Plan Review Details - Permit 19010376
Plan Review Stops For Permit 19010376
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-01-26 Cont ID  
Sent By shill Date 2019-01-26 Time 11:02 Rev Time 0.00
Received By shill Date 2019-01-26 Time 11:02 Sent To  
Notes
2019-01-26 11:09:48PROVISO: PRODUCT APPROVALS REVIEWED BY ARCHITECT OF
 RECORD ARE TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR
 TO INSTALLATION
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By ppetty Date 2019-03-11 Time 13:07 Rev Time 0.00
Received By ppetty Date 2019-03-11 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 14:46 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 09:20 Sent To  
Notes
2019-01-24 14:46:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 3. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-02 Cont ID  
Sent By hmoser Date 2019-04-02 Time 09:58 Rev Time 0.00
Received By hmoser Date 2019-03-29 Time 13:28 Sent To  
Notes
2019-04-01 13:28:18RESUB ROUTED TO HMOSER'S OFFICE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-16 Cont ID  
Sent By cmontell Date 2019-03-16 Time 06:44 Rev Time 0.00
Received By cmontell Date 2019-03-16 Time 06:44 Sent To  
Notes
2019-03-06 15:52:14R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-28 Cont ID  
Sent By hmoser Date 2019-01-28 Time 10:30 Rev Time 0.00
Received By hmoser Date 2019-01-10 Time 13:57 Sent To  
Notes
2019-01-11 13:58:27R14

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By hmoser Date 2019-04-02 Time 09:57 Rev Time 0.00
Received By hmoser Date 2019-04-02 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-16 Cont ID  
Sent By cmontell Date 2019-03-16 Time 06:43 Rev Time 0.00
Received By cmontell Date 2019-03-16 Time 06:23 Sent To I
Notes
2019-03-16 06:33:18MECHANICAL PLAN REVIEW FAIL
  
  
  
 1. FBC ENERGY SECTION R 103.1.1.2 THE SUBMITTED
 DOCUMENTS FOR ENERGY CALCULATIONS NEED TO BE SIGNED BY
 THE OWNER/AGENT.
 2. FBC RESIDENTIAL M1602.3 THE RETURN AIR DUCTS DO NOT
 MEET THE REQUIRED SIZE, CONSIDERING THE SIZE OF SUPPLY
 DUCTS, AT THE ROOMS OF THE SECOND FLOOR.
 PASS THROUGH RETURNS SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) PER 2017 -
 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION PER
 SECTION M1602.3BALANCED RETURN AIR.
 PLAN DENIED
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-28 Cont ID  
Sent By hmoser Date 2019-01-28 Time 10:30 Rev Time 0.00
Received By hmoser Date 2019-01-28 Time 09:02 Sent To I
Notes
2019-01-28 10:30:12PLAN DENIED
  
 1. FBC ENERGY SECTION R 103.1.1.2 THE SUBMITTED
 DOCUMENTS FOR ENERGY CALCULATIONS NEED TO BE SIGNED BY
 THE OWNER/AGENT.
 2. FBC RESIDENTIAL M1602.3 THE RETURN AIR DUCTS DO NOT
 MEET THE REQUIRED SIZE, CONSIDERING THE SIZE OF SUPPLY
 DUCTS, AT THE ROOMS OF THE SECOND FLOOR.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-13 Cont ID  
Sent By thunt Date 2019-03-13 Time 15:41 Rev Time 0.00
Received By thunt Date 2019-03-13 Time 15:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-24 Cont ID  
Sent By jesmith Date 2019-01-24 Time 13:18 Rev Time 0.00
Received By jesmith Date 2019-01-24 Time 12:12 Sent To  
Notes
2019-01-24 13:18:29CODES IN EFFECT:
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET A-5.0; PLUMBING DIAGRAM
 A. CLOTHES WASHER DRAIN SHALL NOT CONNECT TO BATHROOM
 GROUP WET VENT PER FBC RES P3108.1. CONNECT DOWNSTREAM
 TO COMPLY.
 B. 3" RISER SHALL BE LABELED "SOIL STACK", NOT "VENT"
 PER WPB FBC 107.2.1.
 2.PROVIDE MANUFACTURER'S SPECIFICATION TO INCLUDE THE
 GPM AND ELECTRICAL CHARACTERISTICS FOR THE TANKLESS
 WATER HEATERS PER WPB FBC 107.2.1 AND CONFIRM THEY WILL
 SUPPLY THE HOT WATER DEMAND.
  
 SINCERELY,
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 561-805-6715
 [email protected]