Plan Review Details - Permit 19010225
Plan Review Stops For Permit 19010225
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By rmcdouga Date 2019-01-15 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2019-01-15 Time 17:45 Sent To  
Notes
2019-01-15 17:45:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER IS REQUIRED TO SIGN, SEAL AND DATE THE
 CONSTRUCTION DRAWINGS. FLORIDA ADMINISTRATIVE CODE
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.002, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-10 Cont ID  
Sent By scaldero Date 2019-01-10 Time 11:27 Rev Time 0.00
Received By scaldero Date 2019-01-10 Time 11:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2019-01-08 Time 14:58 Sent To  
Notes
2019-01-08 14:58:09B04
 **TRAVELLING TOGETHER - 19010224 & 19010225**

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By rcaranci Date 2019-01-15 Time 14:57 Rev Time 0.00
Received By rcaranci Date 2019-01-15 Time 14:57 Sent To  
Notes
2019-01-15 14:58:20PROVIDE SPECIES OF HEDGE PLANTS.
 SUBMIT A TREE ALTERATION PERMIT, SHOW FINAL LOCATIONS
 OF 2 RELOCATED SABAL PALMS.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By llouie Date 2019-01-15 Time   Rev Time  
Received By llouie Date 2019-01-15 Time   Sent To  
Notes
2019-01-15 15:04:26** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) IDENTIFY THE MATERIAL USED FOR THE 6 FT. HIGH FENCE
 AROUND THE GENERATOR/TANK PAD(S). PLEASE NOTE THAT
 CHAIN LINK FENCE IS NOT PERMITTED FOR SCREENING; THE
 SCREEN MUST BE OPAQUE.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * TREE ALTERATION PERMIT REQUIRED PRIOR TO THE REMOVAL
 OF ANY TREES/PALMS ON THE PREMISE. CONTACT RAY CARANCI,
 CITY LANDSCAPE PLANNER, FOR ADDITIONAL INFORMATION.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (FOUNTAIN VIEW)
  
  