Plan Review Details - Permit 19010393
Plan Review Stops For Permit 19010393
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 10:00 Rev Time 0.00
Received By pvalenti Date 2019-07-03 Time 09:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 15:42 Rev Time 0.00
Received By pvalenti Date 2019-06-04 Time 13:06 Sent To  
Notes
2019-06-04 15:49:25***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN 3RD REVIEW DENIED:
  
 PENDING ITEMS FROM ORIGINAL LIST:
  
 2. IS STILL PENDING: THE TYPE OF CONSTRUCTION (TYPE
 III-A) ENTERED ON PAGE A-1 UNDER CODE SUMMARY IS
 INCORRECT. PROVIDE THE RIGHT BUILDING TYPE, SHOULD BE
 TYPE I-A.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-08 Cont ID  
Sent By pvalenti Date 2019-05-08 Time 14:27 Rev Time 0.00
Received By pvalenti Date 2019-05-08 Time 11:46 Sent To  
Notes
2019-05-08 14:48:54***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING 2ND REVIEW DENIED:
  
 1. OK
 2. FAIL, SHEET A-1 UNDER CODE SUMMARY BUILDING CODE 2.4
 LEVELS OF ALTERATION - LEVEL III ALTERATION IS
 INCORRECT.
 PLEASE NOTE, THIS IS A NEW HIGHRISE BUILDING WITH THE
 1ST FLOOR BEING BUILT AS A SHELL SPACE, THIS IS NOT TO
 BE REVIEWED UNDER THE EXISTING BUILDING CODE, SINCE
 THIS WILL BE THE FIRST OCCUPANCY FOR THIS SPACE.
 3. OK
 4. FAIL, SHEET A-1 UNDER DESIGN WIND PRESSURES
 (NEGATIVE PRESSURE), NEEDS TO BE CLEARLY ADDED TO
 REVISED PLAN.
 5. OK
 6. OK
 7. OK
 8. OK
 9. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE
 REVISION AND REMOVE ANY VOIDED SHEETS AND REPLACE AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OFTHE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By jwitmer Date 2019-01-22 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2019-01-22 Time 12:49 Sent To  
Notes
2019-01-22 14:18:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010393
 ADD: 333 FERN ST. SUITE: 118
 CONT: BELA VISTA CONTRACTORS, INC.
 TEL: 9544-644-3121
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 22 / 2019
 ACTION: DENIED
  
 1) SHEET A-1 AT THE TOP PORTION OF THIS SHEET THE SCOPE
 OF WORK LIST THE ADDRESS OF 7070 SEMINOLE PRATT WHITNEY
 ROAD SUITE # 2 LOXAHATCHEE, FL. THE BOTTOM HALF OF THE
 SHEET UNDER THE HEADING OF GENERAL NOTES LIST THE
 PROJECT LOCATED AT 333 FERN ST. WEST PALM BEACH, FL.
 THE PERMIT APPLICATION ALSO LIST THE
 ADDRESS OF 333 FERN ST. SUITE # 118. DISCREPANCY IN THE
 LOCATION OF WHERE THE WORK IS TO BE COMPLETED UNDER
 THIS PERMIT. 7070 SEMINOLE PRATT WHITNEY ROAD SUITE # 2
 LOXAHATCHEE, FL. IS NOT IN THE CITY LIMITS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-1 UNDER THE HEADING CODE SUMMARY 1.0
 APPLICABLE CODES:
 APPLICABLE CODES 1.1 LIST THE ALTERATION AS A LEVEL II
 ALTERATION, WHEREAS UNDER THE NOTE 2.4 THE LEVEL OF THE
 ALTERATION AS A LEVEL III ALTERATION. DISCREPANCY IN
 LEVEL OF ALTERATION, 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED. PLEASE NOTE THIS IS A NEW HIGHRISE
 BUILDING WITH THE 1ST FLOOR BEING BUILT AS SHELL SPACE,
 THIS IS NOT TO BE REVIEWED UNDER THE EXISTING BUILDING
 CODE, SINCE WILL BE 1ST OCCUPANCY FOR THIS SPACE!!!
  
 3) SHEET A-1 UNDER THE HEADING BUILDING CODE LIST THIS
 BUILDING AS CONSTRUCTION TYPE III- UNPROTECTED/
 UNSPRINKLERED. PLEASE STOP BY THE JOBSITE, THIS IS A 20
 STORY HIGHRISE BUILDING, PLEASE CORRECT THE BUILDING
 TYPE AND THE BUILDING IS FIRE SPRINKLERED. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A-1 THE WIND DESIGN INFORMATION GIVEN IS THE
 EXISTING BUILDING IS, THAN 19 FEET TALL, PLEASE
 CORRECT. THIS IS A 20 STORY HIGHRISE BUILDING. PLEASE
 ALSO CORRECT THE NEGATIVE PRESSURES, THEY ARE TAKEN
 FROM THE ROOF LEVEL, SEE ASCE 7-10, CHAPTER 30.
  
 5) SHEET A-5 LIST THE TOILET ACCESSORY SCHEDULE UNDER
 THE 2014 FBC. PLEASE NOTE THE 2017 FBC-ACCESSIBILITY
 CODE WENT INTO EFFECT ON DECEMBER 31, 2017, STATEWIDE,
 PLEASE UPDATE PLAN NOTES.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A-2 IS THE DIMENSIONED FLOOR PLAN. PLEASE
 REVIEW THE CORRIDOR THAT LEEDS TO THE ACCESSIBLE
 RESTROOM. IT IS DIMENSIONED 3 FOOT 4 INCHES IN WIDTH.
 PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE 404.2.3
 AND FIGURE 404.2.1(H) THAT REQUIRES THE CORRIDOR TO BE
 48 INCHES IN WIDTH.
  
 7) SHEET A-2 DOES NOT INDICATE THE FRONT ENTRY DOOR IF
 THE SIDEWALK IS THE SAME LEVEL AS THE FINISH FLOOR IN
 THE INTERIOR, PLEASE SHOW COMPLIANCE WITH THE 22017
 FBC-ACCESSIBILITY CODE SECTION 402.2 COMPONENTS.
 ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE
 FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING
 SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB
 RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND
 PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE
 SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 CHAPTER 4 AND 208.3.1.
  
 8) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: HT
 TP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTF
 EES/FORMS/QUESTIONNAIRE.PDF
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-22 Cont ID  
Sent By jpearson Date 2019-04-22 Time 13:22 Rev Time 0.00
Received By jpearson Date 2019-04-22 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-03 Cont ID  
Sent By jpearson Date 2019-02-03 Time 10:44 Rev Time 0.00
Received By jpearson Date 2019-02-03 Time 10:44 Sent To I
Notes
2019-02-03 10:44:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. NOTE ON PLAN STATES EMERGENCY AND EXIT LIGHTS ARE
 REQUIRED TO BE FED FROM THE GENERAL LIGHTING CIRCUIT IN
 THE AREA, BUT THE LIGHTING PLAN SHOWS THEM FED FROM
 OTHER CIRCUITS. PROVIDE CORRECTION. NEC 700.12(F)
 3. PROVIDE SHOW WINDOW RECEPTACLE PER CODE. IT IS
 LISTED IN PANEL SCHEDULE BUT NOT SHOWN ON PLAN. NEC
 210.62
 4. SIGN CIRCUIT SHOWN ON PANEL SCHEDULE, BUT NOT ON
 PLAN. PROVIDE CORRECTION. NEC 600.5; WPB FBC 107.2.1
 5. RISER DIAGRAMS STATES THERE IS A 400 AMP SINGLE
 PHASE PANEL THAT IS EXISTING. LIGHTING AND POWER PLAN
 SHOW A 200 AMP PANEL EXISTING. PROVIDE CLARIFICATION
 AND/OR CORRECTIONS. WPB FBC 107.2.1; NEC 215.5
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 7. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THREE PHASE LOADS WOULD NOT HAVE
 ALL OF THE LOAD ON ONE PHASE AND NONE ON THE OTHERS.
 LOAD CALCULATION SHOULD INCLUDE 100% OF NON-CONTINUOUS
 LOADS AND 125% OF CONTINUOUS LOADS. NEC 215.2, 220,
 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-17 Cont ID  
Sent By pleduc Date 2019-05-17 Time   Rev Time 0.00
Received By pleduc Date 2019-05-17 Time 14:06 Sent To  
Notes
2019-05-17 14:06:555/17/19
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-04 Cont ID  
Sent By pleduc Date 2019-04-04 Time   Rev Time 0.00
Received By pleduc Date 2019-04-04 Time 16:23 Sent To  
Notes
2019-04-04 16:40:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By pleduc Date 2019-01-18 Time   Rev Time 0.00
Received By pleduc Date 2019-01-18 Time 12:45 Sent To  
Notes
2019-01-18 12:57:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1 - THERE ARE TWO SCOPES OF PROJECT
 INDICATED, ONE STATES THE ADDRESS OF SEMINOLE PRATT
 WHITNEY RD AND THE OTHER FERN ST.
  
 PLEASE REMOVE THE ONE THAT IS NOT APPLICABLE.
  
  
  
 2) SHEET A 1 - UNDER SECTION 1.0 APPLICABLE CODES THERE
 IS AN INCORRECT EDITION OF THE CURRENT FLORIDA FIRE
 PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITIONS OF NFPA 1 AND NFPA 101.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE.
  
  
  
 3) SHEET A 1 - UNDER SECTION 2.0 BUILDING CODE, THERE
 IS AN INDICATION OF TYPE 3 UNPROTECTED, UNSPRINKLERED.
 ADDITIONALLY, ON SHEET A 3, THERE IS AN INDICATION NEXT
 TO MAXIMUM TRAVEL DISTANCE TO EXIT 75' SPRINKLERED.
  
 IS THE BUILDING PROTECTED WITH FIRE SPRINKLERES?
  
 PLEASE REVIEW, CLARIFY AND OR CORRECT.
  
 IF SO, PLEASE PROVIDE A STATEMENT INDICATING SUCH AND
 THAT ALL WORK OF THE FIRE SPRINKLER SYSTEM SHALL BE
 UNDER SEPARATE SHOP DRAWINGS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 10:00 Rev Time 0.00
Received By pvalenti Date 2019-06-26 Time 16:21 Sent To  
Notes
2019-06-27 16:21:57RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-11 Cont ID  
Sent By lmarchan Date 2019-06-11 Time 10:21 Rev Time 0.00
Received By lmarchan Date 2019-05-15 Time 15:20 Sent To  
Notes
2019-06-10 16:30:44ROUTED FROM ZONING TO PERMIT LIBRARIAN 6/11/2019 EL
2019-05-16 15:20:34B26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-08 Cont ID  
Sent By pvalenti Date 2019-05-08 Time 14:49 Rev Time 0.00
Received By pvalenti Date 2019-04-03 Time 10:58 Sent To  
Notes
2019-04-17 15:30:51ROUTED FROM ZONING TO PERMIT LIBRARIAN 4/17/2019 EL
2019-04-04 10:58:44B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-11 Time 14:04 Sent To  
Notes
2019-01-16 14:10:55ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/16/19 EL
2019-01-11 14:04:24B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-08 Cont ID  
Sent By pvalenti Date 2019-05-08 Time 13:52 Rev Time 0.00
Received By pvalenti Date 2019-05-08 Time 13:52 Sent To  
Notes
2019-05-08 13:59:39 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED
  
 RECEIVED COUNTY STAMPED PLANS AND RECEIPT.
 TRACKING NUMBER MU-2019-008631-0000
 RECEIPT NUMBER 2019-0402-307

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By jwitmer Date 2019-01-22 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2019-01-22 Time 12:49 Sent To  
Notes
2019-01-22 14:17:47IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: HT
 TP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTF
 EES/FORMS/QUESTIONNAIRE.PDF
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-07-03 Cont ID  
Sent By ccole Date 2019-07-03 Time 09:46 Rev Time 0.00
Received By ccole Date 2019-07-03 Time 07:35 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-05-31 Cont ID  
Sent By ccole Date 2019-05-31 Time 14:02 Rev Time 0.00
Received By ccole Date 2019-05-31 Time 12:25 Sent To  
Notes
2019-05-31 14:10:132ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19010393
 5/31/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ME-1: SHOW THE EXACT LOCATION OF THE AC
 CONDENSER AND PROVIDE ENGINEERED DETAILS FOR
 INSTALLATION- SECTIPON 301.15 FBC M.
  
 2) ME-1: PROVDE A SEQUENCE OF OPERATION FOR THE OUTSIDE
 AIR FAN. WILL THE FAN BE ELECTRICALLY LINKED WITH THE
 AIR HANDLER FOR AUTOMATIC OPERATION?
  
 3) ME-1: PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION
 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By ccole Date 2019-04-18 Time 15:17 Rev Time 0.00
Received By ccole Date 2019-04-18 Time 14:58 Sent To  
Notes
2019-04-18 15:26:122ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19010393
 4/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ME-1: THE OUTDOOR AIR TABLE IS INCORRECT. REFER TO
 TABLE 403.3.1.1 FBC M: OUTDOOR AIR FOR FAST FOOD IS
 CALCULATED AT 100 PERSONS PER 100 S.F. (23 PERSONS/7.5
 CFMS PER PERSON= 172.5 CFMS ) + (0.18 CFMS/232 SF.= 42)
 = 215 CFMS OF OUTSIDE AIR REQUIRED. PLEASE CORRECT THE
 TABLE THAT INDICATES 98.4 CFMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By ccole Date 2019-01-29 Time 15:03 Rev Time 0.00
Received By ccole Date 2019-01-29 Time 14:28 Sent To  
Notes
2019-01-29 15:44:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010393
 1/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ME-1: PROVIDE A SCOPE OF WORK OUTLINE ON THE
 PLAN FOR CLARIFICATION. CURRENTLY THERE IS AN EQUIPMENT
 SCHEDULE SHOWN FOR AN EXISTING 3.5 TON SYSTEM, HOWEVER
 THE DUCT LAYOUT PLAN SHOWS A 2-TON SYSTEM. IS THE 3.5
 TON SYSTEM BEING REPLACED WITH A NEW 2-TON?
  
 2) ME-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED AND
 AUTOMATICALLY CONTROLLED AS REQUIRED BY SECTION 403.1
 FBC M, AND SECTION C403.2.4.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 10:19 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-30 Cont ID  
Sent By gjohnson Date 2019-01-30 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2019-01-30 Time 16:13 Sent To  
Notes
2019-01-30 16:13:33 
 1ST REVIEW: 19010393
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE TEMPERED WATER AT THE LAVATORY SHALL BE
 DELINERED BY A TEMPERATURE LIMITING DEVICE CONFORMING
 WITH ASSE 1070/ CSA B125.3.PER FBC PL 416.5
  
 2. PROVIDE WATER VALVES AT EACH DROP ON THE WATER
 ISOMETRIC DRAWING. PER FBC PL 606.1(5)
  
 3. THE HAND SINK CUP WASHER AND FLOOR DRAIN IN THE
 EMPLOYEE SERVICE AREA SHALL BE CONNECTED TO GREASE
 INTERCEPTOR.PER FBC PL 1003.3.1
  
 4. PROVIDE A GREASE TRAP SIZING CALCULATION FROM THE
 MANUFACTURE FOR SCHIER YOU CAN CONTACT LEE SCHNEEWEISS
 @ 1-800-538-4792 IT SHOULD INCUDE THE FLOOR SINK FOR
 THE MIXER AND FLOOR SINK IN PREP ROOM AND THE FIXTURES
 IN THE EMPLOYEE SERVICE AREA. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 10:20 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 10:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-06-10 Cont ID  
Sent By elevesqu Date 2019-06-10 Time 16:30 Rev Time 0.00
Received By elevesqu Date 2019-06-10 Time 16:30 Sent To  
Notes
2019-06-10 16:30:27REPEAT PROVISO: SEPARATE OUTDOOR SEATING PERMIT
 REQUIRED
 NO LANDSCAPE MODIFICATIONS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-17 Cont ID  
Sent By elevesqu Date 2019-04-17 Time 10:10 Rev Time 0.00
Received By elevesqu Date 2019-04-17 Time 15:30 Sent To  
Notes
2019-04-17 15:30:37PROVISO: SEPARATE OUTDOOR SEATING PERMIT REQUIRED
 NO LANDSCAPE MODIFICATIONS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
2019-04-17 10:11:08PROVISO: SEPARATE PERMIT REQUIRED FOR OUTDOOR SEATING.
 NO LANDSCAPE MODIFICATIONS APPROVED.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2019-01-16 Cont ID  
Sent By elevesqu Date 2019-01-16 Time 14:09 Rev Time 0.00
Received By elevesqu Date 2019-01-16 Time 14:09 Sent To  
Notes
2019-01-16 14:10:35PROVISO:
 OUTDOOR SEATING REQUIRES SEPARATE PERMIT.
 NO LANDSCAPE MODIFICATIONS.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426


Account Summary | Usage Policy | Privacy Policy