Plan Review Details - Permit 19010075
Plan Review Stops For Permit 19010075
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-30 Cont ID  
Sent By dbattles Date 2019-01-30 Time 13:43 Rev Time 0.00
Received By dbattles Date 2019-01-29 Time 16:04 Sent To  
Notes
2019-01-30 13:44:54****CORRECTIONS****
 W.P.B. PERMIT: 19010075
 REVIEWED: JANUARY 30, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[RE] = FBC EXISTING RESIDENTIAL
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 PROJECT DATA:
 1. 501 FBC[RE] STATE THE LEVEL OF ALTERATION FOR WORK
 BEING PERFORMED.
 PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS
 WOULD BE A LEVEL 2 ALTERATION.
 OCCUPANCY = (R-3 FOR SINGLE FAMILY)
 TYPE OF WALL CONSTRUCTION = _________(VB?)
 RISK CATEGORY = ___(II)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF
 PEAK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 COMPONANT & CLADDING:
 FBC TABLE 301.2(2) FBC[R]
 DESIGN PRESSURE = +___ & -___
  
 2. 301.2(3) FBC[R] PROVIDE PRESSURE ON EACH WINDOW/DOOR
 AND INDICATE IF THE OPENING IS IN THE INTERIOR OR
 EXTERIOR ZONE.
  
 3. 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
  
 4. 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE
 PART OF THE ALTERATION SHALL COMPLY WITH SECTION
 R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH
 R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5
 HOW ARE ENERGY CODES BEING APPLIED?
 PROVIDE INSULATION VALUE OF CEILING ABOVE AND
 INSULATION AT IN-FILL LOCATIONS.
  
 5. 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES.
  
 6. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWS AND FOLDING GLASS DOOR SYSTEM FOR CLADDING AND
 COMPONENTS.
  
 7. 107.3.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL FOR
 WINDOW MULL IF THE WINDOW OPENINGS CONSIST OF MORE THAN
 ONE WINDOW FRAME PER OPENING.
 301.2(2) TABLE FBC[R]
  
 8.PLEASE PROVIDE ONE ADDITIONAL COPY OF THE THREE
 PRODUCT APPROVALS 17-0420.04, 18-0627.01 AND 17-0420.12
 THAT WERE PROVIDED. ONLY ONE SET WAS IN THE PERMIT SET,
 BUT WE NEED TWO SETS TOTAL.
  
 9. IS THERE A STEPDOWN FROM THE INTERIOR SPACE?
 10. HOW WILL THIS BE FILLED IN?
 11. CAN THE REQUIRMENTS FOR THE NEXT TO CODE SECTIONS
 BELOW BE MET?
  
 506.2.3 FBC[R] VAPOR RETARDER. A 6-MIL (0.006 INCH; 152
 ?M) POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS
 LAPPED NOT LESS THAN 6 INCHES SHALL BE PLACED BETWEEN
 THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR THE
 PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS.
  
 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2019-01-23 Cont ID  
Sent By jpearson Date 2019-01-23 Time 15:29 Rev Time 0.00
Received By jpearson Date 2019-01-23 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 13:54 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 13:54 Sent To  
Notes
2019-01-04 14:38:37R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-30 Cont ID  
Sent By dbattles Date 2019-01-30 Time 13:45 Rev Time 0.00
Received By dbattles Date 2019-01-30 Time 13:45 Sent To  
Notes
2019-01-30 13:45:52109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 13:54 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 13:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By llouie Date 2019-01-15 Time   Rev Time  
Received By llouie Date 2019-01-15 Time   Sent To  
Notes
2019-01-15 09:26:48** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED, SIGNED AND SEALED SURVEY IS MISSING FROM
 THE PERMIT APPLICATION. PLEASE PROVIDE.
  
 2.) SCOPE OF WORK SEEMS TO BE THE ENCLOSURE OF AN
 EXISTING SCREENED PATIO SPACE WHICH DOES NOT SEEM TO BE
 REFLECTED IN THE DESCRIPTION. PLEASE REVISE.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (BEAR LAKE ISLAND); ORD. 2066-87
  