Plan Review Details - Permit 19010093
Plan Review Stops For Permit 19010093
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By shill Date 2019-05-24 Time 10:28 Rev Time 0.00
Received By shill Date 2019-05-24 Time 10:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By shill Date 2019-05-14 Time 07:51 Rev Time 0.00
Received By shill Date 2019-05-14 Time 07:16 Sent To  
Notes
2019-05-14 07:51:59SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE SIGNATURE REVIEW REGARDING ARCHITECT'S TITLE BLOCK
 AND RESPONSE. PLEASE HAVE HIM CONTACT ME. PLANS HAVE
 BEEN STAMPED.
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
  
 ****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
  
 1. 2017 FBC-B 2204.1 WELDING, 2017 FBC-B 2204.2 BOLTING
 AT TIME OF INSPECTION THE CONTRACTOR IS REQUIRED TO
 PROVIDE:
 1. WELD PROCEDURE SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONNEL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-04 Cont ID  
Sent By jwitmer Date 2019-02-04 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2019-01-30 Time 10:44 Sent To  
Notes
2019-02-04 10:11:082017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010093
 ADD: 2235 OKEECHOBEE BLVD.
 CONT: HODGEN CONSTRUCTION, LLC
 TEL: 954-727-0333
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 04/2019
 ACTION: DENIED
  
 1) PROJECT COVER SHEET G001:
 1A) APPLICABLE CODES, PLEASE UPDATE THE AMENDMENTS
 CHAPTER 1FROM THE 2010 FLORIDA BUILDING CODE TO THE
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, 6TH EDITION (2017) CHAPTER 1, ADMINISTRATION.
  
 1B) APPLICABLE CODES, PLEASE UPDATE THE FLORIDA
 BUILDING CODE 5TH EDITION (2014) TO THE 6TH EDITION OF
 THE FLORIDA BUILDING CODE (2017). THIS CODE WAS ADOPTED
 STATEWIDE ON DEC. 31/ 2017.
  
 1C) SPECIAL INSPECTION SUMMARY INDICATES THE USE OF THE
 IBC AS THE CODE THESE PLANS WERE DEVELOPED UNDER.
 PLEASE NOTE IN THE 2017 FBC-B SECTIONS 1704 & 1705
 WHICH DEAL WITH TEST AND INSPECTIONS IS RESERVED. THE
 TERM SPECIAL INSPECTORS IS A TERM USED IN CONJUNCTION
 WITH THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 NOT APPLICABLE TO THIS PROJECT.
  
 1D)(1) THE COVERSHEET DOES NOT INDICATE WHAT THE
 MINIMUM BUILDING TYPE OF CONSTRUCTION IS? THE PLANS DO
 NOT PROVIDE THE SQUARE FOOT AREA, IF THERE WAS AREA
 INCREASES TAKEN FRONTAGE AND OR FIRE SPRINKLERS. THE
 SUBMITTED PLAN DOES NOT INCLUDE FIRE SPRINKLER PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
 BUILDING AREA INCLUDES: AREAS OF THE BUILDING NOT
 PROVIDED WITH SURROUNDING WALLS SHALL BE INCLUDED IN
 THE BUILDING AREA IF SUCH AREAS ARE INCLUDED WITHIN THE
 HORIZONTAL PROJECTION OF THE ROOF OR FLOOR ABOVE.
  
 1D)(2) SHEET 021_S600 SECTION 4 INDICATES THE USE OF
 PLYWOOD SHEATHING, THIS MAYBE AN ISSUE IF THE BUILDING
 TYPE IS DECLARED EITHER A TYPE I OR II CONSTRUCTION.
 SEE 2017 FBC-B 603.1.1(1.2) FIRE RETARDANT TREATED WOOD
 MAYBE USED IN NONBEARING EXTERIOR WALLS WHERE FIRE
 RESISTANCE RATED CONSTRUCTION IS NOT REQUIRED.
  
 2) BOTH THE SITE DEMO PLAN D100S AND THE ARCHITECTURAL
 SITE PLAN A100S NEITHER OF THESE PLANS INDICATE WHERE
 THE WORK IS TO BE COMPLETED UNDER THIS PERMIT. IT?S
 ASSUMED UNDER THE SERVICE ADVISORS AREA BUT TO THE
 RIGHT OF THE BUILDING THERE APPEARS TO BE A SMALL
 BUILDING AT THE GATE ENTRY? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET 016_S001 UNDER THE HEADING OF FOUNDATION NOTES
 THE LINE IS BLANK AS TO WHAT THE MINIMUM BEARING VALUE
 OF THE SOIL IS TO BE. THIS SHOULD BE A KNOWN FACTOR AS
 TO WHAT THE SOILS CAPACITY (ALLOWABLE) PER SQUARE FOOT
 FOR FILL AND FOR FOOTINGS? THE NOTE FURTHER INDICATES
 THE SOIL BEARING CAPACITY SHALL ALSO BE VERIFIED BY A
 SOILS ENGINEER.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) SHEETS S001, S002, S201, S600 & S680 ALL SHOW EITHER
 WELDED OR BOLTED CONNECTIONS TO OTHER STEEL FRAMING
 MEMBERS, THESE INSPECTIONS WILL NEED TO BE COMPLETED BY
 A 3RD PARTY ENGINEER. FOR FURTHER INFORMATION ON THIS
 INSPECTION CONTACT CHIEF BUILDING INSPECTOR KEN CONRAD
 8:00-9:00 (AM) AT 561-805-6666. ALL OTHER BUILDING
 INSPECTIONS WILL BE COMPLETED BY CITY INSPECTORS.
 2017 FBC-B WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING
  
 5) SHEET S600 INDICATES PLYWOOD SUB-SHEATHING, DOES NOT
 INDICATE THICKNESS NOR GRADE, THIS SECTION IS TAKEN
 ABOVE THE WINDOW LINE BUT A901 THE PERSPECTIVE VIEW
 DOES SHOW PLYWOOD SHEATHING BELOW THE WINDOWS, PLEASE
 SHOW HOW COMPLIANCE WILL BE ACHIEVED WITH:
  
 2017 FBC-B 2304.12.1.5 WOOD SIDING. CLEARANCE BETWEEN
 WOOD SIDING AND EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM) OR LESS THAN 2
 INCHES (51 MM) VERTICAL FROM CONCRETE STEPS, PORCH
 SLABS, PATIO SLABS AND SIMILAR HORIZONTAL SURFACES
 EXPOSED TO THE WEATHER EXCEPT WHERE SIDING, SHEATHING
 AND WALL FRAMING ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 6) THE PRODUCT APPROVALS DOES NOT SHOW THE DESIGNERS
 REVIEW AND APPROVAL. 2017 W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) THE KAWNEER TECHNICAL DRAWINGS ARE NOT A PRODUCT
 APPROVAL THAT SHOWS 3RD PARTY TESTING. 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)( (B) WINDOWS & MULLIONS
  
 8) THE PRESSURES FOUND ON SHEET 016_S001 VULT AND VASD
 ARE LOW. THE WALL ZONE 4 THE NEGATIVE PRESSURES AVERAGE
 4.166 PSF LOW AND FOR WALL ZONE 5 THEY AVERAGE 5.166
 PSF LOW. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 WE WERE USING THE MEAN ROOF HEIGHT OF 15 FT. OUR TABLES
 FOR ZONE 4 & 5 ARE ONLY 0.01 PSF DIFFERENT THAN
 ENGINEERING EXPRESS TABLES FOR BUILDINGS < THAN 60
 FEET.
  
 9) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By jpearson Date 2019-05-24 Time 07:40 Rev Time 0.00
Received By jpearson Date 2019-05-24 Time 07:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 15:54 Rev Time 0.00
Received By jleahy Date 2019-02-20 Time 15:54 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By rrossano Date 2019-05-28 Time   Rev Time 0.00
Received By rrossano Date 2019-05-28 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-05-15 Cont ID  
Sent By rrossano Date 2019-05-15 Time   Rev Time 0.00
Received By rrossano Date 2019-05-15 Time   Sent To I
Notes
2019-05-15 15:35:24PROPOSED SERVICE WRITER STRUCTURE FOUNDATION IS OVER
 ONSITE DRAINAGE PIPES. USE CAUTION.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By RRossano Date 2019-01-29 Time   Rev Time  
Received By rrossano Date 2019-01-29 Time   Sent To I
Notes
2019-01-29 07:12:27PROVIDE SEPARATE SUBMITTAL TO ENGINEERING DEPARTMENT
 FOR REVIEW. CITY OF WPB ENGINEERING FORMS AND DESIGN
 REQUIREMENT INFORMATION CAN BE FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By pleduc Date 2019-05-24 Time   Rev Time 0.00
Received By pleduc Date 2019-05-24 Time 09:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-17 Cont ID  
Sent By scaldero Date 2019-01-17 Time 15:08 Rev Time 0.00
Received By scaldero Date 2019-01-17 Time 14:41 Sent To  
Notes
2019-01-17 15:08:47PERMIT # 19010093
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) SHEET G001 - OCCUPANT LOAD STATES TOTAL OF 4
 PERMITTED, HOWEVER THERE ARE 6 DESKS AND SEATS SHOWN
 WITH THE LAYOUT DIVIDED BY 3. PLEASE CORRECT OR PROVIDE
 JUSTIFICATION FOR ALLOWED OCCUPANCY OF 6.
  
 2) SHEET A101 - THE PROVIDED FIRE EXTINGUISHER SHOULD
 BE EASILY ACCESSIBLE TO ALL OCCUPANTS. THE HALF WALLS
 THAT CREATE THE DIVIDERS BETWEEN THE 3 SEPARATE
 SECTIONS OF THIS STRUCTURE PREVENT EASY ACCESS TO THE
 EXTINGUISHER.
 PLEASE CONSIDER MOVING THE FIRE EXTINGUISHER, OR
 PLACING AN ADDITIONAL ONE, MORE CENTRALLY LOCATED AND
 EASILY ACCESSIBLE FOR ALL OCCUPANTS. A POSSIBLE OPTION
 IS PLACING THE FIRE EXTINGUISHER ON THE EXTERIOR OF THE
 STRUCTURE.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-29 Cont ID  
Sent By shill Date 2019-05-29 Time 06:15 Rev Time 0.00
Received By shill Date 2019-05-22 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 07:27 Rev Time 0.00
Received By shill Date 2019-04-11 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-15 Cont ID  
Sent By lmarchan Date 2019-03-15 Time 16:29 Rev Time 0.00
Received By lmarchan Date 2019-01-16 Time 16:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-05 Cont ID  
Sent By lmarchan Date 2019-06-05 Time 10:47 Rev Time 0.00
Received By lmarchan Date 2019-05-29 Time 12:32 Sent To  
Notes
2019-06-05 10:47:256/5/19 PER IMPACT OFFICE, NO FEES DUE. EMAIL UPLOADED
 INTO SYSTEM. LEM
2019-05-29 12:32:325/29/19 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-04 Cont ID  
Sent By jwitmer Date 2019-02-04 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2019-01-30 Time 10:44 Sent To  
Notes
2019-02-04 10:11:38IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 08:29 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 08:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-02 Cont ID  
Sent By ccole Date 2019-05-02 Time 12:21 Rev Time 0.00
Received By ccole Date 2019-05-01 Time 17:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By ccole Date 2019-02-27 Time 16:28 Rev Time 0.00
Received By ccole Date 2019-02-27 Time 16:17 Sent To  
Notes
2019-02-27 16:33:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010093
 2/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC EC.
  
 2) SHEET M201: THE ROOF SURFACE IS NOT AN APPROVED
 PLACE OF DISPOSAL FOR THE CONDENSATE- SECTION 307.2.1
 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-02-26 Cont ID  
Sent By gjohnson Date 2019-02-26 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2019-02-26 Time 16:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By shill Date 2019-05-14 Time 08:53 Rev Time 0.00
Received By shill Date 2019-05-14 Time 08:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-01 Cont ID  
Sent By shill Date 2019-04-01 Time 08:05 Rev Time 0.00
Received By shill Date 2019-04-01 Time 08:05 Sent To  
Notes
2019-04-01 08:06:03ROOF REVIEW - SEE BUILDING COMMENTS
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-06-06 Cont ID  
Sent By shill Date 2019-06-06 Time 17:15 Rev Time 0.00
Received By shill Date 2019-06-06 Time 17:15 Sent To  
Notes
2019-06-06 17:15:34ORIGINAL S&S MEPS SUBMITTED UNDER SUBMITTAL #19060161
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By shill Date 2019-05-24 Time 10:30 Rev Time 0.00
Received By shill Date 2019-05-24 Time 10:30 Sent To  
Notes
2019-06-05 11:06:55PROVISO: SUBMIT ORIGINAL SIGNED & SEALED MEP DRAWINGS
  
2019-05-24 07:32:46ELECTRICAL SHEETS FAIL, MISSING THE STATEMENT PER FAC
 61G15-23.004, MISSING THE TIRD PARTY VERIFICATION. WPB
 FBC 107.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 10:01 Rev Time 0.00
Received By shill Date 2019-04-30 Time 10:01 Sent To  
Notes
2019-05-02 12:23:42 
 1) MECH SHEETS NOT DIGITALLY SIGNED AND SEALED.
 2) THE COMCHECK REPORT AND THE AC CALCS REQUIRE SHOP
 DRAWING STAMPS BY THE EOR
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
  
2019-04-30 10:02:12SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. ARCHITECTURAL PAGES ARE DIGITALLY SIGNED BUT LACK A
 TITLE BLOCK, FS481. NOTE THAT THE ARCHITECT BUSINESS
 LICENSE NUMBER IS REQUIRED TO BE INCLUDED IN THE TITLE
 BLOCK (SPARC + ARCHITECTURE STUDIO). NEW PAGES
 SUBMITTED WILL REQUIRE VERIFICATION.
  
 2ND REVIEW, RESPONSE STATES THAT ORIGINAL PRINTS WILL
 BE PROVIDED. THIS IS NOT AN OPTION - DIGITAL PLANS
 REQUIRE A TITLE BLOCK IN COMPLIANCE WITH FLORIDA
 STATUTE 481 AND FLORIDA ADMINISTRATIVE CODE. INCLUDE
 SPARC + ARCHITECTURE STUDIO'S ARCHITECT BUSINESS NUMBER
 IN THE TITLE BLOCK OR CALL ME TO DISCUSS.
  
 AS ARCHITECT HAS A DIGITAL SIGNATURE, ALL PAGES ARE
 REQUIRED TO BE DIGITALLY SIGNED. NOTE THAT THERE IS NO
 ISSUE WITH THE DIGITAL SIGNATURE, ONLY THE TITLE BLOCK.
  
 2. THE FOLLOWING COMMENTS REGARDING THE STRUCTURAL
 ENGINEER WERE NOT ADDRESSED:
  
 THE STRUCTURAL PAGES ARE NOT DIGITALLY SIGNED. IF THE
 ENGINEER, WALID A NANNIS, PE DOES NOT HAVE A DIGITAL
 SIGNATURE, ONE PAPER ORIGINAL WILL BE REQUIRED AFTER
 ALL REVIEWS HAVE PASSED, FS471.
  
 THE STRUCTURAL PAGES LACK A TITLE BLOCK, FS471 - THIS
 IS REQUIRED FOR DIGITALLY SUBMITTED PLANS.
  
 THE STRUCTURAL ENGINEER'S SEAL IS NOT IN COMPLIANCE
 WITH FAC61G15-23 (USES THE WORD "CERTIFICATE" RATHER
 THAN "LICENSE") - THIS IS REQUIRED TO BE CHANGED ON THE
 DIGITALLY SUBMITTED PLANS.
  
 5. THE MECHANICAL AND ELECTRICAL PAGES ARE NOT
 DIGITALLY SIGNED. ONE PAPER ORIGINAL WILL BE REQUIRED
 AFTER ALL REVIEWS HAVE PASSED, FS471. (TITLE BLOCK OK)
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-01 Cont ID  
Sent By shill Date 2019-04-01 Time 07:59 Rev Time 0.00
Received By shill Date 2019-04-01 Time 07:59 Sent To  
Notes
2019-04-01 08:05:40SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ARCHITECTURAL PAGES ARE DIGITALLY SIGNED BUT LACK A
 TITLE BLOCK, FS481. NOTE THAT THE ARCHITECT BUSINESS
 LICENSE NUMBER IS REQUIRED TO BE INCLUDED IN THE TITLE
 BLOCK (SPARC + ARCHITECTURE STUDIO). NEW PAGES
 SUBMITTED WILL REQUIRE VERIFICATION.
  
 2. THE STRUCTURAL PAGES ARE NOT DIGITALLY SIGNED. IF
 THE ENGINEER, WALID A NANNIS, PE DOES NOT HAVE A
 DIGITAL SIGNATURE, ONE PAPER ORIGINAL WILL BE REQUIRED
 AFTER ALL REVIEWS HAVE PASSED, FS471.
  
 3. THE STRUCTURAL PAGES LACK A TITLE BLOCK, FS471.
  
 4. THE STRUCTURAL ENGINEER'S SEAL IS NOT IN COMPLIANCE
 WITH FAC61G15-23 (USES THE WORD "CERTIFICATE" RATHER
 THAN "LICENSE").
  
 5. THE MECHANICAL AND ELECTRICAL PAGES ARE NOT
 DIGITALLY SIGNED. ONE PAPER ORIGINAL WILL BE REQUIRED
 AFTER ALL REVIEWS HAVE PASSED, FS471. (TITLE BLOCK OK)
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By eschneid Date 2019-05-28 Time 11:56 Rev Time 0.25
Received By eschneid Date 2019-05-28 Time 11:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-03 Cont ID  
Sent By eschneid Date 2019-05-03 Time 16:03 Rev Time 0.25
Received By eschneid Date 2019-05-03 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By eschneid Date 2019-03-15 Time 16:15 Rev Time 0.50
Received By eschneid Date 2019-03-15 Time 16:15 Sent To  
Notes
2019-03-15 16:26:12FAILED
  
 THE NEW UNDER CANOPY LIGHTS NEED TO BE RECESSED OR
 FLUSH MOUNTED. PROVIDE VERIFICATION THAT LIGHTS LB1
 MEETS THIS REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]