Plan Review Details - Permit 19010025
Plan Review Stops For Permit 19010025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By dharvey Date 2019-01-14 Time 12:07 Rev Time 0.00
Received By dharvey Date 2019-01-14 Time 12:07 Sent To  
Notes
2019-01-14 12:08:16EXISTING BUILDING. INTERIOR WORK ONLY, NO MECHANICAL
 WITHOUT PERMITS.
 NEED SUBS FOR ELECTRIC AND PLUMBING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 10:10 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 08:29 Sent To  
Notes
2019-01-08 10:16:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN SUBMITTED DOES NOT REPRESENT THE BUILDING
 DESIGN AS REPRESENTED ON THE PROPERTY APPRAISERS
 OFFICE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. PROVIDE PLAN THAT REPRESENTS STRUCTURE WITH ACCURATE
 DEMENSIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. REPEAT
 COMMENT
  
 3. DESIGNER TO PRINT NAME AND SIGN PLAN.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By dharvey Date 2019-01-14 Time 12:08 Rev Time 0.00
Received By dharvey Date 2019-01-14 Time 12:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 11:10 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 08:30 Sent To  
Notes
2019-01-08 11:22:34ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ELECTRICAL PERMIT REQUIRED
  
 1. IF SCOPE OF WORK EXCEEDS THE REMOVAL OF FIXTURES
 ONLY AND ANY WIRING SYSTEMS ARE ALTERED A WIRING RISER
 DIAGRAHM WILL BE REQUIRED IN ADDITION TO A LOAD
 CALCULATION FOR THE HOUSE.
  
 E3401.4 ADDITIONS AND ALTERATIONS.
 ANY ADDITION OR ALTERATION TO AN EXISTING ELECTRICAL
 SYSTEM SHALL BE MADE IN CONFORMITY TO THE PROVISIONS OF
 CHAPTERS 34 THROUGH 43. WHERE ADDITIONS SUBJECT
 PORTIONS OF EXISTING SYSTEMS TO LOADS EXCEEDING THOSE
 PERMITTED HEREIN, SUCH PORTIONS SHALL BE MADE TO COMPLY
 WITH CHAPTERS 34 THROUGH 43.
  
 E3403.2 INSPECTION REQUIRED.
 NEW ELECTRICAL WORK AND PARTS OF EXISTING SYSTEMS
 AFFECTED BY NEW WORK OR ALTERATIONS SHALL BE INSPECTED
 BY THE BUILDING OFFICIAL TO ENSURE COMPLIANCE WITH THE
 REQUIREMENTS OF CHAPTERS 34 THROUGH 43.
  
 E3403.3 LISTING AND LABELING.
 ELECTRICAL MATERIALS, COMPONENTS, DEVICES, FIXTURES AND
 EQUIPMENT SHALL BE LISTED FOR THE APPLICATION, SHALL
 BEAR THE LABEL OF AN APPROVED AGENCY AND SHALL BE
 INSTALLED, AND USED, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. [110.3(B)]
  
 2. PROVIDE SMOKE DETECTORS PER FBC R314.
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 12:34 Rev Time 0.00
Received By cthroop Date 2019-01-02 Time 10:18 Sent To  
Notes
2019-01-04 10:18:13R29

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-01-14 Cont ID  
Sent By dharvey Date 2019-01-14 Time 12:09 Rev Time 0.00
Received By dharvey Date 2019-01-14 Time 12:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 10:16 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 10:10 Sent To  
Notes
2019-01-08 10:19:52MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 MECHANICAL PERMIT REQUIRED
  
 1. BASED ON THE SCOPE OF WORK WHICH INCLUDES THE
 REMOVAL OF ALL DRYWALL THE AIR HANDLER UNIT (AHU) WILL
 NEED TO BE REMOVED AND RE-INSTALLED BY A LICENSED
 MECHANICAL CONTRACTOR.
  
 M1201.1 SCOPE.
 THE PROVISIONS OF CHAPTERS 12 THROUGH 24 SHALL REGULATE
 THE DESIGN, INSTALLATION, MAINTENANCE, ALTERATION AND
 INSPECTION OF MECHANICAL SYSTEMS THAT ARE PERMANENTLY
 INSTALLED AND USED TO CONTROL ENVIRONMENTAL CONDITIONS
 WITHIN BUILDINGS. THESE CHAPTERS SHALL ALSO REGULATE
 THOSE MECHANICAL SYSTEMS, SYSTEM COMPONENTS, EQUIPMENT
 AND APPLIANCES SPECIFICALLY ADDRESSED IN THIS CODE.
  
 M1202.1 ADDITIONS, ALTERATIONS OR REPAIRS.
 ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO A
 MECHANICAL SYSTEM SHALL CONFORM TO THE REQUIREMENTS FOR
 A NEW MECHANICAL SYSTEM WITHOUT REQUIRING THE EXISTING
 MECHANICAL SYSTEM TO COMPLY WITH ALL OF THE
 REQUIREMENTS OF THIS CODE. ADDITIONS, ALTERATIONS OR
 REPAIRS SHALL NOT CAUSE AN EXISTING MECHANICAL SYSTEM
 TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. MINOR
 ADDITIONS, ALTERATIONS OR REPAIRS TO EXISTING
 MECHANICAL SYSTEMS SHALL MEET THE PROVISIONS FOR NEW
 CONSTRUCTION, UNLESS SUCH WORK IS DONE IN THE SAME
 MANNER AND ARRANGEMENT AS WAS IN THE EXISTING SYSTEM,
 IS NOT HAZARDOUS, AND IS APPROVED.
  
 M1202.3 MAINTENANCE.
 MECHANICAL SYSTEMS, BOTH EXISTING AND NEW, AND PARTS
 THEREOF SHALL BE MAINTAINED IN PROPER OPERATING
 CONDITION IN ACCORDANCE WITH THE ORIGINAL DESIGN AND IN
 A SAFE AND SANITARY CONDITION. DEVICES OR SAFEGUARDS
 THAT ARE REQUIRED BY THIS CODE SHALL BE MAINTAINED IN
 COMPLIANCE WITH THE CODE EDITION UNDER WHICH INSTALLED.
 THE OWNER OR THE OWNER?S DESIGNATED AGENT SHALL BE
 RESPONSIBLE FOR MAINTENANCE OF THE MECHANICAL SYSTEMS.
 TO DETERMINE COMPLIANCE WITH THIS PROVISION, THE
 BUILDING OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE A
 MECHANICAL SYSTEM TO BE REINSPECTED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By dharvey Date 2019-01-14 Time 12:09 Rev Time 0.00
Received By dharvey Date 2019-01-14 Time 12:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 11:22 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 08:30 Sent To  
Notes
2019-01-08 12:12:00PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLUMBING PERMIT REQUIRED
  
 1. PROVIDE PLUMBING RISER DIAGRAHM.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12).
  
 P2601.2 CONNECTIONS TO DRAINAGE SYSTEM
 PLUMBING FIXTURES, DRAINS, APPURTENANCES AND APPLIANCES
 USED TO RECEIVE OR DISCHARGE LIQUID WASTES OR SEWAGE
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM OF THE BUILDING OR PREMISES, IN ACCORDANCE WITH
 THE REQUIREMENTS OF THIS CODE. THIS SECTION SHALL NOT
 BE CONSTRUED TO PREVENT INDIRECT WASTE CONNECTIONS
 WHERE REQUIRED BY THE CODE.
  
 P2603.1 GENERAL.
 IN THE PROCESS OF INSTALLING OR REPAIRING ANY PART OF A
 PLUMBING AND DRAINAGE INSTALLATION, THE FINISHED
 FLOORS, WALLS, CEILINGS, TILE WORK OR ANY OTHER PART OF
 THE BUILDING OR PREMISES THAT MUST BE CHANGED OR
 REPLACED SHALL BE LEFT IN A SAFE STRUCTURAL CONDITION
 IN ACCORDANCE WITH THE REQUIREMENTS OF THE BUILDING
 PORTION OF THIS CODE.
  
 2. IF WATER HEATER IS TO BE REPLACED, INCLUDE IT ON THE
 ENERGY CALCULATIONS REQUIRED UNDER THE ELECTRICAL
 REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  