Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-09 Cont ID  
Sent By fgiaquin Date 2019-01-09 Time 06:23 Rev Time 0.00
Received By fgiaquin Date 2019-01-09 Time 05:44 Sent To I
Notes
2019-01-09 06:23:47ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED
 AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 2. ORIGINAL PLAN SHOWS LOUVER MOTOR, FANS, AND LIGHTING
 FOR PERGOLA. IF LOUVER MOTOR AND FANS ARE STILLL TO BE
 INSTALLED SHOW THAT ON NEW REVISED PLAN. FBC 107.2.1
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-09 Cont ID  
Sent By fgiaquin Date 2019-01-09 Time 06:24 Rev Time 0.00
Received By fgiaquin Date 2019-01-04 Time 13:37 Sent To  
Notes
2019-01-07 13:37:19REVISION ROUTED TO FGIAUQINTO