| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | APPROVED PROVISO. PROVISIONAL REQUIREMENTS MAY BE |
| | INSPECTED BY THIS DEPARMENT TO ENSURE COMPLIANCE. |
| | |
| | 1) THE OCCUPANT LOAD FOR THE MAIN TENT(S) SHALL COMPLY |
| | WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: |
| | CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY |
| | USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15 |
| | SQ FT/PERSON. |
| | |
| | 2) ASSEMBLY USE TENT SHALL HAVE THE SEATING ARRANGED IN |
| | A MANNER THAT COMPLIES WITH THE AISLE AND AISLEWAY |
| | REQUIREMENTS AS LISTED UNDER NFPA 101: 12.2.5 |
| | (ARRANGEMENT OF MEANS OF EGRESS). |
| | |
| | 3) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| | |
| | 4) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| | BUILDING STRUCTURES. |
| | |
| | 5) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| | |
| | 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | 7) IF BEING USED, GENERATORS AND OTHER INTERNAL |
| | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS |
| | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM |
| | CONTACT BY FENCING OR ENCLOSURE. |
| | |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |