Plan Review Details - Permit 19010144
Plan Review Stops For Permit 19010144
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By pleduc Date 2019-01-14 Time   Rev Time 0.00
Received By pleduc Date 2019-01-14 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-08 Cont ID  
Sent By pleduc Date 2019-01-08 Time   Rev Time 0.00
Received By pleduc Date 2019-01-08 Time 14:50 Sent To M
Notes
2019-01-08 15:01:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL COMPLY WITH NFPA 96.
  
 PER CHAPTER 10, FIRE-EXTINGUISHING EQUIPMENT
  
 10.2.6 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE
 INSTALLED IN
 ACCORDANCE WITH THE TERMS OF THEIR LISTING, THE
 MANUFACTURER?S
 INSTRUCTIONS, AND THE FOLLOWING STANDARDS WHERE
 APPLICABLE:
 (1) NFPA 12
 (2) NFPA 13
 (3) NFPA 17
 (4) NFPA 17A
 (5) NFPA 750
  
 PLEASE ENSURE COMPLIANCE PRIOR TO INSPECTION.
  
  
  
 2) TIE - IN THE FIRE ALARM SYSTEM PER NFPA .
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO
 SHOW THAT THE SYSTEM HAS ACTIVATED.
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
  
  
 3) PROVIDE MANUFACTURER'S EQUIPMENT SPEC SHEETS FOR
 FIRE INSPECTOR REVIEW ON INSPECTION.
  
 ENSURE SPEC SHEETS ARE PROVIDED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-14 Cont ID  
Sent By lmarchan Date 2019-01-14 Time 13:50 Rev Time 0.00
Received By lmarchan Date 2019-01-04 Time 12:53 Sent To  
Notes
2019-01-07 12:53:32ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-11 Cont ID  
Sent By ccole Date 2019-01-11 Time 17:43 Rev Time 0.00
Received By ccole Date 2019-01-11 Time 17:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-09 Cont ID  
Sent By ccole Date 2019-01-09 Time 17:19 Rev Time 0.00
Received By ccole Date 2019-01-09 Time 17:19 Sent To I
Notes
2019-01-09 17:27:481ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010144
 1/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS DO NOT PROVIDE ANY DETAILS AND
 SPECIFICATIONS FOR THE GREASE EXHAUST AND MAKEUP AIR
 DUCTS. PLEASE PROVIDE COMPLETE PLANS- SEXCTION 107.2.1
 WPB.
  
 2) THE PLANS MUST BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL WHO PREPARED THEM, OR BEAR THE SHOP
 DRAWING APPROVAL STAMP OF THE MAIN BUILDING DESIGN
 PROFESSIONAL OF RECORD- SECTIONS 107.1 & 107.2.1 WPB.
  
 3) INDICATE THE TYPE OF HOOD BACKING TO BE USED AND THE
 DIMENSIONS OF THE BACKING- SEE SECTION 507.2.6
 EXCEPTION FBC M.
  
 4) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-01-11 Cont ID  
Sent By ccole Date 2019-01-11 Time 17:44 Rev Time 0.00
Received By ccole Date 2019-01-11 Time 17:44 Sent To  
Notes
***NONE***