Plan Review Details - Permit 19010208
Plan Review Stops For Permit 19010208
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-05 Cont ID  
Sent By dbattles Date 2019-04-05 Time 09:46 Rev Time 0.00
Received By dbattles Date 2019-04-05 Time 09:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-22 Cont ID  
Sent By dbattles Date 2019-02-22 Time 16:06 Rev Time 0.00
Received By dbattles Date 2019-02-22 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By dbattles Date 2019-01-29 Time 09:29 Rev Time 0.00
Received By dbattles Date 2019-01-28 Time 07:42 Sent To  
Notes
2019-01-29 09:30:11****CORRECTIONS****
 W.P.B. PERMIT: 19010208
 REVIEWED: JANUARY 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1. 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
  
 2. 107.5.3 FBC[AMENDED] GENERAL NOTES.
 A. PLEASE LABEL SECTION NUMBER 14 ON SHEET A-2.1. THERE
 IS A CALL OUT ON SHEET A-1.0 THAT REFERS TO IT.
 B. SHEET A-2.0 HAS SECTION 7 AND 8 SHOWN. WHERE ARE
 THEY CALLED OUT FROM? I DON?T SEE THEM ON SHEET A-1.0.
  
 3. 107.5.3 FBC[AMENDED] GENERAL DATA.
 A. PROVIDE AREA TABULATIONS FOR ALL NEW SPACES AND
 EXISTING SPACES.
 B. STATE THE OCCUPANCY OF THE SPACES.
 C. STATE OCCUPANT LOAD.
 D. LIFE SAFTEY PLAN
 E. STATE THE TYPE OF CONSTRUCTION.
  
 4. 30.1 ASCE 7-10 PROVIDE POSITIVE AND NEGATIVE DESIGN
 PRESSURES FOR ALL DOOR AND LOUVER OPENINGS.
  
 5. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 DOORS AND LOUVERS, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERRED.
  
 6. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-27 Cont ID  
Sent By jpearson Date 2019-02-27 Time 15:39 Rev Time 0.00
Received By jpearson Date 2019-02-27 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-01-23 Cont ID  
Sent By jpearson Date 2019-01-23 Time 09:53 Rev Time 0.00
Received By jpearson Date 2019-01-23 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-23 Cont ID  
Sent By scaldero Date 2019-01-23 Time 09:17 Rev Time 0.00
Received By scaldero Date 2019-01-23 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-29 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-08 Cont ID  
Sent By gjohnson Date 2019-03-08 Time 18:39 Rev Time 0.00
Received By gjohnson Date 2019-02-19 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-29 Cont ID  
Sent By dbattles Date 2019-01-29 Time 09:30 Rev Time 0.00
Received By dbattles Date 2019-01-22 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-05 Cont ID  
Sent By ccole Date 2019-04-05 Time 14:31 Rev Time 0.00
Received By ccole Date 2019-04-05 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-01 Cont ID  
Sent By ccole Date 2019-03-01 Time 16:44 Rev Time 0.00
Received By ccole Date 2019-03-01 Time 11:09 Sent To  
Notes
2019-03-01 17:22:542ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19010208
 1/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.0: REFER TO SECTION 514.2 FBC M PROHIBITED
 APPLICATIONS: ENERGY RECOVERY VENTILATION SYSTEMS SHALL
 NOT BE USED IN THE FOLLOWING SYSTEMS:
 1.HAZARDOUS EXHAUST SYSTEMS COVERED IN SECTION 510.
 IT APPEARS THAT THE REVISED PLAN IS NOT IN COMPLIANCE.
  
 2) COMMENT #11 FROM THE 1ST REVIEW STILL EXISTS: THE
 REQUESTED UL CERTIFICATE FOR THE GENERATOR SHOWING
 LISTING AND LABELING IN ACCORDANCE WITH UL 2200 NOT
 SUBMITTED- SECTION 915.1 FBC M. PLEASE NOTE THE
 GENERATOR SHALL ALOS BE IN COMPLIANCE WITH NFPA 37-
 SECTION 915.2 FBC M.
  
 3) COMMENT #12 FROM THE 1ST REVIEW STILL EXISTS: SITE
 SPECIFIC WIND LOAD ENGINEERING FOR THE GENERATOR
 INSTALLATIONS IS REQUIRED- SEE SECTION 1609 FBC B. THE
 SUBMITTED WIND LOAD COMMUTATIONS FROM GENERAC ARE BASED
 ON THE OUTDATED ASCE 7-98 AND HAVE A DISCLAIMER THAT
 STATES THE SUMMARY RESULTS IN THE DOCUMENT ARE FOR
 REFERENCE ONLY AND MUST BE VERIFED BY A LICENSED
 ENGINEER IN THE STATE OF RECORD.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By ccole Date 2019-01-25 Time 14:41 Rev Time 0.00
Received By ccole Date 2019-01-25 Time 13:27 Sent To  
Notes
2019-01-25 15:35:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010208
 1/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXHAUST VENTILATION IS REQUIRED FOR THE UPS SYSTEM,
 HOWEVER DETERMINING HOW THE SYSTEM WILL BE VENTILATED
 IS DEPENDENT ON SUBMITTAL OF MSDS SHEETS FOR THE
 BATERRIES, AND CLARIFICATION OF HOW THE BATTERIES ARE
 BEING STORED, AND BATTERY QUANTITIES- SEE FBC M CODE
 SECTIONS BELOW.
  
 502.4 STATIONARY STORAGE BATTERY SYSTEMS.
 STATIONARY STORAGE BATTERY SYSTEMS, AS REGULATED BY THE
 FLORIDA FIRE PREVENTION CODE, SHALL BE PROVIDED WITH
 VENTILATION IN ACCORDANCE WITH THIS CHAPTER AND SECTION
 502.4.1 OR 502.4.2.
 EXCEPTION: LITHIUM-ION AND LITHIUM METAL POLYMER
 BATTERIES SHALL NOT REQUIRE ADDITIONAL VENTILATION
 BEYOND THAT WHICH WOULD NORMALLY BE REQUIRED FOR HUMAN
 OCCUPANCY OF THE SPACE.
  
 502.4.1 HYDROGEN LIMIT IN ROOMS.
 FOR FLOODED LEAD ACID, FLOODED NICKEL CADMIUM AND VRLA
 BATTERIES, THE VENTILATION SYSTEM SHALL BE DESIGNED TO
 LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0
 PERCENT OF THE TOTAL VOLUME OF THE ROOM.
  
 502.4.2 VENTILATION RATE IN ROOMS.
 CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE OF
 NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER SQUARE FOOT
 (CFM/FT2) [0.00508 M3/(S ? M2)] OF FLOOR AREA OF THE
 ROOM.
  
 502.4.3 SUPERVISION.
 MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION
 502.4 SHALL BE SUPERVISED BY AN APPROVED CENTRAL,
 PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE
 AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED
 ON-SITE LOCATION.
  
 502.5 VALVE-REGULATED LEAD-ACID BATTERIES IN CABINETS.
 VALVE-REGULATED LEAD-ACID (VRLA) BATTERIES INSTALLED IN
 CABINETS, AS REGULATED BY THE FLORIDA FIRE PREVENTION
 CODE, SHALL BE PROVIDED WITH VENTILATION IN ACCORDANCE
 WITH SECTION 502.5.1 OR 502.5.2.
  
 502.5.1 HYDROGEN LIMIT IN CABINETS.
 THE CABINET VENTILATION SYSTEM SHALL BE DESIGNED TO
 LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0
 PERCENT OF THE TOTAL VOLUME OF THE CABINET DURING THE
 WORST-CASE EVENT OF SIMULTANEOUS BOOST CHARGING OF ALL
 BATTERIES IN THE CABINET.
  
 502.5.2 VENTILATION RATE IN CABINETS.
 CONTINUOUS CABINET VENTILATION SHALL BE PROVIDED AT A
 RATE OF NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER
 SQUARE FOOT (CFM/FT2) [0.00508 M3/(S ? M2)] OF THE
 FLOOR AREA COVERED BY THE CABINET. THE ROOM IN WHICH
 THE CABINET IS INSTALLED SHALL BE VENTILATED AS
 REQUIRED BY SECTION 502.4.1 OR 502.4.2.
  
 502.5.3 SUPERVISION.
 MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION
 502.5 SHALL BE SUPERVISED BY AN APPROVED CENTRAL,
 PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE
 AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED
 ON-SITE LOCATION.
  
 2) PROVIDE THE FOLLOWING INFORMATION FOR THE UPS
 SYSTEMS AS OUTLINED IN SECTION 414.1.3 FBC B. PLEASE
 NOTE THAT THE WALLS ENCLOSING THE UPS ROOM MAY HAVE TO
 BE FIRE-RATED.
  
 414.1.3 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 3) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 4) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW UPS
 ADDITION AND ENCLOSED WALKWAY- SECTION
  
 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE NEW
 UPS ADDITION AND ENCLOSED WALKWAY- TABLE 404.3.1.1 FBC
 M.
  
 6) SHEET M1.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF EACH NEW AC SYSTEM PER SECTION
 606.2.1. PLEASE PROVIDE SYSMBOLS ON THE PLAN AT THE
 REQUIRED LOCATIONS, AND INDICATE A SEQUENCE OF
 OPERATION FOR FAN SHUTDOWN ON SHEET M2.0- SECTION 606.4
 FBC M.
  
 7) M3.0: INDICATE THE TYPE AND SIZE FASTENER TO ATTACH
 THE CONDENSER CLIP TO THE CONDENSER HOUSING AND PROVIDE
 THE WIND LOAD DESIGN CRITERIA- SECTION 301.15 FBC M AND
 SECTION 1609 FBC M.
  
 8) PROVIDE A DETAIL SHOWING HOW THE AIR HANDLERS WILL
 BE ATTACHED AND SUSPENDED FROM THE STRUCTURE- SECTION
 304.1 FBC M
  
 9) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR
 HANDLERS- SECTION 307.2.1 FBC M.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE GENERATORS- SECTION 304.1
 FBC M..
  
 11) SUBMIT THE UL COMPLIANCE CERTIFICATES FOR THE
 GENERATORS- SECTION 915.2 FBC M.
  
 12) PROVIDE WIND LOAD ENGINEERING AND DETAILS FOR
 INSTALLATION OF THE GENERATORS- SECTION 301.15 FBC M.
  
 13) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR
 THE LOUVERS- RULE 9N-3 FAC.
  
  
  
  
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-03-08 Cont ID  
Sent By gjohnson Date 2019-03-08 Time 18:38 Rev Time 0.00
Received By gjohnson Date 2019-03-08 Time 18:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-04-05 Cont ID  
Sent By dbattles Date 2019-04-05 Time 09:46 Rev Time 0.00
Received By dbattles Date 2019-04-05 Time 09:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-01-28 Cont ID  
Sent By dbattles Date 2019-01-28 Time 12:43 Rev Time 0.00
Received By dbattles Date 2019-01-28 Time 12:43 Sent To  
Notes
2019-01-28 12:46:35W.P.B. PERMIT: 19010208
 REVIEWED: JANUARY 28, 2019
  
 SEE BUILDING COMMENT
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-04-05 Cont ID  
Sent By dbattles Date 2019-04-05 Time 09:46 Rev Time 0.00
Received By dbattles Date 2019-04-05 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-02-22 Cont ID  
Sent By dbattles Date 2019-02-22 Time 16:03 Rev Time 0.00
Received By dbattles Date 2019-02-22 Time 15:40 Sent To  
Notes
2019-02-22 16:05:55STRUCTURAL SHEETS STILL LACK THE DIGITAL SIGNATURE.
 PLEASE CONTACT PERMIT LIBRARIANS OR DYLAN BATTLES TO
 RESOLVE.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-01-23 Cont ID  
Sent By jpearson Date 2019-01-23 Time 08:46 Rev Time 0.00
Received By jpearson Date 2019-01-23 Time 08:46 Sent To  
Notes
2019-01-23 08:46:05EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION FOR "S" SHEETS.
 ALL OTHER SHEETS OK. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2019-04-05 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-05 Time 08:56 Sent To  
Notes
2019-04-05 08:56:50PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2019-02-26 Time   Rev Time 0.00
Received By pgreilic Date 2019-02-26 Time 15:00 Sent To  
Notes
2019-02-26 15:01:331.) PROVIDE APPROVED SITE PLAN AND MINOR PD APPROVAL
 LETTER WITH PERMIT SET
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-01-28 Time   Rev Time 0.00
Received By pgreilic Date 2019-01-28 Time 14:34 Sent To  
Notes
2019-01-28 14:35:161.) PROVIDE APPROVED SITE PLAN IN PERMIT SET
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved