Plan Review Details - Permit 18120839
Plan Review Stops For Permit 18120839
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-01-02 Cont ID  
Sent By fgiaquin Date 2019-01-02 Time 06:11 Rev Time 0.00
Received By fgiaquin Date 2019-01-02 Time 05:56 Sent To  
Notes
2019-01-02 06:11:34ROUTED TO SHILL'S DESK. NEEDS SIGNATURE FROM QUALIFIER
 ON PLANS.
  
 ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2019-01-07 Cont ID  
Sent By shill Date 2019-01-07 Time 16:08 Rev Time 0.00
Received By shill Date 2019-01-07 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By shill Date 2019-01-02 Time 06:18 Rev Time 0.00
Received By shill Date 2018-12-21 Time 12:46 Sent To  
Notes
2019-01-02 06:20:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
  
 FBC 107.2.1, ALL INFORMATION, DRAWINGS,SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 EITHER RESUBMIT A DOCUMENT WHICH INCLUDES THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN OR
 MAKE AN APPOINTMENT WITH ME FOR THE QUALIFIER TO SIGN
 THE PLAN (AND THE PERMIT WILL BE ISSUED AT THAT TIME).
  
  
2018-12-26 12:46:47ELEC <5K