Plan Review Details - Permit 19010211
Plan Review Stops For Permit 19010211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-13 Cont ID  
Sent By pvalenti Date 2019-03-13 Time 11:02 Rev Time 0.00
Received By pvalenti Date 2019-03-13 Time 10:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-30 Cont ID  
Sent By jduprey Date 2019-01-30 Time 10:16 Rev Time 0.00
Received By jduprey Date 2019-01-30 Time 10:07 Sent To  
Notes
2019-01-30 10:15:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ONLY FIRE COMMENTS WERE ADDRESSED.
  
 1. PLEASE PROVIDE A LIFE SAFETY PLAN WITH EVERY ROOM
 LABELED. THERE IS A CONCERN IN REGARDS EGRESS THROUGH
 INTERVEINING SPACES. THE MEANS OF EGRESS ROUTE MUST
 MEET THE FBC 1016.2 THROUGH 1016.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By jduprey Date 2019-01-15 Time 12:06 Rev Time 0.00
Received By jduprey Date 2019-01-15 Time 11:46 Sent To  
Notes
2019-01-15 12:02:17BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLEASE PROVIDE A FLOOR PLAN WITH EVERY ROOM LABELED,
 OCUPAND LOAD AND THE MEANS OF EGRESS ROUTE FOR THE
 ENTIRE BUILDING. THE MEANS OF EGRESS ROUTE MUST MEET
 THE FBC 1016.2 THROUGH 1016.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-03-07 Cont ID  
Sent By pleduc Date 2019-03-07 Time   Rev Time 0.00
Received By pleduc Date 2019-03-07 Time 12:57 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By pleduc Date 2019-01-22 Time   Rev Time 0.00
Received By pleduc Date 2019-01-22 Time 13:02 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By pleduc Date 2019-01-08 Time   Rev Time 0.00
Received By pleduc Date 2019-01-08 Time 15:07 Sent To B
Notes
2019-01-08 15:19:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN INDICATON OF AN EXISTING TENANT FIRE
 SEPARATION WALL AND AN INFILL WITHIN THE WALL.
  
 THERE IS NO INDICATION OF A LISTED FIRE WALL DESIGN TO
 MATCH THE PROPOSED INFILL.
  
 PER NFPA 1, CHAPTER 12, FEATURES OF FIRE PROTECTION
  
 12.3 FIRE-RESISTIVE MATERIALS AND CONSTRUCTION.
 12.3.1 THE DESIGN AND CONSTRUCTION OF FIRE WALLS AND
 FIRE BARRIER WALLS
 THAT ARE REQUIRED TO SEPARATE BUILDINGS OR SUBDIVIDE A
 BUILDING TO PREVENT
 THE SPREAD OF FIRE SHALL COMPLY WITH SECTION 12.3 AND
 NFPA 221,
 STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE WALLS, AND
 FIRE BARRIER
 WALLS.
  
 12.3.3* MAINTENANCE OF FIRE-RESISTIVE CONSTRUCTION.
 12.3.3.1 REQUIRED FIRE-RESISTIVE CONSTRUCTION,
 INCLUDING FIRE BARRIERS, FIRE
 WALLS, EXTERIOR WALLS DUE TO LOCATION ON PROPERTY,
 FIRE-RESISTIVE
 REQUIREMENTS BASED ON TYPE OF CONSTRUCTION, DRAFT-STOP
 PARTITIONS, AND
 ROOF COVERINGS, SHALL BE MAINTAINED AND SHALL BE
 PROPERLY REPAIRED,
 RESTORED, OR REPLACED WHERE DAMAGED, ALTERED, BREACHED,
 PENETRATED,
 REMOVED, OR IMPROPERLY INSTALLED.
  
 PLEAE PROVIDE A LISED WALL DESIGN .
  
  
  
  
 2) THERE IS A NEW DOOR INDICATED. THERE IS NO DOOR SIZE
 OR SCHEDULE, INCLUDING HARDWARE, INDICATED.
  
 IF THIS AN EXIT DOOR?
  
 IS THE WALL A RATED WALL?
  
 IF THE WALL IS A RATED WALL, THE DOOR IS REQUIRED TO BE
 RATED.
  
 PLEASE PROVIDE DETAILS
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-13 Cont ID  
Sent By pvalenti Date 2019-03-13 Time 11:02 Rev Time 0.00
Received By pvalenti Date 2019-03-05 Time 15:06 Sent To  
Notes
2019-03-06 15:06:42RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-30 Cont ID  
Sent By jduprey Date 2019-01-30 Time 10:17 Rev Time 0.00
Received By jduprey Date 2019-01-17 Time 14:05 Sent To  
Notes
2019-01-18 14:06:12RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-15 Cont ID  
Sent By jduprey Date 2019-01-15 Time 12:07 Rev Time 0.00
Received By jduprey Date 2019-01-08 Time 15:00 Sent To  
Notes
2019-01-08 15:00:17ROUTED TO FIRE INBOX