMARILY
 PERMANENT IN NATURE. THE 2015 IBC COMMENTARY ON THE
 SUBJECT OF CARE FACILITIES, THE INTENT IS TO ALLOW
 PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR HOME,
 ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER THAT
 IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME, THIS IS
 TO BE CONSIDERED LONG TERM.
  
 IN THE 2017 FBC-B SECTION 308.4.2 INSTITUTIONAL GROUP
 I-2. FIVE OR FEWER PERSONS RECEIVING MEDICAL CARE.
 A FACILITY WITH FIVE OR FEWER PERSONS RECEIVING MEDICAL
 CARE SHALL BE CLASSIFIED AS GROUP R-3 OR SHALL COMPLY
 WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED AN
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1. THE COMMENTARY AGAIN DECLARES IT
 TO ALLOW PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR
 HOME, ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER
 THAT IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME,
 THIS IS TO BE CONSIDERED LONG TERM.
 THE USE OF THE SPACE (FIRST & SECOND FLOOR) IS GOING TO
 BE HOW WE REVIEW WHAT CODE REQUIREMENTS AN OCCUPANCY
 CAN BE DECLARED. I HAVE MET WITH THE BUILDING OFFICIAL
 ROBERT BROWN, ASSISTANT BUILDING OFFICIAL STEVEN
 KENNEDY AND WITH SAMANTHA HILL THE CHIEF PLANS EXAMINER
 ON THIS MATTER. AS DISCUSSED FOR THIS REVIEW WE ARE
 LOOKING AT THE 1ST FLOOR AS A BUSINESS OCCUPANCY
 OFFERING SERVICES SUCH AS A DOCTOR?S OFFICE AND OR
 DENTIST WITH STATE REQUIREMENTS F. S. 383.309 REQUIRING
 US TO ALSO LOOK INTO THE SPECIAL OCCUPANCY PROVISIONS
 FOR BIRTHING CENTERS FOUND IN THE 2017 FBC-B CHAPTER 4
 AND SECTION 452 FOR BIRTHING CENTERS.
 THIS REVIEW WILL ALSO LOOK AT THE BUILDING AS A MIXED
 USE BUILDING. THE 2ND FLOOR AS A R2 OCCUPANCY SINCE THE
 PLANS INDICATE THE KITCHEN ON THE 1ST FLOOR AS PART OF
 THE BUSINESS OCCUPANCY, EVEN THOUGH THE PLANS STATE A
 CARETAKERS QUARTERS AS PRIMARILY PERMANENT IN NATURE.
 THE 1ST FLOOR AS A BUSINESS OCCUPANCY, SPECIAL
 OCCUPANCY, SECTION 452 FOR BIRTHING CENTERS.
 DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE,
 INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS,
 INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING,
 EATING, COOKING AND SANITATION.
 SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP,
 WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING,
 EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT
 NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A
 DWELLING UNIT ARE NOT SLEEPING UNITS.
  
 2A) SHEET A1.02. IN A MIXED USE BUILDING THERE NEEDS TO
 BE A HORIZONTAL FIRE BARRIER BETWEEN THE R2 OCCUPANCY
 UPSTAIRS AND THE BUSINESS OCCUPANCY DOWNSTAIRS. SEE
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL
 ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT
 FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE
 RATING OF NOT LESS THAN THAT REQUIRED BY SECTION
 707.3.10.
 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL
 ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT
 FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE
 RATING OF NOT LESS THAN THAT REQUIRED BY SECTION
 707.3.10. TABLE 707.3.10 WILL REQUIRE A 2 HOUR FIRE
 BARRIER BETWEEN THE R2 OCCUPANCY ABOVE AND THE PORTION
 OF THE BUSINESS OCCUPANCY DIRECTLY BELOW THE R2
 OCCUPANCY AS WELL AS BENEATH THE STAIR, 1ST FLOOR
 SHOWER CEILING.
  
 2B) SHEET A1.02. THE NEW STAIRWAY ADDITION WILL NEED TO
 BE SEPARATED VERTICALLY AS WELL AS HORIZONTALLY, THE
 VESTIBULE 2 BOTH HORIZONTALLY AS WELL AS VERTICALLY
 TABLE 508.4 WITH A 2 HOUR FIRE BARRIER.
  
 707.3.9 SEPARATED OCCUPANCIES. WHERE THE PROVISIONS OF
 SECTION 508.4 ARE APPLICABLE, THE FIRE BARRIER
 SEPARATING MIXED OCCUPANCIES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT INDICATED
 IN TABLE 508.4 BASED ON THE OCCUPANCIES BEING
 SEPARATED.
  
 2C) SHEET A1.02. VESTIBULE 2 ALSO SHOWS THE STAIR
 WINDERS AT THE BOTTOM OF THE STAIRWELL. PLEASE INDICATE
 BETWEEN STAIR 1 AND 2 IT APPEARS THE WINDER STAIR GOES
 TO A POINT, THERE IS A DASHED LINE THAT COULD BE THE
 HEADER ABOVE, PLEASE CLARIFY FOR CODE COMPLIANCE WITH
 FBC-B 1011.4. THE 12-INCH (305 MM) DIMENSION SHALL BE
 MEASURED FROM THE WIDEST POINT OF THE CLEAR STAIR WIDTH
 AT THE WALKING SURFACE OF THE WINDER. WHERE WINDERS ARE
 ADJACENT WITHIN THE FLIGHT, THE POINT OF THE WIDEST
 CLEAR STAIR WIDTH OF THE ADJACENT WINDERS SHALL BE
 USED.
  
 3) PLEASE NOTE THAT THE DESIGNER OF RECORD CANNOT USE
 NONSEPARATED OCCUPANCIES BETWEEN THE R2 OCCUPANCY AND
 BUSINESS OCCUPANCY ON THE 1ST FLOOR, SECTION
 508.2.4.(2) TAKES YOU TO SECTION 420 SPECIAL
 OCCUPANCIES FOR GROUPS I-1, R-1,R-2, R-3 AND R-4.
 SECTION 420.2 AND 420.3 SEPARATION WALLS AND HORIZONTAL
 SEPARATION BETWEEN DWELLING UNITS/ SLEEPING UNITS AND
 OTHER OCCUPANCIES.
  
 4) PLEASE ALSO REVIEW FLORIDA STATUTE 383.308 (B) FOR
 FOOD SERVICES, IF JUST LIGHT SNACKS OR IF A FOOD
 SERVICE IS PROVIDED, SPECIAL REQUIREMENTS SHALL BE MET
 AS DEFINED IN RULES PROMULGATED PURSUANT TO CHAPTER
 381.0072 FOOD SERVICES PROTECTION.
  
 5) PLEASE NOTE THAT THAT THE BIRTHING CENTER SHALL
 COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR
 BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS MAY APPLY. SEE AGENCY OF HEALTH
 CARE ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES.
 FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES
 THAT THE AGENCY (AHCA) MAY ENFORCE THE
 SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING
 CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY
 ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA
 BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO
 ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL-
 OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF
 THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE
 ACCESSIBILITY CODE.
 PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE
 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE
 DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE
 COMPLIANCE.
  
 5.1) PLEASE SHOW COMPLIANCE WITH SECTIONS: FBC-B
 452.2.2.1. BIRTH ROOMS SHALL BE LOCATED TO PROVIDE
 UNIMPEDED, RAPID ACCESS TO AN EXIT OF THE BUILDING
 WHICH WILL ACCOMMODATE EMERGENCY TRANSPORTATION
 VEHICLES.
  
 5.2) 452.2.6 HALLWAYS AND DOORS PROVIDING ACCESS AND
 ENTRY INTO THE BIRTH CENTER AND BIRTH ROOM SHALL BE OF
 ADEQUATE WIDTH AND CONFORMATION TO ACCOMMODATE
 MANEUVERING OF AMBULANCE STRETCHERS AND WHEELCHAIRS.
 THE STRETCHER REQUIREMENTS ARE AMBULANCE STRETCHER 24
 INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS
 THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL
 POSITION. PLEASE SHOW THE STRETCHER GOING DOWN THE
 CORRIDOR, THROUGH THE DOORWAY AND INTO THE BIRTHING
 ROOMS FOR BOTH BIRTHING ROOMS.
  
 6) PLEASE ALSO BE AWARE THAT THE KITCHEN BEING LOCATED
 ON THE 1ST FLOOR, THE BUSINESS OCCUPANCY, COMPLIANCE
 WITH SECTION 904.2.2 OF THE 2017 FBC-B FOR COMMERCIAL
 HOOD AND DUCT SYSTEMS AND 904.3 THE INSTALLATION OF AN
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS TO BE INSTALLED IN
 ACCORDANCE WITH THIS SECTION.
  
 7) IN THE 2017 EXISTING BUILDING CODE FOR CHANGE OF
 OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. SECTION
 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER SYSTEM IN THE
 PORTION OF THE BUILDING THAT REQUIRES A FIRE SPRINKLER
 SYSTEM, WHEN SEPARATION (HORIZONTAL) IS INSTALLED BY
 OTHER REQUIREMENTS IN THE CODE. SECTION 1004 E. B. C.
 FIRE PROTECTION IS REQUIRED IN CHAPTER 9 OF THE FBC-B.
 SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA 13R SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN GROUP R
 OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN HEIGHT
 IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE
 INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R.
  
 AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP
 TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS
 NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE
 PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13R.
 8) IN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY PLAN,
 JUST A FLOOR PLAN A1.02. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 9) PLEASE PROVIDE AN ITEMIZED LETTER FROM EITHER THE
 DESIGNER OF RECORD OR THE CONTRACTOR ON THEIR
 LETTERHEAD WHERE 20% OF THEIR BUDGET OR $30,000.00
 DOLLARS WILL BE SPENT IN MAKING ACCESSIBLE UPGRADES TO
 THE 1ST FLOOR. PLEASE REVIEW THE FOLLOWING CODE SECTION
 IN WHAT ORDER THESE FUNDS ARE TO BE SPENT.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 9A) PLEASE NOTE CURRENTLY THERE IS NO ACCESSIBLE
 ENTRANCE. GOGGLE STREET VIEW SHOWS STEPS AND LANDING TO
 THE FRONT DOOR.
  
 9B) THE PLANS DO NOT SHOW TRAVEL DISTANCES AND IF A 2ND
 EGRESS IS REQUIRED ON THE 1ST FLOOR AND THE VESTIBULE 2
 IS GOING TO BE USED AS THE 2ND REQUIRED EGRESS PLEASE
 SHOW ACCOMMODATIONS FOR MANEUVERING OF AMBULANCE
 STRETCHERS TO THE EXTERIOR OF THE BUILDING.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 9C) SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR SHOWS A
 TABLE AND CHAIRS LISTED AS 120, AND LISTED STAFF AREA,
 WILL ANY OF THE CUSTOMERS AND OR RELATIVE EVER BE ABLE
 TO USE THIS AREA FOR EITHER SNACKS OR MEALS? IF SO THEN
 COMPLIANCE WILL BE REQUIRED WITH THE 2017 ACCESSIBILITY
 CODE SECTIONS:
 9C)(1) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 9C)(2) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 9C)(3) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10) IMPACT FEES- PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2019-02-05 16:54:46NOTES IN ERROR DELETED PV

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-09-18 Cont ID  
Sent By jpearson Date 2019-09-18 Time 14:48 Rev Time 0.00
Received By jpearson Date 2019-09-18 Time 14:48 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-09-11 Cont ID  
Sent By jpearson Date 2019-09-11 Time 07:56 Rev Time 0.00
Received By jpearson Date 2019-09-11 Time 07:56 Sent To  
Notes
2019-09-11 07:56:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED. GENERATOR NOW SHOWN AS FUTURE, WIRE SIZE
 WILL BE REQUIRED AT TIME OF SUBMITTAL FOR GENERATOR
 PERMIT.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
  
 NEW COMMENTS:
  
 21. PLAN SETS ARE NOT IDENTICAL, SEVERAL SHEETS ARE
 MISSING FROM ONE SET. THE OTHER SET HAS DUPLICATE
 SHEETS BECAUSE THE OLD SHEETS WERE NOT REMOVED. PROVIDE
 2 IDENTICAL PLAN SETS FOR REVIEW WITH ALL CORRECTIONS.
 WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-21 Cont ID  
Sent By jpearson Date 2019-05-21 Time 09:13 Rev Time 0.00
Received By jpearson Date 2019-05-21 Time 07:31 Sent To  
Notes
2019-05-21 08:08:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. CORRECTED.
 3. CORRECTED. GENERATOR NOW SHOWN AS FUTURE, WIRE SIZE
 WILL BE REQUIRED AT TIME OF SUBMITTAL FOR GENERATOR
 PERMIT.
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 GENERATORS, SIGNS, AND SITE LIGHTING(WHERE APPLICABLE)
 ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW.
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1 (NOTE NOT PROVIDED.)
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
  
 NEW COMMENTS:
  
 18. NOW THAT GENERATOR IS SHOWN AS FUTURE, HOW WILL THE
 ESSENTIAL ELECTRICAL BE MAINTAINED? NEC 517.45
 19. TRANSFER SWITCH IS NOW ALSO SHOWN AS FUTURE. WILL
 THIS BE INSTALLED AT TIME OF GENERATOR INSTALLATION, OR
 WILL THIS BE INSTALLED AS PART OF THE SERVICE? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1
 20. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-14 Cont ID  
Sent By jpearson Date 2019-02-14 Time 12:43 Rev Time 0.00
Received By jpearson Date 2019-02-14 Time 07:00 Sent To I
Notes
2019-02-14 12:43:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. RISER NOTE 3 SHOWS 1/0 CONDUCTORS AS SERVICE
 CONDUCTORS AND FEEDER TO PANEL A. THIS WIRE SIZE IS NOT
 RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16)
 3. RISER NOTE 7 SHOWS 1/0 CONDUCTORS FROM GENERATOR TO
 TRANSFER SWITCH. THIS WIRE IS NOT RATED TO HANDLE THE
 CALCULATED LOAD, OR THE OUTPUT OF THE GENERATOR.
 PROVIDE CORRECTION. NEC 310.15(B)(16)
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 GENERATORS, SIGNS, AND SITE LIGHTING(WHERE APPLICABLE)
 ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW.
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 6. ELECTRICAL SPECIFICATION 2.C STATES THAT NM CABLE
 SHALL NOT BE USED. HOWEVER, THE PLAN STATES THAT 2ND
 FLOOR CIRCUITS WILL BE RE-USED. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1
 7. PROVIDE DETAIL FOR WIRING METHODS IN PATIENT CARE
 AREAS. IDENTIFY ON PLAN WHICH AREAS WILL BE REQUIRED TO
 MEET THESE WIRING METHODS. WPB FBC 107.2.1; NEC 517
 8. LOAD CALCULATION PROVIDED IS THE TYPE USED FOR A
 DWELLING UNIT. THIS WILL NOT BE A DWELLING UNIT.
 PROVIDE ACCURATE LOAD CALCULATION. NEC 220
 9. ALL RECEPTACLE OUTLETS IN LAUNDRY THAT ARE WITHIN 6
 FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 10. PROVIDE LOCATION OF PANEL B ON PLAN TO CONFIRM CODE
 COMPLIANCE. WPB FBC 107.2.1
 11. BIRTH ROOM 1, RECEPTACLE OUTLETS THAT ARE WITHIN 6
 FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 12. BIRTH ROOM 1 SHOWS A RECEPTACLE OUTLET LOCATED IN
 THE DOORWAY. PROVIDE CLARIFICATION AND/OR CORRECTION.
 WPB FBC 107.2.1
 13. CONSULTATION ROOM 2, RECEPTACLE OUTLETS THAT ARE
 WITHIN 6 FEET OF THE SINK REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8
 14. EXAM ROOM, RECEPTACLE OUTLETS THAT ARE WITHIN 6
 FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 15. KITCHEN, RECEPTACLE OUTLETS THAT ARE WITHIN 6 FEET
 OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 16. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 17. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-09-19 Cont ID  
Sent By pleduc Date 2019-09-19 Time   Rev Time 0.00
Received By pleduc Date 2019-09-19 Time 12:05 Sent To  
Notes
2019-09-19 12:07:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ONE PLAN SET DOES NOT HAVE SHEET ES1.01 ATTACHED.
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS
 DEFICIENCY WAS PROVISOED.
  
 PLEASE REVIEW AND PROVIDE SHEET AS APPLICABLE FOR CONST
 SET.
  
  
 2) SHEET ES1.01 - THERE ARE INDICATIONS OF FUTURE WORK.
  
 THE PROPOSED DOMESTIC FIRE SPRINKLER SYSTEM. EMERGENCY
 GENERATOR AND FIRE PIT SHALL ALL BE DONE UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE FUTURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-20 Cont ID  
Sent By pleduc Date 2019-08-20 Time   Rev Time 0.00
Received By pleduc Date 2019-08-20 Time 14:26 Sent To  
Notes
2019-08-20 14:37:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ONE PLAN SET DOES NOT HAVE SHEET ES1.01 ATTACHED.
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS
 DEFICIENCY WAS PROVISOED.
  
 PLEASE REVIEW AND PROVIDE SHEET AS APPLICABLE FOR CONST
 SET.
  
  
 2) SHEET ES1.01 - THERE ARE INDICATIONS OF FUTURE WORK.
  
 THE PROPOSED DOMESTIC FIRE SPRINKLER SYSTEM. EMERGENCY
 GENERATOR AND FIRE PIT SHALL ALL BE DONE UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE FUTURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By pleduc Date 2019-05-21 Time   Rev Time 0.00
Received By pleduc Date 2019-05-21 Time 10:55 Sent To  
Notes
2019-05-21 10:56:415/21/19
  
 THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONTIORED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By pleduc Date 2019-01-25 Time   Rev Time 0.00
Received By pleduc Date 2019-01-25 Time 11:18 Sent To  
Notes
2019-01-25 11:29:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) FRONT SHEET: THERE IS AN INDICATION OF A BUILDING
 CODE OCCUPANCY CLASSIFICATION; HOWEVER, THERE IS NO
 INDICATION OF FLORIDA FIRE PREVENTION CODE
 CLASSIFICATION.
  
 PLEASE PROVIDE A CLEAR NARRATIVE EXPLAINING WHAT OCCURS
 AT THIS FACILTY AND HOW MANY PATIENTS/OCCUPANTS.
  
 PLEASE PROVIDE THE OCCUPANY CLASSIFICATION PER THE
 FFPC.
  
 ENSURE THAT THE SUBMITTED PLANS ARE COMPLIANT WITH THAT
 OCCUPANCY.
  
  
  
 2) FRONT SHEET: THERE IS AN INDICATION OF A FIRE
 SPRINKER SYSTEM.
  
 FOR CLARIFICATION PURPOSES; IS A FIRE SPRINKLER SYSTEM
 BEING PROVIDED FOR THIS FACILTIY ?
  
 IF SO, F.A.C. DOCUMENTS ARE REQUIRED TO BE SUBMITTED
 WITH THIS MASTER PERMIT.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW
 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-09-10 Cont ID  
Sent By jesmith Date 2019-09-10 Time 13:49 Rev Time 0.00
Received By jesmith Date 2019-09-05 Time 16:35 Sent To  
Notes
2019-09-10 13:49:30GAS COMMENTS: APPROVED W/PROVISO
  
 1. ONE (1) EACH STAMPED AND SEALED PLAN SHEET ES1.01
 SHALL BE PROVIDED FOR REVIEWERS? NOTATIONS AS
 APPLICABLE INTO SET OF PLANS WHICH WAS MISSING THIS
 PAGE.
 2. FUTURE GENERATOR AND ASSOCIATED GAS PIPING SHOWN ON
 PLAN SHEET ES1.01 IS NOT PART OF THIS PROJECT AND SHALL
 REQUIRE A SEPARATE PERMIT.
 3. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA
 SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE FIRE
 PIT INDICATING 50 MBTU. THE DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO THE FIRST GAS
 ROUGH INSPECTION.
 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA
 SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE
 TANKLESS WATER HEATERS.INDICATING 199 MBTU EACH. THE
 DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO THE FIRST GAS ROUGH INSPECTION.
 5. SEE PLAN SHEET ES1.01 FOR LOCATION OF FPU GAS METER.
 6. RE: PLAN SHEET P1.02; PRIOR TO FINAL INSPECTION, A
 RECORD DRAWING SHALL BE PROVIDED NOTING THE FIRE PIT AS
 50 MBTU.
 7. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION.
 CALL 561-805-6692 FOR FURTHER INFORMATION.
 8. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By jesmith Date 2019-05-30 Time 15:12 Rev Time 0.00
Received By jesmith Date 2019-05-28 Time 16:20 Sent To  
Notes
2019-05-30 15:11:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
 1. EMERGENCY GENERATOR IS INDICATED FUTURE. PLEASE
 CLARIFY AS THIS PRESENTS LOGISTICAL COMPLICATIONS FOR A
 COMPLETED PROJECT AS WELL AS THE PERMITTING PROCESS.
 2. SUBMIT ON THE ISOMETRIC DRAWING THAT WHICH CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC FG
 SECS. 402.4.1, 402.4.2.
 3. PER WPB FBC 107.2.1, PROVIDE A SCHEDULE INDICATING
 GAS TYPE AND CALCULATIONS EACH FOR THE 2 LB. SYSTEM AND
 THE .5 LB. SYSTEM. LIST APPLIANCES WITH BTU LOAD WITH
 BTU TOTAL AND PROVIDE DISTANCE FROM POINT OF DELIVERY
 TO THE MOST REMOTE OUTLET IN THE SYSTEM AND SIZE
 ACCORDINGLY USING THE APPROPRIATE TABLES. ALTHOUGH THE
 SIZING SHOWN WAS PROBABLY DONE CORRECTLY IT NEEDS TO BE
 CLEARLY NOTED ON THE PLANS. IT WOULD BE HELPFUL TO
 INCLUDE COPIES OF THE TABLES REFERENCED TO HELP THE
 REVIEW PROCESS.
 4. WILL THE DOWNSTREAM MANIFOLD AT THE GAS METER AND
 THE PIPING BETWEEN APPLIANCE VALVES AND APPLIANCE
 REGULATORS BE GALVANIZED? IF SO, PLEASE INCLUDE IN 2
 LB. CALCULATIONS REFERENCING THE PROPER TABLE AND
 INDICATE ON THE PLANS. BE SURE TO USE THE FURTHEST
 POINT MEASUREMENT WHEN CALCULATING. INDICATE ALL
 GALVANIZED PIPING ON THE GAS RISER.
 5. THE GAS RISER SHOWS 1? TO THE WATER HEATERS,
 BRANCHING TO ?? TO EACH OF THE TWO APPLIANCES AS NOTED
 IN THE RESPONSE LETTER. HOWEVER THE TANKLESS HOT WATER
 SYSTEM DETAIL SHOWS ?? TO THE BRANCHES. PER WPB FBC
 107.2.1, PLEASE RECONCILE DETAIL WITH THE GAS RISER.
 6. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR ALL GAS APPLIANCES AND EQUIPMENT PER WPB FPC
 107.2.1.
 7. PER WPB FBC 107.2.1, INDICATE ON P1.01 THE DISTANCE
 FROM THE INTERSECTION OF THE BRANCH TO THE FIRE PIT TO
 FPU METER. ARCHITECT SHALL LOCATE THE FPU METER ON
 A0.02. AN APPROVED PLUMBING REVIEW WILL DEPEND UPON
 THIS REQUIREMENT BEING MET.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19010578 2717 POINSETTIA AVE
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-02-12 Cont ID  
Sent By jesmith Date 2019-02-12 Time 15:16 Rev Time 0.00
Received By jesmith Date 2019-02-12 Time 15:15 Sent To  
Notes
2019-02-12 15:16:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1. SHOW THE LOCATION FOR THE EMERGENCY GENERATOR AND
 FPU METER PER WPB FBC 107.2.1.
 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 APPLIANCES AND EQUIPMENT PER WPB FPC 107.2.1.
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 KITCHEN RANGE PER FBC FG304.1.
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR PER
 FBC FG 410.1.
 5. PROVIDE TRANSITION COMPATIBLE WITH GAS TYPE AS
 REQUIRED BY FBC FG 403.11 (3) FROM PE PIPING IN THE
 GROUND TO GALVANIZED PIPING ABOVE GROUND ON THE
 HIGH-PRESSURE SIDE OF THE REGULATOR TO COMPLY WITH FBC
 FG 404.17.1 OR PROVIDE MANUFACTURER?S SPECIFICATION AND
 INSTALLATION INSTRUCTIONS FOR FUEL GAS SERVICE HEAD
 ADAPTER RISER TO REGULATOR TO COMPLY WITH FBC FG
 404.17.1 EXCEPTION 1.
 6. NOTE MATERIAL TYPE (SCHEDULE 40 GALVANIZED OR FUEL
 GAS SERVICE HEAD RISER ADAPTER), SIZE AND APPLICABLE
 SIZING TABLE FOR ABOVE GROUND PIPING ON LOW PRESSURE
 SIDE OF THE REGULATOR.
 7. INDICATE SIZE OF LOW PRESSURE PIPING TO EMERGENCY
 GENERATOR PER WPB FBC 107.2.1.
 8. DETAIL ON P2.01 FOR TANKLESS WATER HEATERS INDICATES
 3/4" LOW PRESSURE PIPING TO THE TWO HEATERS AS OPPOSED
 TO 1" ON THE GAS RISER. PLEASE CLARIFY AND CORRECT PER
 WPB FBC 107.2.1.
 9. PLEASE NOTE ON THE PLANS THE TYPE OF GAS PROVIDED
 PER WPB FBC 107.2.1.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-19 Cont ID  
Sent By shill Date 2019-09-19 Time 13:41 Rev Time 0.00
Received By shill Date 2019-09-17 Time 14:13 Sent To  
Notes
2019-09-18 14:13:46RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-09-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-15 Time 14:37 Sent To  
Notes
2019-08-16 14:37:57B31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-30 Cont ID  
Sent By jesmith Date 2019-05-30 Time 15:13 Rev Time 0.00
Received By jesmith Date 2019-05-30 Time 15:13 Sent To  
Notes
2019-05-28 13:10:22TO J.SMITH DESK
  
  
2019-05-20 14:31:02B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-22 Time 14:35 Sent To  
Notes
2019-01-22 14:36:05B06
2019-01-22 11:43:38APPLICATION COMPLETE THIS DATE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By shill Date 2019-09-27 Time 11:06 Rev Time 0.00
Received By shill Date 2019-09-27 Time 11:06 Sent To  
Notes
2019-09-27 11:18:23MU 2019 029591 $4,632.87 PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By jwitmer Date 2019-02-11 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2019-02-11 Time 08:32 Sent To  
Notes
2019-02-11 08:31:56IMPACT FEES- PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM
2019-01-22 12:22:47THIS WILL REQUIRE PBC IMPACT FEE REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-09-12 Cont ID  
Sent By ccole Date 2019-09-12 Time 11:49 Rev Time 0.00
Received By ccole Date 2019-09-12 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-21 Cont ID  
Sent By ccole Date 2019-05-21 Time 13:41 Rev Time 0.00
Received By ccole Date 2019-05-21 Time 12:07 Sent To  
Notes
2019-05-21 14:52:352ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19010578
 5/21/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.02 & M1.01: THE REVISED PLANS INDICATE A
 2HR. FIRE-RATED CEILING ASSEMBLY BETWEEN THE 1ST AND
 2ND STORY OF THE TWO-STORY SECTION OF THE BUILDING.
 LISTED CEILING RADIATION DAMPERS ARE REQUIRED FOR THE
 DUCTS AND DIFFUSERS PENETRATING THE ASSEMBLY- SECTION
 607.2 FBC M.
  
 2) A1.02 & M1.01: THE 6X6" AND 6" ROUND AC DUCTS
 PENETRATING INTO THE VESTIBULE AND INTERIOR EXIT
 STAIRWAY ARE PROHIBITED IN ACCORDANCE WITH SECTIONS
 1023.5 AND 1023.6 FBC B.
  
 3) A1.02 & M1.01: THE DRYER AND BATH EXHAUST DUCTS
 SHALL NOT PENETRATE INTO THE FIRE-RATED INTERIOR EXIST
 STAIRWAY WALL PER SECTION 1023.5 FBC B.
  
 4) M1.01: BECAUSE THE NEW BIRTHING CENTER IS A CHANGE
 OF OCCUPANCY FROM R-3 TO B, THE AIR HANDLER (AH-1) IS
 NO LONGER ALLOWED TO BE INSTALLED IN THE ATTIC- SEE
 SECTION C403.2.9.6 FBC EC AND RELOCATE THE UNIT.
  
 5) M1.01: THE REQUESTED AC COOLING AND HEATING
 CALCULATIONS WERE NOT PROVIDED (SEE 1ST REVIEW COMMENT
 #2). THE ENGINEER'S NARRATIVE RESPONSE STATES THAT THE
 SYSTEMS ARE LIKE FOR LIKE CHANGEOUTS HOWEVER THERE IS A
 PARTIAL MANUAL J HEAT LOAD CALCULATION SHOWN ON THE
 PLAN. PLEASE NOTE THAT ACCA MANUAL J CALCULATIONS ARE
 FOR SIZING SYSTEMS IN RESIDENTIAL OCCUPANCIES UNDER 3
 STORIES. BECAUSE OF THE CHANGE OF OCCUPANCY AND
 INCREASED HEAT LOAD FORM LIGHTING, EQUIPMENT, PEOPLE
 ETC, IT IS NECESSARY TO PROVIDE SIZING CALCULATIONS
 USING MANUAL N FOR THE BIRTHING CENTER, AND MANUAL J
 FOR THE 2ND FLOOR APARTMENT- REFER TO SECTIONS C403.2.1
 AND R403.6.1. AS PREVIOUSLY NOTED IN THE 1ST REVIEW
 COMMENT, THE 5-TON SYSTEM AH-2 APPEARS TO BE OVERSIZED
 FOR THE APPROXIMATE 778 SF. APARTMENT.
  
 6) M1.01: 2ND REQUEST FOR A DUCT SMOKE DETECTOR TO BE
 INSTALLED IN THE SUPPLY AIR SYSTEM OF AH-2 PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE
 SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR
  
 7) M1.01: THE NEW KITCHEN EXHAUST HOOD SHALL BE FOR
 DOMESTIC USE PER SECTION 505.4 FBC M. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND NOTE THAT MAKEUP AIR
 MAY BE REQUIRED PER SECTION 505.2 FBC M.
  
 8) M1.01: 2ND REQUEST FOR MANUFACTURER'S SPECIFICATIONS
 FOR THE CLOTHES DRYER- SECTION 504.1 FBC M. PLEASE NOTE
 THAT MAKEUP AIR SHALL BE PROVIDED IF THE APPLIANCE HAS
 AN EXHAUST CAPACITY EXCEEDING 200 CFMS- SECTION 504.6
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By ccole Date 2019-02-11 Time 16:21 Rev Time 0.00
Received By ccole Date 2019-02-11 Time 12:56 Sent To  
Notes
2019-02-11 17:14:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010578
 2/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: PLEASE PROVIDE A LIST OF CURRENT
 CODES AND STANDARDS USED IN THE DESIGN OF THE NEW
 BIRTHING CENTER. THE PROPOSED CENTER IS CLASSIFIED AS A
 CHANGE OF OCCUPANCY PER SECTION 202 FBC EX. PLEASE
 REFER TO SECTION 301.1 FBC EX AND INDICATE WHICH
 COMPLIANCE METHOD WILL BE USED, AND INCLUDE THE CODE
 AND COMPLIANCE INFORMATION WITH THE NOTES SHOWN ON THE
 COVER SHEET. THE FOLLOWING REVIEW COMMENTS ARE BASED ON
 THE CURRENT PLANS WHICH MAY BE SUBJECT TO CHANGE BASED
 ON THE COMPLIANCE METHOD CHOSEN, AND BASED ON REQUIRED
 CHANGES PER THE BUILDING REVIEW COMMENTS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
 PLEASE NOTE THAT AC-2 APPEARS TO BE OVERSIZED FOR THE
 PROPOSED 2ND FLOOR ROOMS AND SPACES.
  
 3) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTIONS C505.1
 AND C101.5 FBC EC.
  
 4) MINIMUM VENTILATION RATES FOR THE FACILITY SHALL BE
 IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M, AND THE
 FOLLOWING SECTIONS FROM THE FBC B. PLEASE COMPLY BY
 PROVIDING A VENTILATION SCHEDULE ON THE PLAN SHOWING
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR AND AND
 EXHAUST AIR.
 452.2.8.2
 WHEN MECHANICAL VENTILATION OR COOLING SYSTEMS ARE
 EMPLOYED, THE SYSTEM SHALL BE PROPERLY MAINTAINED AND
 KEPT CLEAN. INTAKE AIR DUCTS SHALL BE DESIGNED AND
 INSTALLED SO THAT DUST OR FILTERS CAN BE READILY
 REMOVED. IN RESIDENCE AREAS AND SEGREGATION ROOMS WITH
 SOLID DOORS, MECHANICAL VENTILATION SYSTEMS SHALL
 PROVIDE A MINIMUM OF 10 CUBIC FEET (0.3 M3) OF FRESH OR
 FILTERED RECIRCULATED AIR PER MINUTE FOR EACH CLIENT
 OCCUPYING THE AREA.
 452.2.9
 ADEQUATE HEATING AND COOLING FACILITIES SHALL BE
 PROVIDED TO MAINTAIN A MINIMUM TEMPERATURE OF 68
 DEGRESS F (20 DEGREES C) AND MAXIMUM TEMPERATURE OF 78
 DEGREES F (26 DEGREES C) AT A POINT 20 INCHES (508 MM)
 ABOVE THE FLOOR.
 452.2.10
 ALL HEATING DEVICES SHALL COMPLY WITH FIRE PREVENTION
 PROVISIONS FOUND IN RULE 69A-3, FIRE PREVENTION,
 GENERAL PROVISION, FLORIDA ADMINISTRATIVE CODE.
  
 5) SHEET M1.01: EXHAUST VENTILATION AT A RATE OF 1.0
 CFMS PER SF. IS REQUIRED FOR THE LAB AND RECIRCULATION
 OF AIR IS PROHIBITED, OR LIMITED TO A MAXIMUM OF 10
 PERCENT OF AIR RECIRCULATED FROM THE ROOM- TABLE
 403.3.1.1 FOOTNOTE G.
  
 6) M1.01: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF AH-2 PER SECTION 606.2.1. PLEASE
 NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 7) M1.01: NO REFLECTIVE CEILING PLAN HAS BEEN
 SUBMITTED, BUT AH-1 AND DH-1 APPEAR TO BE ABOVE HARD
 CEILINGS. CLARIFY HOW ACCESS WILL BE PROVIDED FOR
 SERVICE AND REPLACEMENT OF THE UNITS- SECTION 306.1 FBC
 M.
  
 8) M1.01: NO ROOMS HAVE BEEN DESIGNATED FOR STORAGE OF
 MEDICAL GASES. WILL ANESTHESIA BE PROVIDED TO PATIENTS,
 AND IF SO, HOW WILL IT BE ADMINISTERED AND STORED AT
 THE FACILITY?
  
 9) M1.01: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN PER TABLE 403.3.1.1 FBC M, AND AN EXHAUST HOOD
 IS REQUIRED OVER THE RANGE IN ACCORDANCE WITH EITHER
 SECTION 507.1 OR 507.1.2 DEPENDING ON WHETHER A
 COMMERCIAL OR DOMESTIC COOKING APPLIANCE IS BEING
 INSTALLED.
  
 10) M1.01: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 NEW AIR HANDLERS. SHOW THE TYPE AND SIZE OF CONDENSATE
 PIPING, THE PIPING RUNS, AND DISPOSAL LOCATIONS-
 SECTION 307.2 FBC M.
  
 11) M1.01: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CLOTHES DRYER- SECTION 504.1 FBC M. PLEASE NOTE THAT
 MAKEUP AIR SHALL BE PROVIDED IF THE APPLIANCE HAS AN
 EXHAUST CAPACITY EXCEEDING 200 CFMS- SECTION 504.6
  
 12) PROVIDE ENGINEERING FOR INSTALLATION OF THE OUTDOOR
 AC CONDENSERS- SECTION 301.15 FBC M.
  
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 RANGE- SECTION 623.1 FBC FG.
  
 14) SHOW THE LOCATION FOR THE EMERGENCY GENERATOR AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 616.1 FBC
 FG. PROVIDE A NARRATIVE INDICATING WHICH ESSENTIAL
 SYSTEMS WILL BE POWERED BY THE SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-05 Cont ID  
Sent By jesmith Date 2019-09-05 Time 16:43 Rev Time 0.00
Received By jesmith Date 2019-09-05 Time 07:57 Sent To  
Notes
2019-09-05 16:43:35PLUMBING COMMEMTS:APPROVED WITH PROVISO
 1. RE: OCCUPANT LOAD. AS DIRECTED BY ROBERT BROWN,
 BUILDING OFFICIAL, CITY OF WEST PALM BEACH, IN
 CONVERSATION WITH ROBERT BROWN, JIM WHITMER AND JERALD
 SMITH, ASSIGN THREE (3) EACH CUSTOMERS TO EACH OF THE
 TWO (2) BIRTHING ROOMS. DEDUCT SQUARE FOOTAGE OF THE
 TWO ROOMS, INCLUDING BATHROOMS (551.5 SQ. FT.) FROM THE
 TOTAL SQUARE FOOTAGE (2035.75 SQ. FT.) LEAVING A TOTAL
 OF 1480 SQ. FT./100=15 OCCUPANTS
 2. ROOMS 122, 123 AND 126 SHALL COMPLY WITH FBC ACC
 212.3, HAVING CLEAR FLOOR SPACE (FBC ACC 606.2)AND
 PROVIDE A MAXIMUM HEIGHT OF 34? TO TOP OF COUNTER OR
 SINK RIM, WHICHEVER IS HIGHER (FBC ACC 606.3), OR THE
 OWNER SHALL PROVIDE A LETTER, SIGNED AND DATED STATING
 THAT IF ANY EMPLOYEE OR POTENTIAL EMPLOYEE SHOULD
 REQUIRE ACCESSIBILITY TO PERFORM THEIR DUTIES IN ANY OF
 THE STATED ROOMS THAT THE OWNER SHALL BRING SAID ROOMS
 INTO COMPLIANCE.
 3. A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW
 PREVENTOR. PROVIDE CERTIFICATION DOCUMENTS AT FINAL
 INSPECTION.
 4. PROVIDE SPECIFICATION SHEETS FOR TANKLESS WATER
 HEATERS SHOWING INTEGRAL RECIRCULATING PUMPS. SUBMITTAL
 SHALL BE SUBMITTED, APPROVED AND IN PLACE PRIOR TO
 FINAL INSPECTION.
 5. RE: P2.02; WATER RISER DIAGRAM. PROVIDE FULL OPEN
 ACCESSIBLE VALVE ON EACH DOWNFEED PIPE PER FBC PL
 606.1(5) AND 606.3. VALVES SHALL BE IDENTIFIED PER FBC
 PL 606.4
 6. PROVIDE ANTI-SCALD SHOWER CONTROL VALVE FOR SECOND
 FLOOR SHOWER PER FBC PL 424.3.
 7. PROVIDE TEMPERATURE LIMITING DEVICE FOR P-6 THERAPY
 TUBS ON GROUND FLOOR AND FOR THE SECOND FLOOR BATHTUB
 PER FBC PL 423.5
 8. WASHING MACHINE SHUT OFF VALVES SHALL BE ACCESSIBLE
 PER FBC PL 606.3.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By jesmith Date 2019-05-30 Time 13:53 Rev Time 0.00
Received By jesmith Date 2019-05-28 Time 15:36 Sent To  
Notes
2019-06-04 10:28:35ADDED COMMENTS EMAILED 6/4/2019 TO AUSTIN DUFFY OF PA
 TWIN MANAGEMENT
 REGARDING THE BIRTHING CENTER AT 2717 POINSIATTIA AVE;
 PERMIT #19010578
 PLEASE NOTE THAT I PERFORMED A COMPREHENSIVE REVIEW OF
 THE PLUMBING ON 5/30/2019. AFTER ADDITIONAL
 CONSIDERATION I WANT TO BRING SOME ADDITIONAL POTENTIAL
 ISSUES TO LIGHT THAT SHOULD BE CONSIDERED BY THE
 DESIGNERS OF RECORD. PLEASE FORWARD TO THOSE DESIGN
 PROFESSIONALS FOR THEIR CONSIDERATION IN PREPARING THE
 NEXT SUBMITTAL.
 ITEM 1: PLEASE NOTE THE FOLLOWING SECTIONS OF THE
 FLORIDA BUILDING CODE.
 ? 452.1SCOPE.
 ALL BIRTHING CENTERS SHALL COMPLY WITH THE FOLLOWING
 DESIGN AND CONSTRUCTION STANDARDS AS DESCRIBED HEREIN.
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 MAY APPLY. SEE AGENCY OF HEALTH CARE ADMINISTRATION
 [AHCA] RULE 59A-11, FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 383, FLORIDA STATUTES.
  
 ? FBC 452.2.2.3
 A SEPARATE SPACE FOR A CLEAN AREA AND A CONTAMINATED
 AREA; IF IT IS NOT FEASIBLE TO PROVIDE SUCH SEPARATE
 AREAS, SPECIAL PROCEDURES SHALL BE ESTABLISHED FOR THE
 DISPOSAL OF INFECTIOUS WASTE. SANITARY WASTE
 CONTAINERS, SOILED LINEN CONTAINERS, STORAGE CABINETS
 AND AN AUTOCLAVE, PRESSURE COOKER OR OTHER EFFECTIVE
 STERILIZATION EQUIPMENT SHALL BE AVAILABLE.
 ? 452.2.11LAUNDRY.
 452.2.11.1
 WHERE LAUNDRY FACILITIES ARE PROVIDED, LAUNDRY
 FACILITIES SHALL BE OF SOUND CONSTRUCTION AND SHALL BE
 IN GOOD REPAIR AND CLEAN. ADEQUATE SPACE SHALL BE
 PROVIDED AND AREAS SHALL BE DESIGNATED FOR THE
 SEPARATION OF CLEAN AND SOILED CLOTHING, LINEN AND
 TOWELS.
  
 PLEASE REVIEW THE PLANS TO INSURE COMPLIANCE WITH THESE
 SECTIONS. IF SPECIAL PROCEDURES FOR DISPOSAL OF
 INFECTIOUS WASTE ARE TO BE EMPLOYED, THEN PLEASE STATE
 THE SAME ON THE PLANS TO SHOW COMPLIANCE.
 DISCHARGES FROM AUTOCLAVES AND OTHER STERILIZERS TO THE
 SANITARY SYSTEM SHALL COMPLY WITH FBC PL CHAPTER 8 AND
 SECTION 713.
  
 ITEM 2: BIRTHING TUB DRAINAGE
 ? 452.2.3.4
 ALL FLOOR SURFACES, WALL SURFACES, WATER CLOSETS,
 LAVATORIES, TUBS, SHOWERS, SHALL BE KEPT CLEAN, AND ALL
 APPURTENANCES OF THE STRUCTURES SHALL BE OF SOUND
 CONSTRUCTION, PROPERLY MAINTAINED, IN GOOD REPAIR AND
 FREE FROM SAFETY HAZARDS.
 REGARDING THE BIRTHING TUBS, THE ELIMINATION OF THE
 OVERFLOW WAS DONE TO ELIMINATE BACTERIA FORMING IN THAT
 SPACE. HOWEVER, THE TUB WASTE IS A DIRECT CONNECTION TO
 THE SANITARY WHICH CAN ALLOW A STOPPAGE TO BACK UP INTO
 THE TUB POTENTIALLY INTRODUCING HAZARDOUS BACTERIA INTO
 THE VESSEL. THIS CONDITION CAN BE ELIMINATED BY
 DISCHARGING THE TUB DRAIN INTO A TRAPPED AND VENTED
 INDIRECT WASTE RECEPTOR WITH AN AIR GAP. IF THE TRAPPED
 AND VENTED DIRECT CONNECTION TO THE SANITARY CONTINUES
 TO BE THE CHOICE BY THE DESIGN ENGINEER THEN IT MUST BE
 INSTALLED IN A MANNER THAT DOES NOT ALLOW THE FIXTURE
 DRAIN TO CONNECT TO THE VENT BELOW THE TRAP.
  
2019-05-30 13:53:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLEASE NOTE THAT THE LETTER SIGNED AND SEALED, DATED
 5/21/2019, PROVIDED BY STUDIO SR ARCHITECTURE AND
 DESIGN REQUESTING THAT OVERFLOWS NOT BE REQUIRED FOR
 THE BIRTHING TUB(S) HAS BEEN REVIEWED BY THIS
 DEPARTMENT AND THE TUB(S) ARE APPROVED AS NOTED ON THE
 SUBMITTALS.
  
 PLUMBING COMMEMTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. THE FOLLOWING COMMENTS ARE OFFERED AS A GUIDE
 BUT MAY NOT BE ALL INCLUSIVE. ALL REQUIREMENTS MUST BE
 SATISFACTORILY ADDRESSED ON THE PLANS PRIOR TO A
 PLUMBING REVIEW APPROVAL.
 A. 212.3 SINKS. WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
 B. PROVIDE PLAN VIEW DETAILS OF KITCHEN CONFORMING TO
 FBC ACC 804.3.1
 C. PROVIDE ELEVATION DETAILS OF KITCHEN CONFORMING TO
 FBC ACC 804.3.2
 D. ALL OPERABLE PARTS SHALL MEET THE REQUIREMENTS OF
 FBC ACC 309.
 E. SHOW ALL REQUIRED CLEAR FLOOR SPACES AND TURNING
 RADIUS AS REQUIRED BY FBC ACC 305.
 F. PROVIDE DETAILS (PLAN AND ELEVATION) OF ALL
 COMPLIANT FIXTURES SHOWING COMPLIANCE WITH FBC ACC
 CHAPTER 3 AND CHAPTER 6. INCLUDE ALL GRAB BARS, SHOWER
 SEATS, CONTROLS, TOILET ROOM ACCESSORIES AND RELATED
 MILLWORK.
 G. SEE FBC ACC 604.8.1.2. TOILET ROOM DOORS SHALL BE
 LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL OR
 PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED
 IN THE FRONT PARTITION, THE DOOR OPENING SHALL BE 4
 INCHES (100 MM) MAXIMUM FROM THE SIDE WALL FARTHEST
 FROM THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL
 OR PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100
 MM) MAXIMUM FROM THE FRONT PARTITION. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
 H. TOILET ROOM(S) ACCESSIBLE TO THE WAITING AREA SHALL
 MEET THE REQUIREMENTS OF FBC ACC 213
 2. PER FBC PL 403.1, 403.2 AND TABLE 403.1, BASED UPON
 THE OCCUPANT LOAD, SEPARATE TOILET ROOM FACILITIES ARE
 REQUIRED FOR EACH SEX AND MUST BE ACCESSIBLE FROM THE
 WAITING ROOM. THE DESIGN CRITERIA FOR THE PROJECT
 INCLUDED 2017 EXISTING BUILDING CODE CHAPTER 801,
 SECTION 801.3. PLEASE NOTE CHAPTER 810 CONCERNING
 PLUMBING WHICH MAY ALLOW AN EXCEPTION TO THE SEPARATE
 FACILITIES REQUIREMENT.
 3. PER FBC PL 403.1 AND TABLE 403.1, BASED UPON THE
 OCCUPANT LOAD, A DRINKING FOUNTAIN IS REQUIRED; SAID
 DRINKING FOUNTAIN SHALL MEET THE REQUIREMENTS OF 410.1
 AND 410.3 (MINIMUM TWO REQUIRED, ONE FOR WHEELCHAIR AND
 ONE FOR STANDING, OR SINGLE BI-LEVEL), AS WELL AS
 MEETING THE REQUIREMENTS OF FBC ACC 211.2 AND 602.
 4. SINKS FROM LAB RM #126 AND CONSULTATION 2 RM #123
 SHALL NOT CONNECT TO THE WET VENT SERVICING BATH #2 RM
 #113 PER FBC PL 912.1 AND FBC RES P3108.1. CONNECT TO
 BRANCH DOWNSTREAM OF BATHROOM FIXTURES AHEAD OF BRANCH
 SERVICING BATH 1 RM #105 AND BIRTH RM 1 RM #112. MAKE
 CORRECTION ON P1.01 AND P2.01 PER WPB FBC 107.2.1.
 5. RE: P2.01 SANITARY ISOMETRIC; A SINK IS SHOWN
 CONNECTING TO BRANCH BETWEEN BATH #2 AND BIRTH #1
 TUB/BATH #1. THIS SINK DOES NOT APPEAR ON P1.01 OR
 A102.1 FLOOR PLANS. PLEASE CLARIFY PER WPB FBC 107.2.1.
 6. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING
 INFORMATION:
 A. IDENTIFY GAS TANKLESS WATER HEATERS ON P1.01 FLOOR
 PLAN AND INTEGRATE WITH WATER DISTRIBUTION.
 B. ON P2.01 TANKLESS HOT WATER SYSTEM DETAIL, PROVIDE
 ADDITIONAL DETAIL INTEGRATING THE POTABLE WATER SERVICE
 WITH THE HOT WATER SYSTEM AND TO HOUSE DISTRIBUTION.
 C. PROVIDE SCHEDULE, DETAIL AND SPECIFICATION FOR HOT
 WATER RECIRCULATING PUMP; INCLUDE ELECTRICAL
 CHARACTERISTICS AND CONTROLS. COMPLY WITH THE
 REQUIREMENTS OF FBC EC C404 AND FBC PL 607.
 7. REGARDING THE SIZING OF THE WATER DISTRIBUTION
 SYSTEM, PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR
 SIZING OF THE SYSTEM. IDENTIFY FIXTURE, QUANTITY AND
 WSFU/ GPM FOR EACH FIXTURE WITH TOTALS FOR COLD AND HOT
 WATER.
 8. REGARDING ?PLUMBING SPECIFICATIONS? ON P2.01, PER
 WPB FBC 107.2.1, MAKE THE FOLLOWING CHANGES:
 A. SECTION 2-CODES AND STANDARDS; REPLACE ?STANDARD
 PLUMBING CODE (SBCCI)? WITH ?FLORIDA PLUMBING CODE 2017
 6TH EDITION?
 B. SECTION 5, -MATERIALS, ITEM F ; REPLACE ?AIR CHAMBER
 OR SHOCK ABSORBERS? WITH ?WATER HAMMER ARRESTORS
 CONFORMING TO ASSE 1010?. ADD AT THE END OF NOTE ?AND
 AT DISHWASHER, ICE LINE AND CLOTHES WASHER.?
 C. SECTION 5 -MATERIALS, ADD SPECIFICATION FOR
 INSULATION OF THE HOT WATER CONFORMING TO THE
 REQUIREMENTS OF FBC EC C404.
 9. REGARDING THE WATER DISTRIBUTION SYSTEM, PER WPB FBC
 107.2.1, PROVIDE FULL OPEN VALVE ON EACH DOWN FEED PIPE
 PER FBC PL 606.1(5) AND SHOW ON THE WATER DISTRIBUTION
 ISOMETRIC. VALVES SHALL BE ACCESSIBLE PER FBC PL 606.3.
 VALVES SHALL BE IDENTIFIED AS REQUIRED BY FBC PL 606.4.
 10. REGARDING THE WATER DISTRIBUTION SYSTEM, PER WPB
 FBC 107.2.1, PROVIDE FULL OPEN VALVE AT THE BASE OF
 SUPPLY TO SECOND FLOOR PER FBC PL 606.1(4) EFFECTIVELY
 PREVENTING IMPACT OF THE FIRST FLOOR SYSTEM AND SHOW ON
 THE WATER DISTRIBUTION ISOMETRIC. THE HOT WATER RETURN
 SHOULD BE MODIFIED TO NEGATE ANY IMPACT ON THE FIRST
 FLOOR. VALVES SHALL BE ACCESSIBLE PER FBC PL 606.3.
 VALVES SHALL BE IDENTIFIED AS REQUIRED BY FBC PL 606.4.
 11. PER WPB CCCM SECTION C PARA III AND IV, A LEAD FREE
 BACKFLOW PREVENTER IS REQUIRED. INDICATE ON P1.01, THE
 LOCATION, SIZE AND TYPE. SHOW ON P2.02 WATER
 DISTRIBUTION ISOMETRIC. INDICATE EXISTING OR NEW. TYPE
 SHALL BE AS REQUIRED BY THE CITY OF WEST PALM BEACH
 UTILITIES (561-822-2244) MEETING THE REQUIREMENTS OF
 WPB CCCM AND FBC PL 608. UP TO DATE CERTIFICATION OF
 THE DEVICE WILL BE REQUIRED FOR FINAL INSPECTION.
 12. PER WPB FBC 107.2.1, NOTE ON THE PLUMBING FIXTURE
 SCHEDULE THE REQUIRED TEMPERATURE LIMITING DEVICES TO
 BE EMPLOYED AT THE FIRST FLOOR LAVATORIES; SHOW
 COMPLIANCE WITH FBC PL 416.5 AND CONFORM TO ASSE 1070
 OR CSA B125.3.
 13. PER WPB FBC 107.2.1, NOTE ON THE PLUMBING FIXTURE
 SCHEDULE THE REQUIRED TEMPERATURE LIMITING DEVICES TO
 BE EMPLOYED AT THE BATHTUBS AND SHOWERS; SHOW
 COMPLIANCE WITH FBC PL 424.5.
 14. REMOVE DUPLICATE ARCHITECTURAL PAGES PER WPB FBC
 107.2.1.
 15. PER WPB FBC 107.2.1, ARCHITECT SHALL LOCATE THE
 WATER METER AND BACKFLOW PREVENTER ON A0.02. AN
 APPROVED PLUMBING REVIEW WILL DEPEND UPON THIS
 REQUIREMENT BEING MET.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19010578 2717 POINSETTIA AVE
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-12 Cont ID  
Sent By jesmith Date 2019-02-12 Time 12:42 Rev Time 0.00
Received By jesmith Date 2019-02-12 Time 12:42 Sent To  
Notes
2019-02-12 14:03:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW; DENIED
 PLUMBING COMMENTS
  
 1. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 HAVE NOT BEEN DETERMINED. PLEASE, PROVIDE SO THAT THE
 MINIMUM PLUMBING FACILITIES REQUIREMENTS CAN BE
 DETERMINED AND PLANS CAN BE REVIEWED FOR COMPLIANCE PER
 WPB FBC 107.3.5.1.3 (1).
 2. SINKS FROM LAB RM #126 AND CONSULTATION 2 RM #123
 SHALL NOT CONNECT TO THE WET VENT SERVICING BATH 1 RM
 #105 AND BIRTH RM 1 RM #112 PER FBC PL 912.1 AND FBC
 RES P3108.1. CONNECT DOWNSTREAM OF TUB. MAKE CORRECTION
 ON P1.01 AND P2.01 PER WPB FBC 107.2.1.
 3. P1.01 SECOND FLOOR PLAN INDICATES TWO (2)
 LAVATORIES, ONE (1) WATER CLOSET, ONE (1) SHOWER AND
 ONE (1) TUB. P2.01 SECOND FLOOR SANITARY ISO INDICATES
 TWO (2) LAVATORIES, TWO (2) WATER CLOSETS AND ONE (1)
 SHOWER. PLEASE CLARIFY PER WPB FBC 107.2.1.
 4. PROVIDE WATER DISTRIBUTION ISO INDICATING SIZING,
 VALVING, REQUIRED BACKFLOW PREVENTERS AND OTHER
 APPURTENANCES REQUIRED IN THE SYSTEM PER WPB FBC
 107.3.5.1.3 (3).PROVIDE WATER DISTRIBUTION LAYOUT ON
 PLUMBING FLOOR PLAN CORRESPONDING TO THE ISO PER WPB
 FBC 107.2.1.
 5. PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING THE
 FIXTURE TYPE, WATER REQUIREMENTS, WASTE, REQUIRED
 TEMPERATURE LIMITING DEVICES TO BE EMPLOYED WHERE
 APPLICABLE AND TYPE OF BACKFLOW PREVENTION REQUIRED
 WHERE APPLICABLE PER FWPNB FBC 107.2.1..
 6. PROVIDE A DETAIL OF THE BIRTHING ROOM TUBS SHOWING
 HOW WATER SOURCE IS TO BE APPLIED PER WPB FBC 107.2.1.
  
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-30 Cont ID  
Sent By llouie Date 2019-08-30 Time   Rev Time 0.00
Received By llouie Date 2019-08-29 Time   Sent To  
Notes
2019-08-30 14:24:12ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) CLASSIFIED MEDICAL OFFICE. NO OVERNIGHT STAYS
 PERMITTED.
  
 2.) SEPARATE PERMITS REQUIRED FOR: HARDSCAPES AND
 PARKING AND LANDSCAPING.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-24 Cont ID  
Sent By llouie Date 2019-05-24 Time   Rev Time 0.00
Received By llouie Date 2019-05-24 Time 08:53 Sent To  
Notes
2019-05-24 08:54:07** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE USE.
 ACCORDING TO BUSINESS TAX #0000048302 (BLISS BIRTH AND
 WELLNESS CENTER), THE PROPOSED USE AT THIS ADDRESS IS
 AN OUTPATIENT MEDICAL OFFICE. THIS MEANS THAT PATIENTS
 ARE NOT PERMITTED TO STAY AT THE FACILITY MORE THAN 24
 HOURS. PLEASE CLARIFY. [1/30/19 REPEAT COMMENT: A
 WRITTEN STATEMENT SHALL BE PROVIDED IN THE PLANS AND/OR
 IN A RESPONSE LETTER TO PROVIDE ASSURANCE TO ZONING
 STAFF]
  
 2.) THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($92,443) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. [1/30/19 REPEAT
 COMMENT: A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED
 PRIOR TO ZONING SIGN-OFF OF THIS PERMIT. THE LANDSCAPE
 PLAN MUST DEMONSTRATE THAT THE PROJECT MEETS THE
 MINIMUM LANDSCAPE REQUIREMENTS TO THE GREATEST EXTENT
 POSSIBLE FOR A SINGLE-FAMILY DWELLING AND LANDSCAPING
 FOR THE PARKING. CONTACT RAY CARANCI, THE CITY'S
 LANDSCAPE PLANNER, @ 561-855-1462 IF THERE ARE ANY
 QUESTIONS.]
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CMUD - EDGE SUBDISTRICT
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-30 Cont ID  
Sent By llouie Date 2019-01-30 Time   Rev Time  
Received By llouie Date 2019-01-30 Time   Sent To  
Notes
2019-01-30 11:14:14** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE USE.
 ACCORDING TO BUSINESS TAX #0000048302 (BLISS BIRTH AND
 WELLNESS CENTER), THE PROPOSED USE AT THIS ADDRESS IS
 AN OUTPATIENT MEDICAL OFFICE. THIS MEANS THAT PATIENTS
 ARE NOT PERMITTED TO STAY AT THE FACILITY MORE THAN 24
 HOURS. PLEASE CLARIFY.
  
 2.) THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($92,443) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CMUD - EDGE SUBDISTRICT
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved