Plan Review Details - Permit 19010113
Plan Review Stops For Permit 19010113
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 10:00 Rev Time 0.00
Received By pvalenti Date 2019-06-04 Time 10:00 Sent To  
Notes
2019-06-04 10:03:46PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 PROVIDE, AT TIME OF INSPECTION, THE PRODUCT APPROVALS
 FOR THE WINDOW MULLIONS (SIGNED AND STAMPED BY DESIGNER
 OF RECORD).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-08 Cont ID  
Sent By jgomez Date 2019-04-08 Time 18:08 Rev Time 0.00
Received By jgomez Date 2019-04-05 Time 17:08 Sent To  
Notes
2019-04-05 17:18:27RESIDENTIAL (R3)ALTERATION/ADDITION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT;
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.4.2
 AND R101.5 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM:
 (1) THE ADDRESS IS 300 LYTLE ST. NOT 301 LYTLE ST.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 (2) PROVIDE THE OWNER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 (3) PROVIDE THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B) ITEM # 1 ON PAGE 1 OF 5 IS INCORRECT. THIS IS NOT
 NEW CONSTRUCTION. THE HOUSE IS EXISTING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) ITEM #4 ON PAGE 1 OF 5 IS INCORRECT. ACCORDING TO
 PLANS SUBMITTED, THERE ARE 3 BEDROOMS NOT 4. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) ITEM #6 ON PAGE 1 OF 5 IS INCORRECT. CONDITIONED
 FLOOR AREA DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) IT LOOKS LIKE PERSON PREPARING THE ENERGY
 CALCULATIONS IS DOING THE CALCULATIONS FOR THE ENTIRE
 HOUSE. PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 ON PAGE
 1 OF 5 FOR ALL EXISTING AND NEW WINDOWS/DOORS AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 F) ITEM #8 ON PAGE 1 OF 5 IS INCORRECT. SLAB ON GRADE
 AREA DOESN'T DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) ITEM #9(B) ON PAGE 1 OF 5 IS INCORRECT. THERE IS NOT
 ADJACENT WALL. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) ITEM #11, 12 AND 13 ON PAGE 1 OF 5 ARE INCORRECT.
 SEE PLANS FOR NUMBER OF A/C UNITS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 J) OWNER TO COMPLETE CERTIFICATION AT BOTTOM OF FORM.
 INCLUDE THE DATE WHEN CERTIFYING THAT THE BUILDING IS
 IN COMPLIANCE WITH THE CODE. SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 K) PROJECT INFORMATION ON PAGE 2 OF 5 IS INCORRECT.
 THERE ARE NOT 2 STORIES IN THIS HOUSE. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 L) SPACES INFORMATION ON PAGE 2 OF 5 IS INCORRECT. SEE
 SPACES AND NUMBER OF KITCHENS ON PLANS AND REVISE AS
 REQUIRED. ALSO, PROVIDE CORRECT NUMBER OF OCCUPANTS
 BASED ON THE NUMBER OF BEDROOMS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 M) WALLS AND WINDOWS INFORMATION ON PAGE 3 OF 5 IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 2- INFORMATION ON SHEET 02 FOR PROPOSED ROOF FRAMING
 PLAN IS NOT CLEAR. SEC. 107.2.1 CITY AMENDMENTS.
 A) CLEARLY SPECIFY WHAT AT ARE THE EXISTING AND
 PROPOSED ROOF FRAMING MEMBERS. CLEARLY SPECIFY SIZES OF
 ALL ROOF FRAMING MEMBERS. CLEARLY SPECIFY ALL END
 CONNECTIONS OF THE ROOF FRAMING MEMBERS.
  
 RESPONSE:
 PARTIALLY COMPLIED. NEW ROOF TRUSS SYSTEM WAS PROVIDED.
 BUT NEED TO CLARIFY THE FOLLOWING:
 (1) HOW IS THE PROPOSED TRUSS CONNECTOR "A" (SIMPSON
 HETA20) GOING TO BE INSTALLED. THIS CONNECTOR NEEDS 4"
 EMBEDMENT. HOW DO YOU GET THE 4" EMBEDMENT IN AN
 EXISTING CONCRETE BEAM?. SEC. 107.2.1 CITY AMENDMENTS.
  
 (2) HOW IS THE PROPOSED TRUSS CONNECTOR "B" (SIMPSON
 H10A) GOING TO BE INSTALLED. THIS IS A WOOD TO WOOD
 CONNECTOR. ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE
 THERE IS A CONCRETE TIE BEAM NOT WOOD BEAM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B)OK. NEW ROOF TRUSS SYSTEM.
  
 C) OK. NO STEEL COLUMNS/BEAMS
  
 3- OK.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 ORIGINAL COMMENT:
 A) NEW EXTERIOR DOORS SHOWN ON PLANS.
  
 RESPONSE:
 DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL22513-R2 IS FOR SOLID DOORS ONLY. PLANS SHOW DOOR
 WITH GLAZING. PROVIDE PRODUCT APPROVAL FOR DOOR WITH
 GLAZING AS SHOWN ON PLANS.
  
 ORIGINAL COMMENT:
 B)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT BASED ON DOOR PRODUCT APPROVAL SUBMITTED.
 C) SHUTTERS IF DOOR WITH GLAZING DON'T HAVE IMPACT
 GLASS. AND, PROVIDE COMPLETE SHUTTERS INSTALLATION
 SCHEDULE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 6- PLANS NEED TO SPECIFY INSULATION IN THE GARAGE AREA
 THAT IS GOING TO BE CONVERTED TO BEDROOM. WALLS AND
 CEILING. SEC. R103.2 FBC-ENERGY CONSERVATION. NOTE:
 ENERGY CALCULATIONS AND PLANS TO BE COORDINATED TO
 AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 PLANS DON'T SPECIFY INSULATION AT THE PERIMETER WALL OF
 THE EXISTING GARAGE AREA TO BE CONVERTED TO BEDROOM.
  
 NEW COMMENTS:
 7- WINDOWS IN MASTER BEDROOM WERE REVISED. WINDOWS IN
 MASTER BEDROOM SHOWN ON PREVIOUS SUBMITTAL USED TO
 COMPLY WITH EGRESS. NOW WINDOWS IN THIS BEDROOM DON'T
 SEEM TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. SHOW COMPLIANCE WITH THE
 EGRESS REQUIREMENTS.
  
 8- COMPLETE NEW ROOF SYSTEM IS PROPOSED. SHOW LOCATION
 AND SIZE OF ATTIC ACCESS SHOWING COMPLIANCE WITH SEC.
 R807 FBC-RESIDENTIAL.
  
 9- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-01 Cont ID  
Sent By jgomez Date 2019-02-01 Time 13:37 Rev Time 0.00
Received By jgomez Date 2019-02-01 Time 10:37 Sent To  
Notes
2019-02-01 13:38:21RESIDENTIAL (R3)ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.4.2
 AND R101.5 FBC-ENERGY CONSERVATION.
  
 2- INFORMATION ON SHEET 02 FOR PROPOSED ROOF FRAMING
 PLAN IS NOT CLEAR. SEC. 107.2.1 CITY AMENDMENTS.
 A) CLEARLY SPECIFY WHAT AT ARE THE EXISTING AND
 PROPOSED ROOF FRAMING MEMBERS. CLEARLY SPECIFY SIZES OF
 ALL ROOF FRAMING MEMBERS. CLEARLY SPECIFY ALL END
 CONNECTIONS OF THE ROOF FRAMING MEMBERS.
  
 B)ENGINEER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE PROPOSED UPTURNED BEAM. UPTURN
 BEAM DETAIL SUBMITTED DOESN'T SHOW A BEAM. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING TRUSSES ARE RE-ENGINEERED TO BE SUPPORTED ON
 THIS BEAM. SPECIFY CONNECTIONS AT THE ENDS OF THE BEAM.
 INFORMATION ON ROOF FRAMING PLAN AND DETAIL ON SAME
 SHEET DON'T MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
 C) STEEL POST DETAIL IS NOT CLEAR. SIZE OF BOTTOM AND
 TOP PLATES ARE NOT CLEAR. CONNECTION OF POST TO BOTTOM
 PLATE IS NOT SPECIFIED. CLARIFY CONNECTION OF ROOF
 FRAMING MEMBERS TO PROPOSED I BEAM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- PROPOSED FLOOR PLAN SHOWS NEW OPENINGS FOR DOORS AND
 WINDOWS. CLARIFY WHY SOME OPENINGS SHOW REINFORCEMENT
 AT THE ENDS OF THE OPENINGS AND SOME DON'T. CLARIFY
 /REVISE AS REQUIRED TO SHOW REINFORCEMENT AT EACH
 OPENING. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) NEW EXTERIOR DOORS SHOWN ON PLANS.
  
 B)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 6- PLANS NEED TO SPECIFY INSULATION IN THE GARAGE AREA
 THAT IS GOING TO BE CONVERTED TO BEDROOM. WALLS AND
 CEILING. SEC. R103.2 FBC-ENERGY CONSERVATION. NOTE:
 ENERGY CALCULATIONS AND PLANS TO BE COORDINATED TO
 AVOID CONFLICTS/DELAYS.
  
 7- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-06-07 Cont ID  
Sent By cthroop Date 2019-06-07 Time 11:43 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 11:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-05-28 Cont ID  
Sent By jpearson Date 2019-05-28 Time 12:57 Rev Time 0.00
Received By jpearson Date 2019-05-28 Time 07:27 Sent To  
Notes
2019-05-28 12:57:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BASED ON SUBMISSION OF TANKLESS WATER HEATER, THE
 PANEL SCHEDULE AND LOAD CALCULATION IS NOW INCORRECT.
 PROVIDE CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC
 220; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-28 Cont ID  
Sent By jpearson Date 2019-04-09 Time 09:09 Rev Time 0.00
Received By jpearson Date 2019-04-09 Time 07:35 Sent To I
Notes
2019-05-28 12:54:23CHANGED STATUS TO FAIL BASED ON NEW SUBMISSION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By jpearson Date 2019-01-25 Time 09:03 Rev Time 0.00
Received By jpearson Date 2019-01-25 Time 08:03 Sent To  
Notes
2019-01-25 09:03:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. A NOTE WILL SUFFICE. NEC 210.8,
 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, 801.2,
 OR 901.2 AS APPLICABLE.
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE
 INTERIOR PANEL WHICH IS LOCATED IN THE HALLWAY.
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE
 IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE
 OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB.
 PROVIDE CORRECTIONS. NEC 230.70; FBC RE E3601.6
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By jpearson Date 2019-05-28 Time 12:54 Rev Time 0.00
Received By lmarchan Date 2019-05-07 Time 15:35 Sent To  
Notes
2019-05-08 15:35:14R37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-15 Time 16:05 Sent To  
Notes
2019-03-18 16:05:22R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 14:02 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 14:02 Sent To  
Notes
2019-01-07 13:09:22R01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 10:05 Rev Time 0.00
Received By pvalenti Date 2019-06-04 Time 10:05 Sent To  
Notes
2019-06-04 10:08:06PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED
  
 COUNTY IMPACT FEE STAMP ON PLANS.
 MU-2019-005471-0000 DATED: 2/22/2019.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-04-08 Cont ID  
Sent By jgomez Date 2019-04-08 Time 18:10 Rev Time 0.00
Received By jgomez Date 2019-04-08 Time 18:10 Sent To  
Notes
2019-04-08 18:10:57IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-01 Cont ID  
Sent By jgomez Date 2019-02-01 Time 13:38 Rev Time 0.00
Received By jgomez Date 2019-02-01 Time 13:38 Sent To  
Notes
2019-02-01 13:39:05IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-10 Cont ID  
Sent By cmontell Date 2019-05-10 Time 14:40 Rev Time 0.00
Received By cmontell Date 2019-05-10 Time 14:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-06 Cont ID  
Sent By cmontell Date 2019-04-06 Time 07:12 Rev Time 0.00
Received By cmontell Date 2019-04-06 Time 07:08 Sent To  
Notes
2019-04-06 07:12:36MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED CORRECT ADDRESS ON ENERGY CALCULATION AND HEAT
 LOAD CALCULATION PER WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, 6TH EDITION (2017), CHAPTER 1,
 ADMINISTRATION SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 14:02 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 14:02 Sent To  
Notes
2019-02-15 14:02:17NEED MECHANICAL PLAN

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-05-14 Cont ID  
Sent By thunt Date 2019-05-14 Time 15:47 Rev Time 0.00
Received By thunt Date 2019-05-14 Time 15:47 Sent To  
Notes
2019-05-14 15:47:28PLUMBIG 3RD REVIEW**DENIED**
  
 1) ANSWERED**
  
 2) NOT FULLY ANSWERED. PROVIDE COMPLETE INSTALLATION
 MANUAL SHOWING THE E.F RATING IS .92 AND MATCHES THE
 R405-2017 FORM. YOU SUBMITTED SPEC FOR AN ECO 27
 TANKLESS WATER HEATER REQUIRES (3) 40AMP BREAKERS BUT
 ELC SHEET SHOWS ON (1) 50AMP BREAKER. PLEASE CLARIFY.
 OLD NOTE:PROVIDE TANKLESS WATER HEATER MANUFACTURES
 INSTALLATION MANUAL, SHOW WITH THE CORRECT HEAT RISE IT
 WILL BE ABLE TO SUPPLY HOT WATER AS REQUIRED FBC-P
 607.1 WHILE AT FULL DEMAND FBC-P 604.3 TO ALL FIXTURES.
  
 3) ANSWERED**
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-08 Cont ID  
Sent By thunt Date 2019-04-08 Time 10:30 Rev Time 0.00
Received By thunt Date 2019-04-08 Time 10:30 Sent To  
Notes
2019-04-08 10:30:07PLUMBIG 2ND REVIEW**DENIED** PROVISO APPROVAL (1-SET)
 OF THE SHEETS FROM 1ST REVIEW HAVE BEEN REMOVED**
  
 1) PROVIDE A PLUMBING SANITARY ISOMETRIC DRAWING. FBC
 107.3.5
  
 2) PROVIDE TANKLESS WATER HEATER MANUFACTURES
 INSTALLATION MANUAL, SHOW WITH THE CORRECT HEAT RISE IT
 WILL BE ABLE TO SUPPLY HOT WATER AS REQUIRED FBC-P
 607.1 WHILE AT FULL DEMAND FBC-P 604.3 TO ALL FIXTURES.
  
 3) R405-2017 FORM HAS WRONG ADDRESS AND WRONG WATER
 HEATER LISTED. PROVIDE CORRECT TANKLESS AND REMOVE
 40GAL STORAGE TANK. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-24 Cont ID  
Sent By jesmith Date 2019-01-24 Time 14:42 Rev Time 0.00
Received By jesmith Date 2019-01-24 Time 13:28 Sent To  
Notes
2019-01-24 14:42:45APPROVED
 PROVISO
  
 1. RE: TANK-LESS WATER HEATER; SUBMIT MANUFACTURER'S
 SPECIFICATION SHEET TO INCLUDE THE MODEL NUMBER, GPM
 AND ELECTRICAL CHARACTERISTICS FOR THE TANKLESS WATER
 HEATERS PER WPB FBC 107.2.1 AND CONFIRM THEY WILL
 SUPPLY THE HOT WATER DEMAND. SAID SPECIFICATION MAY BE
 SUBMITTED AS A DEFERRED SUBMITTAL AS DEFINED BY WPB FBC
 107.3.4.1 AND SHALL BE SUBMITTED, APPROVED AND IN PLACE
 PRIOR TO THE FIRST PLUMBING INSPECTION.
 2. RE: PLAN SHEET 01: PLUMBING RISER; SEE REDLINED
 ITEMS ON DRAWING TO COMPLY WITH FBC RES SECTION 3108
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop Z ZONING
Rev No 4 Status P Date 2019-06-07 Cont ID  
Sent By awooten Date 2019-06-07 Time   Rev Time 0.00
Received By awooten Date 2019-06-07 Time   Sent To  
Notes
2019-06-07 15:10:51******************************ZONING
 PROVISO********************
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2019-05-17 Cont ID  
Sent By awooten Date 2019-05-17 Time   Rev Time 0.00
Received By awooten Date 2019-05-15 Time 15:35 Sent To  
Notes
2019-05-17 10:26:49*********************************ZONING REVIEW
 FAILED***********************************
  
 PROVIDE A SURVEY SHOWING EXISTING AND PROPOSED
 SETBACKS. (REPEAT COMMENTS)
  
 THE VALUE OF WORK TRIGGERS THE LANDSCAPE CODE. (EXCEEDS
 50% OF THE VALUE OF THE HOME.)
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 YOU CAN SUBMIT A CONDITIONAL LANDSCAPE APPROVAL REQUEST
 TO COMPLETE THE LANDSCAPE PRIOR TO CO FOR HOME. PLEASE
 CONTACT ME FOR MORE INFORMATION.
  
 FURTHER COMMENTS MAY FOLLOW ADDITIONAL REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-05 Cont ID  
Sent By awooten Date 2019-04-05 Time   Rev Time 0.00
Received By awooten Date 2019-04-05 Time   Sent To  
Notes
2019-04-05 12:59:43*********************************ZONING REVIEW
 FAILED***********************************
  
 PROVIDE A SURVEY SHOWING EXISTING AND PROPOSED
 SETBACKS. (REPEAT COMMENTS)
  
 THE VALUE OF WORK TRIGGERS THE LANDSCAPE CODE. (EXCEEDS
 50% OF THE VALUE OF THE HOME.)
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 FURTHER COMMENTS MAY FOLLOW ADDITIONAL REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-17 Cont ID  
Sent By awooten Date 2019-01-17 Time   Rev Time  
Received By awooten Date 2019-01-17 Time   Sent To  
Notes
2019-01-17 16:05:31*********************************ZONING REVIEW
 FAILED***********************************
  
 PROVIDE A SURVEY SHOWING EXISTING AND PROPOSED
 SETBACKS.
  
 THE VALUE OF WORK TRIGGERS THE LANDSCAPE CODE. (EXCEEDS
 50% OF THE VALUE OF THE HOME.)
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 FURTHER COMMENTS MAY FOLLOW ADDITIONAL REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]