| 2018-12-31 15:48:11 | 12/31/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. THE LEGEND OF NUMBER IS NOT CLEAR, PLEASE SIMPLIFY |
| | BY LABELING THE PIPE SIZE ON THE ISOMETRIC AND GET RID |
| | OF THE NUMBER, THIS MAKE IF EASIER FOR FIELD |
| | VERIFICATION, WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| | (DRYER, BBQ AND RANGE TO VERIFY COMPLIANCE WITH 2017 |
| | FBC FUEL GAS RES. SEC. G2408.1. |
| | 3. PLEASE PUT TYPE OF GAS ON ISOMETRIC AND SHOW METER |
| | (LP OR NATURAL). WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| | GAS RES. SEC. G2413.2 AND G2404.3. |
| | 5. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| | OF IGNITION, WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017 |
| | FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE ISOMETRIC PLAN PER 2017 FBC FUEL GAS SEC. 402.2 |
| | OR 2017 FBC FUEL GAS RES. SEC. G2413.2. |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS SECS. |
| | 502 THRU 505 OR 2017 FBC FUEL GAS RES. SECS. G2426 THRU |
| | G2429.1 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |