Plan Review Details - Permit 19010525
Plan Review Stops For Permit 19010525
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 08:13 Rev Time 0.00
Received By shill Date 2019-05-16 Time 08:13 Sent To  
Notes
2019-05-09 10:27:44CHANGED TO RES REMODEL AS IS A TWO UNIT BUILDING.
 VERIFY VALUE IS CORRECT. SEE 5K ON ELECTRICAL
 APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-12 Cont ID  
Sent By jwitmer Date 2019-02-12 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2019-02-12 Time 11:52 Sent To  
Notes
2019-02-12 14:13:572017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010525
 ADD: 919 2ND ST.
 CONT: INGECO CONTRACTORS LLC
 TEL: 561-315-3819
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 12/2019
 ACTION: DENIED
  
 1) PLEASE ASK FOR A RECORDS RESEARCH REQUEST FOR THIS
 PROPERTY. IT WOULD APPEAR THAT THIS BUILDING MAY HAVE
 BEEN CONVERTED FROM A 2 UNIT TO A 4 UNIT APARTMENT
 BUILDING WITHOUT A PERMIT. CONTACT CRAIG MCPHERSON FOR
 A RECORDS RESEARCH REQUEST BE COMPLETED FOR THIS
 PROPERTY. MR. MCPHERSON CONTACT NUMBER IS 561-805-6684.
  
 IT ALSO APPEARS THAT THERE HAS NEVER BEEN A RENTAL
 LICENSE FOR THIS PROPERTY, NEITHER FOR 2 UNITS OR 4
 UNITS. WE HAVE RESEARCHED THIS BY ADDRESS AS WELL AS BY
 PCN.
 IN REVIEWING THE CITY RECORDS (GREEN CARDS) FOR 919 2ND
 ST. IT WAS BUILT AS AN APT. / DUPLEX. THE GREEN CARD
 WAS CREATED IN 11/08/62.
  
 2017 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 2) THE ONLY SHEET SUBMITTED IS AN ELECTRICAL SHEET E1
 IN THE BOTTOM CENTER THERE IS WHAT APPEARS TO BE A
 CONCEPTUAL DRAWING OF STAIR LAYOUT. THERE IS NOT ENOUGH
 INFORMATION ON THIS SHEET TO DO A REVIEW. THERE IS A
 NOTE THAT STATES THE RISERS ARE TO BE MAXIMUM OF 8
 INCHES AND THE MINIMUM OF 6.75 INCHES.
 PLEASE REVIEW THE 2017 FBC-B 1011.5.2 1011.5.2 RISER
 HEIGHT AND TREAD DEPTH. STAIR RISER HEIGHTS SHALL BE 7
 INCHES MAXIMUM AND 4 INCHES MINIMUM.
  
 3) THERE IS A 2ND NOTE THAT INDICATES SEE DETAIL 2
 SHEET S-1. THERE IS NO SHEET S-1 ATTACHED. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT CODE
 THE STAIRS WERE DESIGNED TO, TO WHAT LIVE LOAD, TYPE OF
 MATERIAL FOR THE SUPPORTING STRINGERS, SPECIES, GRADE
 OR SIZE OF THE TIMBERS, HOW MANY STRINGERS THERE WILL
 BE OR HOW MANY THE VERTICAL UPRIGHTS AND SPACING, NO
 INFORMATION ON THE LANDING AND THE HANDRAIL GUARDRAIL
 SYSTEMS. MISSING ANCHORS FOR WIND AND THE WIND DESIGN
 CRITERIA.
  
 5) PLEASE ALSO BE AWARE OF THE CODE VIOLATION OF THE
 WINDOWS WITHIN 10 FEET OF THE STAIR. 2017 FBC-B 1027.6
 EXTERIOR EXIT STAIRWAY AND RAMP PROTECTION. EXTERIOR
 EXIT STAIRWAYS AND RAMPS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1023.2.
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS
 FROM NORMALLY OCCUPIED SPACES. WHERE A VERTICAL PLANE
 PROJECTING FROM THE EDGE OF AN EXTERIOR EXIT STAIRWAY
 OR RAMP AND LANDINGS IS EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES THE
 EXTERIOR WALL SHALL BE RATED IN ACCORDANCE WITH SECTION
 1023.7.
 1023.7 INTERIOR EXIT STAIRWAY AND RAMP EXTERIOR WALLS.
 EXTERIOR WALLS OF THE INTERIOR EXIT STAIRWAY OR RAMP
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 705 FOR
 EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY OR RAMPS
 AND THE WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF
 THE BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES, THE
 BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048 MM)
 HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED OPENING
 SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1
 HOUR. OPENINGS WITHIN SUCH EXTERIOR WALLS SHALL BE
 PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. THIS
 CONSTRUCTION SHALL EXTEND VERTICALLY FROM THE GROUND TO
 A POINT 10 FEET ABOVE THE TOPMOST LANDING OF THE
 STAIRWAY OR RAMP, OR TO THE ROOF LINE, WHICHEVER IS
 LOWER.
  
 6) MINIMUM STAIRWAY WIDTH SEE 2017 FBC-B 1011.2 WIDTH
 AND CAPACITY. THE REQUIRED CAPACITY OF STAIRWAYS SHALL
 BE DETERMINED AS SPECIFIED IN SECTION 1005.1, BUT THE
 MINIMUM WIDTH SHALL BE NOT LESS THAN 44 INCHES. SEE
 SECTION 1009 FOR ACCESSIBLE MEANS OF EGRESS STAIRWAYS.
 EXCEPTIONS: 1.STAIRWAYS SERVING AN OCCUPANT LOAD OF
 LESS THAN 50 SHALL HAVE A WIDTH OF NOT LESS THAN 36
 INCHES.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-09 Cont ID  
Sent By jleahy Date 2019-07-09 Time 12:02 Rev Time 0.00
Received By jleahy Date 2019-07-09 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-06-07 Cont ID  
Sent By jpearson Date 2019-06-07 Time 14:29 Rev Time 0.00
Received By jpearson Date 2019-06-07 Time 14:29 Sent To  
Notes
2019-06-07 13:44:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. CORRECTED.
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED IS THE TYPE
 PERMITTED FOR A SINGLE DWELLING UNIT. NEC 220 (LOAD
 CALCULATION STILL NOT CORRECT. WATER HEATER DOES NOT
 MATCH WHAT IS SHOWN IN PANEL SCHEDULE, MATH IS NOT
 CORRECT, BUILDING LOAD SHOWS A WASHER/DRYER BUT THIS IS
 NOT SHOWN ON PLAN OR IN PANEL SCHEDULES, AND SHOULD BE
 INCLUDED IN THE LOAD CALCULATION FOR WHICHEVER PANEL IT
 IS FED FROM. PROVIDE ACCURATE LOAD CALCULATION.)
 4. PROVIDE ACCURATE RISER DIAGRAM. RISER SHOWS ONE
 SERVICE ENTRANCE TO A METER CAN, BUT THE NOTE SAYS THIS
 IS 4 METER CANS. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED. 4 METER CANS CANNOT FEED ONE DISCONNECT. NEC
 215.5; WPB FBC 107.2.1 (NOT CORRECTED. RISER DOES NOT
 MATCH WHAT IS SHOWN ON PLAN.)
 5. SERVICE DROP IS SHOWN TO BE SUPPLIED BY FPL. IF THIS
 CHANGES, A REVISION TO THE PLAN WILL BE NECESSARY. WPB
 FBC 107.2.1
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 (DEFERRED SUBMITTAL ACCEPTED.)
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9 (NOT PROVIDED.)
 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4 (ONLY ONE PANEL SCHEDULE WAS PROVIDED.
 THERE ARE MULTIPLE PANELS. PROVIDE FOR EACH.)(3RD
 REVIEW: THE PANEL SCHEDULES PROVIDED DO NOT MATCH WHAT
 IS SHOWN ON FLOOR PLAN. WHERE IS THE PANEL SCHEDULE FOR
 THE OUTSIDE METER/MAIN? ARE ANY ITEMS FED FROM THIS?)
 11. CORRECTED.
 12. CORRECTED.
 13. RISER DIAGRAM AND PLAN HAS SEVERAL DISCREPANCIES AS
 TO PANEL SIZE. SOME AREAS SHOW 100 AMP PANELS, ANOTHER
 AREA SHOWS 125 AMP PANELS, ANOTHER SHOWS 150 AMP
 PANELS, AND ONE SHOWS A 200 AMP PANEL. CORRECT
 DISCREAPNCIES. WPB FBC 107.2.1 (PLAN AND RISER STILL DO
 NOT MATCH.)
  
 NEW COMMENTS:
  
 14. FOR EACH DWELLING UNIT OF A MULTIFAMILY DWELLING
 WHERE THE DWELLING UNIT IS LOCATED AT GRADE LEVEL AND
 PROVIDED WITH INDIVIDUAL EXTERIOR ENTRANCE/EGRESS, AT
 LEAST ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM
 GRADE AND NOT MORE THAN 2.0 M (61?2 FT) ABOVE GRADE
 LEVEL SHALL BE INSTALLED. PROVIDE CORRECTION. NEC
 210.52(E)(2)
 15. SHOW LOCATION ON PLAN OF A/C UNITS AND PROVIDE A
 GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-15 Cont ID  
Sent By jpearson Date 2019-05-15 Time 15:00 Rev Time 0.00
Received By jpearson Date 2019-05-15 Time 12:55 Sent To  
Notes
2019-05-15 13:13:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. CORRECTED.
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED IS THE TYPE
 PERMITTED FOR A SINGLE DWELLING UNIT. NEC 220 (NOT
 CORRECT. THERE ARE TWO LOAD CALCULATIONS, BUT THEY ARE
 IDENTICAL AND BOTH MARKED UNIT 1. THERE IS NO LOAD
 CALCULATION FOR THE ENTIRE SERVICE.)
 4. PROVIDE ACCURATE RISER DIAGRAM. RISER SHOWS ONE
 SERVICE ENTRANCE TO A METER CAN, BUT THE NOTE SAYS THIS
 IS 4 METER CANS. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED. 4 METER CANS CANNOT FEED ONE DISCONNECT. NEC
 215.5; WPB FBC 107.2.1 (NOT CORRECTED. RISER SHOWS ONE
 METER WITH 2 PANELS, BUT THE PLAN SHOWS AT LEAST 3
 PANELS. CORRECT DISCREPANCIES.)
 5. WIRE SIZE SHOWN IN SERVICE DROP IS NOT ADEQUATELY
 SIZED TO HANDLE THE LOAD STATED. PROVIDE CORRECTION.
 NEC 310.15(B)(16) (NOT CORRECTED.)
 6. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1(NOT PROVIDED.)
 7. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2
 AS APPLICABLE. (NOT PROVIDED.)
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 (NOT
 PROVIDED.)
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9 (NOT PROVIDED.)
 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4 (ONLY ONE PANEL SCHEDULE WAS PROVIDED.
 THERE ARE MULTIPLE PANELS. PROVIDE FOR EACH.)
 11. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12 (NOT CORRECTED.)
  
 NEW COMMENTS:
  
 12. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 13. RISER DIAGRAM AND PLAN HAS SEVERAL DISCREPANCIES AS
 TO PANEL SIZE. SOME AREAS SHOW 100 AMP PANELS, ANOTHER
 AREA SHOWS 125 AMP PANELS, ANOTHER SHOWS 150 AMP
 PANELS, AND ONE SHOWS A 200 AMP PANEL. CORRECT
 DISCREAPNCIES. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jpearson Date 2019-02-21 Time 15:48 Rev Time 0.00
Received By jpearson Date 2019-02-21 Time 15:50 Sent To I
Notes
2019-02-21 15:48:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. A FULL REVIEW IS NOT POSSIBLE UNTIL BUILDING AND
 ZONING COMMENTS ARE SATISFACTORILY ADDRESSED. WPB FBC
 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED IS THE TYPE
 PERMITTED FOR A SINGLE DWELLING UNIT. NEC 220
 4. PROVIDE ACCURATE RISER DIAGRAM. RISER SHOWS ONE
 SERVICE ENTRANCE TO A METER CAN, BUT THE NOTE SAYS THIS
 IS 4 METER CANS. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED. 4 METER CANS CANNOT FEED ONE DISCONNECT. NEC
 215.5; WPB FBC 107.2.1
 5. WIRE SIZE SHOWN IN SERVICE DROP IS NOT ADEQUATELY
 SIZED TO HANDLE THE LOAD STATED. PROVIDE CORRECTION.
 NEC 310.15(B)(16)
 6. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 7. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2
 AS APPLICABLE.
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4
 11. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2019-05-09 Cont ID  
Sent By skennedy Date 2019-05-09 Time 10:27 Rev Time 0.00
Received By skennedy Date 2019-05-09 Time 10:27 Sent To  
Notes
2019-05-09 10:29:39THIS IS A TWO FAMILY STRUCTURE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-31 Cont ID  
Sent By pleduc Date 2019-01-31 Time   Rev Time 0.00
Received By pleduc Date 2019-01-31 Time 15:16 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2019-02-01 Cont ID  
Sent By fmittner Date 2019-02-01 Time 16:18 Rev Time 0.00
Received By fmittner Date 2019-02-01 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-09 Cont ID  
Sent By jleahy Date 2019-07-09 Time 12:02 Rev Time 0.00
Received By jleahy Date 2019-06-28 Time 12:41 Sent To  
Notes
2019-07-01 12:41:52RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-06-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-31 Time 14:30 Sent To  
Notes
2019-06-03 14:30:45RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 08:14 Rev Time 0.00
Received By shill Date 2019-04-30 Time 15:36 Sent To  
Notes
2019-05-09 10:49:16ROUTED FROM ZONING TO PERMIT LIBRARIAN 5/9/19 EL
2019-05-01 15:36:19B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-21 Time   Rev Time 0.00
Received By skennedy Date 2019-01-29 Time 16:43 Sent To  
Notes
2019-02-05 15:01:34ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/5/2019 EL
2019-01-29 16:45:16B14

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-05-13 Cont ID  
Sent By gjohnson Date 2019-05-13 Time 14:02 Rev Time 0.00
Received By gjohnson Date 2019-05-13 Time 10:49 Sent To  
Notes
2019-05-13 14:03:47NO PLUMBING SHOWN ON PLAN.
 PLANS AND PERMIT REQUIRED FOR ANY PLUMBING WORK.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-09 Cont ID  
Sent By elevesqu Date 2019-05-09 Time 10:49 Rev Time 0.00
Received By elevesqu Date 2019-05-09 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By elevesqu Date 2019-02-05 Time 15:01 Rev Time 0.00
Received By elevesqu Date 2019-02-04 Time 14:43 Sent To  
Notes
2019-02-05 15:01:15PROPERTY RECORD SEARCH FOUND THAT ONLY TWO UNITS WERE
 LEGALLY CREATED IN THIS BUILDING.
  
 PLEASE PERFORM PROPERTY SEARCH TO SEE IF THERE ARE ANY
 LEGAL RECORDS OF 4 UNITS AND RESUBMIT.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426