Plan Review Details - Permit 19010515
Plan Review Stops For Permit 19010515
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By shill Date 2019-04-16 Time 11:31 Rev Time 0.00
Received By jduprey Date 2019-04-16 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-03-12 Cont ID  
Sent By shill Date 2019-03-12 Time 09:39 Rev Time 0.00
Received By shill Date 2019-03-12 Time 09:39 Sent To  
Notes
2019-03-12 09:42:22PROVISO/REDLINE:
 FBC B 2509.2, MATERIALS USED FOR A BASE FOR TILE SHALL
 COMPLY WITH TABLE B 2509.2
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-18 Cont ID  
Sent By jpearson Date 2019-03-18 Time 10:54 Rev Time 0.00
Received By jpearson Date 2019-03-18 Time 10:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-05 Cont ID  
Sent By pleduc Date 2019-03-05 Time   Rev Time 0.00
Received By pleduc Date 2019-03-05 Time 11:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-04 Cont ID  
Sent By pleduc Date 2019-02-04 Time   Rev Time 0.00
Received By pleduc Date 2019-01-31 Time 12:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2019-04-03 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-03-21 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-20 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-20 Cont ID  
Sent By lmarchan Date 2019-02-20 Time 16:41 Rev Time 0.00
Received By lmarchan Date 2019-01-29 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-03-21 Cont ID  
Sent By ccole Date 2019-03-21 Time 13:38 Rev Time 0.00
Received By ccole Date 2019-03-21 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 14:20 Rev Time 0.00
Received By gjohnson Date 2019-04-18 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-03-21 Cont ID  
Sent By gjohnson Date 2019-03-21 Time 09:02 Rev Time 0.00
Received By tklarge Date 2019-03-20 Time 10:00 Sent To  
Notes
2019-03-21 06:26:561) SHT. A 2.1.1 - DETAIL #12 - THE SHOWER FLOOR SHALL
 BE PITCHED A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN
 PER THE 2017 FBC-PLUMBING SEC. 417.5.2.
 2) SHT. A 3.02 - DETAILS #2 & #3 - THE OUTLET OF THE
 TOILET PAPER DDISPENSER SHALL BE LOCATED 19 INCHES
 MAXIMUM ABOVE THE FINISH FLOOOR, NOT TWO FEET AS SHOWN.
 2017 FBC-ACCESS. SEC.604.9.6.
 3) SHT. A 3.02 - DETAIL #3 - THE TOILET PAPER DISPENSER
 SHALL BE LOCATED A MINIMUM OF 7 INCHES AND A AMXIMUM OF
 9 INCHES FROM THE FRONT OF THE TOILET BOWL TO THE
 CENTERLINE OF THE TOILET PAPER DISPENSER.2017
 FBC-ACCESS. SEC. 604.9.6.
 4) SHT. A 3.02 - DETAIL #3 - THE SEAT HEIGHT OF A WATER
 CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES
 MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF
 THE SEAT. THE DETAIL APPEARS TO SHOW THE MEASUREMNT TO
 THE TOP OF THE TOILET BOWL.
 5) SHT. A 3.02 - DETAIL #3 - THE GRAB BAR IN THE SHOWER
 SHALL BE LOCATED A MAXIMUM OF 6 INCHES FROM ADJACENT
 WALLS PER 2017 FBC-ACCESS. SEC.608.3.2. THE DETAIL
 SHOWS 9 INCHES ON ONE SIDE OF THE GRAB BAR. ALSO, SHOW
 THE HEIGHT OF THE GRAB BARS IN THE SHOWER.
 6) SHT. P 4.1 - THE PLANS CALL OUT A HUB DRAIN BELOW
 THE LAVATORY. WHAT WILL BE DISCHARGING INTO THIS HUB
 DRAIN? HOW WILL THE TRAP SEAL BE MAINTAINED IN THE TRAP
 TO PREVENT SEWER GASES FROM ENTERING THE STRUCTURE?
 CLARIFY.
 7) NOTE ON THE PLAN OR SHOW ON THE WATER ISOMETRIC THAT
 A BACKFLOW PREVENTER WILL BE INSTALLED ON THE WATER
 FILTER,REFRIGERATOR ICEMAKER, AND THE COFFEE MAKER.
 2017 FBC-PLUMBING SEC. 608.3, 608.16.10.
 8) SHT. A 3.02 - DETAIL #2 - SHOWS THE WATER CLOSET AT
 1 FOOT 5 INCHES TO THE CENTERLINE OF THE TOILET WHICH
 WOULD MAKE THE GRAB BAR 5 INCHES FROM THE ADJACENT
 WALL, NOT 6 INCHES AS SHOWN TO COMPLY WITH 2017
 FBC-ACCESS. SEC.504.5.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-20 Cont ID  
Sent By gjohnson Date 2019-02-20 Time 08:15 Rev Time 0.00
Received By gjohnson Date 2019-02-20 Time 08:15 Sent To  
Notes
2019-02-20 08:30:22 
 1ST REVIEW: 19010515
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE PRIVATE BATHROOM DOES NOT MEET THE EXEMPTION FOR
 A SINGLE OCCUPANT ACCESSED ONLY THROUGH A PRIVATE
 OFFICE IT SHALL MEET ALL THE REQUIREMENTS OF THE FBC
 ACC CH 6
 2. THE SHOWER DIMENSIONS SHALL COMPLY WITH ONE OF THE
 FOLLOWING FBC ACC 608.2.1, 608.2.2, 608.2.3
 3. THE CONTROLS SHALL COMPLY WITH THE REQUIREMENTS OF
 THE TYPE OF SHOWER. FBC ACC 608.5.1, 608.5.2, 608.5.3
 4. PLEASE NOTE ON THE PLAN OR SHOW ON WATER ISOMETRIC A
 BACKFLOW IS REQUIRED ON THE WATER FILTER , REFRIGERATOR
 ICE MAKER AND COFFEE MAKER .PER FBC PL 608.3, 608.16.10
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2019-04-16 Time 11:32 Sent To  
Notes
2019-04-16 11:32:32BUILDING - OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-03-12 Cont ID  
Sent By shill Date 2019-03-12 Time 09:56 Rev Time 0.00
Received By shill Date 2019-03-12 Time 09:56 Sent To  
Notes
2019-03-12 09:56:34PROVISO: NEW PAGES SUBMITTED NEXT REVIEW CYCLE REQUIRE
 VERIFICATION
  