| Plan Review Stops For Permit 19010469 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-28 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-28 |
Time |
10:56 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-05-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-08 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-08 |
Time |
18:11 |
Sent To |
I |
|
| Notes |
| 2019-05-08 18:37:10 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED ENGINEERING THAT WAS SUBMITTED | | | FOR THE DIVERSITECH PADS IS LIMITED TO GENERAC | | | GENERATORS WITH SPECIFIC DIMENSIONS AND WEIGHT. SEE | | | LIMITS AND REQUIREMENTS OF USE ON PAGE 1 OF THE | | | DOCUMENTS. IN ORDER TO USE THESE PADS FOR THE POOL | | | HEATERS, YOU WILL HAVE TO PROVIDE A COMPARATIVE | | | ANALYSIS TO SHOW THAT THE DIMENSIONS, WEIGHT AND | | | ANCHORING ARE EQUAL TO THE GENERATOR THAT THE PAD IS | | | DESIGNED FOR. YOU WILL ALSO NEED TO SUBMIT THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE POOL HEATER WITH | | | ITS DIMENSIONS AND WEIGHT SPECIFIED. FBC 1609.1, FBCM | | | 301.15 | | | ALTERNATELY, YOU CAN FORM AND POUR A 4" CONCRETE SLAB | | | IN PLACE. YOU WILL HAVE TO SUBMIT A DRAWING SHOWING THE | | | DIMENSIONS OF THE SLAB WITH WIRE MESH OF FIBER-MESH | | | CONCRETE. YOUR NAME AND SIGNATURE AND THE ADDRESS OF | | | THE PROJECT IS REQUIRED ON THE DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-04-24 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-04-24 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2019-04-24 17:17:13 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS ( MIAMI-DADE | | | NOA OR FLORIDA ) OR SIGNED AND SEALED SITE SPECIFIC | | | ENGINEERING FOR THE EQUIPMENT PADS FOR WIND LOADS. FBC | | | 1609.1, FBCM 301.15 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-01-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-01-23 |
Time |
06:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-01-23 |
Time |
06:40 |
Sent To |
|
|
| Notes |
| 2019-01-23 07:40:15 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SCOPE OF WORK FOR THIS PROJECT IS CONSIDERED A | | | MODIFICATION TO THE EXISTING PUBLIC POOL. SUBMIT A COPY | | | OF THE STAMPED RECEIPT FROM THE FLORIDA DEPARTMENT OF | | | HEALTH (PALM BEACH COUNTY HEALTH DEPARTMENT). SEE FAC | | | 64E-9.005 & FBC 105.1.4 | | | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED PLANS SHOWING | | | THE LOCATION OF THE PROJECT, LOCATION OF THE NEW AND | | | EXISTING EQUIPMENT AND ANCHORING OF THE EQUIPMENT | | | WINDLOADS. FBC 107.2.1 | | | | | | 3) THE DESCRIPTION OF WORK AND VALUE ON THE APPLICATION | | | WAS REVISED TO REMOVE THE RESURFACING OF THE WADING | | | POOL. REVISE THE SCOPE OF WORK ON THE OTHER SUBMITTAL | | | DOCUMENTS TO MATCH THE APPLICATION. FBC 107.2.1 | | | | | | 4) ADDITIONAL APPLICATIONS AND PERMITS WILL BE REQUIRED | | | FOR POOL PLUMBING AND ELECTRICAL. FBC 105.1.4 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-05-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-05-02 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-05-02 |
Time |
12:07 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-04-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-04-25 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-04-25 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-02-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-02-01 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-02-01 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2019-02-01 10:01:33 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SUBMIT A SET OF DRAWINGS (2) FOR REVIEW. | | | | | | SHOWING ELECTRICAL WORK, SIZE OF CONDUCTORS AND CIRCUIT | | | PROTECTION. | | | | | | BONDING IF RQUIRED. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2019-02-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-23 |
Time |
04:59 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-02-23 |
Time |
04:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-28 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-22 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2019-05-28 10:24:58 | PLUMBING COMPLETE; ROUTED TO RMCDOUGAL | | 2019-05-23 16:18:37 | RESUB ROUTED TO THUNT | | | **TRAVELLING TOGETHER - 19010469, 19010470, 19010471, & | | | 19010472** |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-05-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-08 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-04-26 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2019-04-29 14:58:17 | RESUB ROUTED TO JLEAHY | | | **TRAVELLING TOGETHER - 19010469, 19010470, 19010471, & | | | 19010472** |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-04-25 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-04-12 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2019-04-16 15:02:12 | RESUB ROUTED TO ZONING INBOX | | | **TRAVELLING TOGETHER - 19010469, 19010470, 19010471, & | | | 19010472** |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-02-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-23 |
Time |
05:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-01-14 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2019-01-15 13:12:09 | ROUTED TO ZONING INBOX | | | **TRAVELLING TOGETHER - 19010469, 19010470, 19010471, & | | | 19010472** |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-05-28 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-05-28 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2019-05-28 10:15:00 | APPROVED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-05-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-05-06 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-05-06 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2019-05-06 07:25:15 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SSPECIFICATIONS FOR ALL SYSTEM COMPONENTS INCLUDING THE | | | HEAT PUMP. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) THE HEAT PUMP SHALL HAVE A MINIMUM COP OF 4.0 PER | | | TABLE C404.2. SUBMIT VERIFICATION THAT THE UNIT | | | COMPLIES. | | | 3) SUBMIT ALL THE DOCUMENTS INTO TWO COMPLETE SETS OF | | | PLANS FOR EACH PERMIT NUMBER. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-23 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-23 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-23 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2019-04-23 14:51:11 | PLUMBING 2ND REVIEW**DENIED**PROVIDE 2 COPIES FOR EACH | | | PERMIT APPLICATION | | | | | | 1) PROVIDE INSTALLATION MANUALS FOR ALL NEW EQUIPMENT | | | BEING INSTALLED. FBC 107.2.1 | | | | | | 2) PROVIDE PLUMBING FLAT DRAWING SHOWING PIPING TO NEW | | | POOL HEATER AND NEW SALT SYSTEM. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-02-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-23 |
Time |
05:00 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-02-22 |
Time |
06:41 |
Sent To |
I |
|
| Notes |
| 2019-02-23 04:48:46 | | | | | | | 1) THE SCOPE OF WORK FOR THIS PROJECT IS CONSIDERED A | | | MODIFICATION TO THE EXISTING PUBLIC POOL. SUBMIT A COPY | | | OF THE STAMPED RECEIPT FROM THE FLORIDA DEPARTMENT OF | | | HEALTH (PALM BEACH COUNTY HEALTH DEPARTMENT). SEE FAC | | | 64E-9.001 (3) (C) & FBC 105.1.4 | | | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED PLANS SHOWING | | | THE LOCATION OF THE PROJECT, LOCATION OF THE NEW AND | | | EXISTING EQUIPMENT AND ANCHORING OF THE EQUIPMENT | | | WINDLOADS. FBC 107.2.1 | | | | | | 3) THE DESCRIPTION OF WORK AND VALUE ON THE APPLICATION | | | WAS REVISED TO REMOVE THE RESURFACING OF THE WADING | | | POOL. REVISE THE SCOPE OF WORK ON THE OTHER SUBMITTAL | | | DOCUMENTS TO MATCH THE APPLICATION. FBC 107.2.1 | | | | | | 4) SUBMIT TWO COPIES OF ALL DOCUMENTS FOR THE | | | COMPONENTS TO BE INSTALLED. WPB AMEND. TO FBC SEC. | | | 107.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-04-19 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-04-19 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-04-19 |
Time |
11:57 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-01-16 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-01-16 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-01-16 |
Time |
15:52 |
Sent To |
B |
|
| Notes |
| 2019-01-16 15:56:05 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) A MINOR PD AMENDMENT WILL BE REQUIRED TO ADD | | | ADDITIONAL MECHANICAL EQUIPMENT. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER | | | THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO | | | SCHEDULE AN APPOINTMENT. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] |
|
|