| Notes |
| 2019-03-15 16:05:46 | THE REVISED E101 SHEET WILL BE INCLUDED IN THE NEW | | | REVISED SET OF PLANS AND WILL BE REVIEWED AT THAT TIME. | | | | | | THE MECHANICAL INSPECTORS WILL CHECK BREAKER SIZES FOR | | | THE EVAPORATORS AND CONDENSERS AT TIME OF INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-03-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-03-14 |
Time |
09:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-03-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-03-01 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-01-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-16 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-08 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-15 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-15 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-11 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-11 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2019-03-11 17:22:32 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19010002 | | | 3/11/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) AN ELECTRICAL PLAN SHEET HAS BEEN UPLOADED UNDER THE | | | TITLE OF M102 WHICH IS SUPPOSED TO BE A MECHANICAL PLAN | | | SHEET- SECTION 107 WPB. | | | | | | 2) THE NEW M101 PLAN SHEET WAS NOT UPLOADED CORRECTLY | | | AND ONLY APPEARS IN THE PRINTABLE FORMAT- SECTION 107 | | | WPB. | | | | | | 3) THIS IS AN ELECTRONIC SUBMITTAL. PLEASE DO NOT | | | UPLOAD DOCUMENTS THAT HAVE BEEN FOLDED OVER AND STAMPED | | | WITH SHOP DRAWING APPROVALS. THE TEXT AND DETAILS ARE | | | HIDDEN BEHIND THE STAMPS- SECTION 107 WPB. | | | | | | 4) THE SUBMITTAL FOR THE ROOF STAND IS AN OUTDATED COPY | | | FROM 2014. PLEASE PROVIDE UPDATED ENGINEERING IN | | | COMPLIANCE WITH THE FBC-7 SIXTH EDITION. | | | | | | 5) THE CHANGE IN VALUE TO $26,000 IS ACCEPTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-01-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-16 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-16 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2019-01-16 16:38:24 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19010002 | | | 1/16/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHOW THE LOCATIONS OF THE REMOTE CONDENSER AND | | | REFRIGERANT PIPING RUNS FROM THE COOLER TO THE | | | CONDENSER- SECTION 107.2.1 WPB, AND SECTION 1107 FBC M. | | | | | | 2) PROVIDE ENGINEERING FOR INSTALLATION OF THE | | | CONDENSER- SECTION 301.15 FBC M. | | | | | | 3) THE $4,000 JOB VALUE ON THE APPLICATION IS LOW FOR A | | | 13'X10' WALK IN COOLER AND REFRIGERATION SYSTEM . | | | PLEASE PROVIDE AN ACCURATE VALUE THAT INCLUDES LABOR, | | | MATERIALS AND THE COST OF THE COOLER AND REFRIGERATION | | | SYSTEM- SECTION 109.3 WPB | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-15 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-15 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-11 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-11 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2019-03-11 17:24:30 | SHEETS ARE OK BUT NEW UPLOADED SHEETS WILL NEED REVIEW. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2019-01-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-16 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-16 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |