Plan Review Details - Permit 19010201
Plan Review Stops For Permit 19010201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-19 Cont ID  
Sent By dbattles Date 2019-04-19 Time 15:38 Rev Time 0.00
Received By dbattles Date 2019-04-19 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-14 Cont ID  
Sent By dbattles Date 2019-03-14 Time 16:34 Rev Time 0.00
Received By dbattles Date 2019-03-14 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-24 Cont ID  
Sent By dbattles Date 2019-01-24 Time 10:44 Rev Time 0.00
Received By dbattles Date 2019-01-24 Time 10:44 Sent To  
Notes
2019-01-24 10:47:15****CORRECTIONS****
 W.P.B. PERMIT: 19010201
 REVIEWED: JANUARY 24, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 107.2.1FBC[AMENDED] ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 -PLEASE ADD NAME AND SIGNATURE OF DESIGNER TO THE PLAN.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-30 Cont ID  
Sent By jpearson Date 2019-04-30 Time 09:10 Rev Time 0.00
Received By jpearson Date 2019-04-30 Time 08:06 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-11 Cont ID  
Sent By ppetty Date 2019-03-11 Time 14:12 Rev Time 0.00
Received By ppetty Date 2019-03-11 Time 14:12 Sent To  
Notes
2019-03-11 14:11:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 5. ELECTRICAL PERMIT REQUIRED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-23 Cont ID  
Sent By jpearson Date 2019-01-23 Time 15:35 Rev Time 0.00
Received By jpearson Date 2019-01-23 Time 07:16 Sent To  
Notes
2019-01-23 15:35:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 3. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-16 Time 13:44 Sent To  
Notes
2019-04-17 13:44:35R11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-19 Cont ID  
Sent By jesmith Date 2019-03-19 Time 09:03 Rev Time 0.00
Received By jesmith Date 2019-03-19 Time 09:03 Sent To  
Notes
2019-03-06 14:58:13R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-24 Cont ID  
Sent By jesmith Date 2019-01-24 Time 11:24 Rev Time 0.00
Received By jesmith Date 2019-01-24 Time 11:24 Sent To  
Notes
2019-01-08 14:20:41R10

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-18 Cont ID  
Sent By jesmith Date 2019-04-18 Time 13:21 Rev Time 0.00
Received By jesmith Date 2019-04-18 Time 13:10 Sent To  
Notes
2019-04-18 13:21:30APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By jesmith Date 2019-03-19 Time 09:03 Rev Time 0.00
Received By jesmith Date 2019-03-19 Time 09:00 Sent To  
Notes
2019-03-19 09:03:18APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR"S
 APPROVAL
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-24 Cont ID  
Sent By jesmith Date 2019-01-24 Time 11:24 Rev Time 0.00
Received By jesmith Date 2019-01-24 Time 11:20 Sent To  
Notes
2019-01-24 11:20:30CODES IN EFFECT:
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST PLUMBING. WPB FBC 109.3
 3. A NEW SHOWER PAN CONFORMING TO THE REQUIREMENTS OF
 FBC RES SECTION P2709 IS REQUIRED AND SHALL BE NOTED AS
 SUCH ON THE PLANS PER WPB FPC 107.2.1.
 4. A NEW SHOWER VALVE CONFORMING TO THE REQUIREMENTS OF
 FBC RES SECTION P2708 IS REQUIRED AND SHALL BE NOTED AS
 SUCH ON THE PLANS PER WPB FPC 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 561-805-6715
 [email protected]