Plan Review Details - Permit 18120823
Plan Review Stops For Permit 18120823
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-04-29 Cont ID  
Sent By jgomez Date 2019-04-29 Time 14:36 Rev Time 0.00
Received By jgomez Date 2019-04-29 Time 11:51 Sent To  
Notes
2019-04-29 12:15:22BUILDING REVIEW APPROVED WITH PROVISO:
 1- DRAINAGE PLAN WAS DISCUSSED WITH RANDY WERTEPNY
 (ENGINEER). PROVIDE REVISED DRAINAGE PLAN PRIOR TO
 INSPECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-03-28 Cont ID  
Sent By jgomez Date 2019-03-28 Time 13:54 Rev Time 0.00
Received By jgomez Date 2019-03-28 Time 13:16 Sent To  
Notes
2019-03-28 13:55:08NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 ORIGINAL COMMENT:
 1- REVISE DRAINAGE PLAN SHOWN ON SHEET C-1. BASED ON
 THE GRADE ELEVATIONS ON THE REAR OF THE LOT, IT LOOKS
 LIKE THE WATER IS BEING DIVERTED TO THE NEIGHBOR.
 REVISE AS REQUIRED SO WATER IS KEPT WITHIN THE LOT OR
 DIVERTED TO AN APPROVED COLLECTION POINT.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 REPEAT COMMENT (TWO TIMES). NO ADDRESSED AT ALL.
 REVISED DRAINAGE PLAN SHOWS SECTION C-C WHICH SHOWS A
 BERM WITH ONE OF THE SLOPES TOWARDS THE REAR PROPERTY.
 THEREFORE, DIVERTING THE WATER TOWARD THE REAR REAR
 PROPERTY. REVISE AS REQUIRED.
  
 2- OK
  
 3- OK.
  
 4- OK
  
 5- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT (TWO TIMES). NO ADDRESSED AT ALL.
 PARTIALLY COMPLIED. PROVIDE CORRECT NAME OF CONTRACTOR.
  
 ORIGINAL COMMENT:
 B)ITEM #5 ON PAGE 1 OF 5 STATES THAT THIS IS NOT A
 WORST CASE SCENARIO BUT ON PAGE 2 OF 5 IT SHOWS THAT
 THE HOUSE WAS ROTATED 315 DEGREES. THIS IS
 CONTRADICTORY. THE ENERGY CALCULATIONS NEED TO BE DONE
 FOR THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT (THREE TIMES). NO ADDRESSED AT ALL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C)PROVIDE WINDOWS AND DOORS DOCUMENTATION FROM
 MANUFACTURER SHOWING THE SHGC FACTOR AND U-FACTOR
 EFFICIENCIES SHOWN ON ITEM #7 ON PAGE 1 OF 5. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION. NOTE: THIS IS ONLY
 REQUIRED WHEN PERSON DOING THE CALCULATIONS IS NOT
 USING THE PROGRAM DEFAULT FACTORS.
  
 RESPONSE:
 REPEAT COMMENT (THREE TIMES). NO ADDRESSED AT ALL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) CEILING R-VALUE INSULATION ON ITEM #10 DOESN'T MATCH
 PLANS. REVISE AS REQUITED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT (THREE TIMES). NO ADDRESSED AT ALL.
 REPEAT COMMENT. NOT ADDRESSED. ALSO, THE ATTIC IS NOT
 VENTED. PLANS SPECIFY FOAM INSULATION. SEE PLANS AND
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 E) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT (THREE TIMES). NO ADDRESSED AT ALL.
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 F) PARTIALLY DONE. THE VENT RATIO WAS REVISED, BUT I
 APOLOGIZE BECAUSE THIS ITEM WAS OVERLOOKED. THERE IS NO
 VENTED ATTIC. SEE ITEM #5D ABOVE.
  
 RESPONSE:
 REPEAT COMMENT (TWO TIMES). NO ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 G) REVISE WINDOWS ORIENTATION AND AREA ON PAGE 3 OF 5
 TO MATCH ACTUAL ORIENTATION AND AREA SHOWN ON PLANS.
 NOTE: COORDINATE WITH ITEM #5(B) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT (THREE TIMES). NO ADDRESSED AT ALL.
 REPEAT COMMENT. COORDINATE WITH ITEM #5(B) ABOVE.
  
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- OK.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL).
  
 A) PRECAST LINTELS. NOTE: NOA 16-0126.03 SPECIFIED ON
 SHEET 3 OF 7 IS EXPIRED. REVISE AS REQUIRED ALSO. THERE
 IS NO NEED TO SPECIFY NOA ON DRAWINGS. JUST REVIEW IN
 WRITING THE ACTUAL PRODUCT APPROVAL.
  
 RESPONSE:
 REPEAT COMMENT. NO SUBMITTED AND NO WORD FROM
 CONTRACTOR IF DEFERRED SUBMITTAL IS PREFERRED AT HIS
 TIME.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. ONLY ONE COPY WAS
 SUBMITTED AND WAS VOID. NEED TWO COPIES. ALSO REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NO ADDRESSED. AND NO WORD FROM
 CONTRACTOR IF DEFERRED SUBMITTAL IS PREFERRED AT HIS
 TIME.
  
 C)GARAGE DOOR FLORIDA PRODUCT APPROVAL SUBMITTED. DOOR
 DOESN'T MEET THE POSITIVE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD. PROVIDE DOOR THAT MEETS THE
 CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NO SUBMITTED AND NO WORD FROM
 CONTRACTOR IF DEFERRED SUBMITTAL IS PREFERRED AT HIS
 TIME.
  
  
 NOTE-
 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- OK.
  
 9- OK.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-11 Cont ID  
Sent By jgomez Date 2019-03-11 Time 16:03 Rev Time 0.00
Received By jgomez Date 2019-03-11 Time 10:14 Sent To  
Notes
2019-03-11 16:04:21NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 ORIGINAL COMMENT:
 1- REVISE DRAINAGE PLAN SHOWN ON SHEET C-1. BASED ON
 THE GRADE ELEVATIONS ON THE REAR OF THE LOT, IT LOOKS
 LIKE THE WATER IS BEING DIVERTED TO THE NEIGHBOR.
 REVISE AS REQUIRED SO WATER IS KEPT WITHIN THE LOT OR
 DIVERTED TO AN APPROVED COLLECTION POINT.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 REVISED DRAINAGE PLAN SHOWS SECTION C-C WHICH SHOWS A
 BERM WITH ONE OF THE SLOPES TOWARDS THE REAR PROPERTY.
 THEREFORE, DIVERTING THE WATER TOWARD THE REAR REAR
 PROPERTY. REVISE AS REQUIRED.
  
 2- OK
  
 3- SHEET D1: REVISE DESIGN CRITERIA SHOWN ON THE TOP
 MIDDLE OF THE SHEET:
 A) OK
  
 B)OK.
  
 4- OK
  
 5- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 PARTIALLY COMPLIED. PROVIDE CORRECT NAME OF CONTRACTOR.
  
 ORIGINAL COMMENT:
 B)ITEM #5 ON PAGE 1 OF 5 STATES THAT THIS IS NOT A
 WORST CASE SCENARIO BUT ON PAGE 2 OF 5 IT SHOWS THAT
 THE HOUSE WAS ROTATED 315 DEGREES. THIS IS
 CONTRADICTORY. THE ENERGY CALCULATIONS NEED TO BE DONE
 FOR THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C)PROVIDE WINDOWS AND DOORS DOCUMENTATION FROM
 MANUFACTURER SHOWING THE SHGC FACTOR AND U-FACTOR
 EFFICIENCIES SHOWN ON ITEM #7 ON PAGE 1 OF 5. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION. NOTE: THIS IS ONLY
 REQUIRED WHEN PERSON DOING THE CALCULATIONS IS NOT
 USING THE PROGRAM DEFAULT FACTORS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) CEILING R-VALUE INSULATION ON ITEM #10 DOESN'T MATCH
 PLANS. REVISE AS REQUITED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. ALSO, THE ATTIC IS NOT
 VENTED. PLANS SPECIFY FOAM INSULATION. SEE PLANS AND
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 E) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 F) PARTIALLY DONE. THE VENT RATIO WAS REVISED, BUT I
 APOLOGIZE BECAUSE THIS ITEM WAS OVERLOOKED. THERE IS NO
 VENTED ATTIC. SEE ITEM #5D ABOVE.
  
 ORIGINAL COMMENT:
 G) REVISE WINDOWS ORIENTATION AND AREA ON PAGE 3 OF 5
 TO MATCH ACTUAL ORIENTATION AND AREA SHOWN ON PLANS.
 NOTE: COORDINATE WITH ITEM #5(B) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. COORDINATE WITH ITEM #5(B) ABOVE.
  
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- OK.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) PRECAST LINTELS. NOTE: NOA 16-0126.03 SPECIFIED ON
 SHEET 3 OF 7 IS EXPIRED. REVISE AS REQUIRED ALSO. THERE
 IS NO NEED TO SPECIFY NOA ON DRAWINGS. JUST REVIEW IN
 WRITING THE ACTUAL PRODUCT APPROVAL.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. ONLY ONE COPY WAS
 SUBMITTED AND WAS VOID. NEED TWO COPIES. ALSO REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 C)GARAGE DOOR FLORIDA PRODUCT APPROVAL SUBMITTED. DOOR
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD. PROVIDE DOOR THAT MEETS THE
 CALCULATED DESIGN PRESSURES.
  
 NOTE-
 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- OK.
  
 9- OK.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By jgomez Date 2019-01-25 Time 17:04 Rev Time 0.00
Received By jgomez Date 2019-01-24 Time 17:58 Sent To  
Notes
2019-01-25 17:05:59NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- REVISE DRAINAGE PLAN SHOWN ON SHEET C-1. BASED ON
 THE GRADE ELEVATIONS ON THE REAR OF THE LOT, IT LOOKS
 LIKE THE WATER IS BEING DIVERTED TO THE NEIGHBOR.
 REVISE AS REQUIRED SO WATER IS KEPT WITHIN THE LOT OR
 DIVERTED TO AN APPROVED COLLECTION POINT.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 2- SHEET 1 OF 7: ENGINEER TO REVISE THE DESIGN
 PRESSURES SHOWN ON THE EXTERIOR ELEVATIONS. DESIGN
 PRESSURES SHOWN DON'T CORRESPOND TO EXPOSURE "D". ALSO,
 CLARIFY WHAT ARE THE "OPENING DESIGN PRESSURE, PSF"
 SHOWN ON THE UPPER RIGHT SIDE OF DRAWING FOR. THEY
 DON'T MATCH DESIGN PRESSURES SHOWN ON EXTERIOR
 ELEVATIONS EITHER.
  
 3- SHEET D1: REVISE DESIGN CRITERIA SHOWN ON THE TOP
 MIDDLE OF THE SHEET:
 A) THE EXPOSURE CATEGORY IS "D" NOT "C". NOTE:
 COORDINATE WITH ITEM #2 ABOVE. SEC. R301.2.1.4
 FBC-RESIDENTIAL.
  
 B)REVISE AND CLEARLY SPECIFY ALL THE LIVE AND DEAD
 LOADS ON THE ROOF TRUSSES. CLEARLY SPECIFY THE TOP AND
 BOTTOM CHORDS LIVE AND DEAD LOADS. NOTE: REVISE THE
 ATTIC LIVE LOAD (BOTTOM OF TRUSS CHORD). ACCORDING TO
 NOTES "B" AND "G" OF TABLE R301.5 FBC-RESIDENTIAL THE
 MIN. LIVE LOAD IS 20 POUNDS.
  
 4- FLOOR PLAN ON SHEET 2 OF 7 DOESN'T PROVIDE ANY
 SPECIFICATIONS FOR THE INSULATION IN THE WALLS BETWEEN
 THE GARAGE AND THE REST OF THE HOUSE. PROVIDE
 SPECIFICATIONS. NOTE: COORDINATE WITH THE ENERGY
 CALCULATIONS TO AVOID CONFLICT/DELAYS. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 5- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)ITEM #5 ON PAGE 1 OF 5 STATES THAT THIS IS NOT A
 WORST CASE SCENARIO BUT ON PAGE 2 OF 5 IT SHOWS THAT
 THE HOUSE WAS ROTATED 315 DEGREES. THIS IS
 CONTRADICTORY. THE ENERGY CALCULATIONS NEED TO BE DONE
 FOR THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE WINDOWS AND DOORS DOCUMENTATION FROM
 MANUFACTURER SHOWING THE SHGC FACTOR AND U-FACTOR
 EFFICIENCIES SHOWN ON ITEM #7 ON PAGE 1 OF 5. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION. NOTE: THIS IS ONLY
 REQUIRED WHEN PERSON DOING THE CALCULATIONS IS NOT
 USING THE PROGRAM DEFAULT FACTORS.
  
 D) CEILING R-VALUE INSULATION ON ITEM #10 DOESN'T MATCH
 PLANS. REVISE AS REQUITED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5. THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR, PROVIDE COMPLETE DOCUMENTATION SHOWING COMPLIANCE
 WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON
 SEC. R806.2 AND COORDINATE WITH ENGINEER OF RECORD SO
 PLANS ARE REVISED ACCORDINGLY.
  
 G) REVISE WINDOWS ORIENTATION AND AREA ON PAGE 3 OF 5
 TO MATCH ACTUAL ORIENTATION AND AREA SHOWN ON PLANS.
 NOTE: COORDINATE WITH ITEM #5(B) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- ALL PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED
 ONCE THE DESIGN PRESSURES ARE REVISED/CLARIFIED. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) PRECAST LINTELS. NOTE: NOA 16-0126.03 SPECIFIED ON
 SHEET 3 OF 7 IS EXPIRED. REVISE AS REQUIRED ALSO. THERE
 IS NO NEED TO SPECIFY NOA ON DRAWINGS. JUST REVIEW IN
 WRITING THE ACTUAL PRODUCT APPROVAL.
  
 8-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $264,094. THE
 PERMIT FEE BALANCE IS $4617.18.
  
 9- FOUNDATION PLAN (SHEET 4 OF 7) IS MISSING THE
 ENGINEER'S OF RECORD SEAL. CHAPTER 471 F.S.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-15 Cont ID  
Sent By ppetty Date 2019-03-15 Time 08:22 Rev Time 0.00
Received By ppetty Date 2019-03-15 Time 08:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-07 Cont ID  
Sent By jpearson Date 2019-01-07 Time 16:37 Rev Time 0.00
Received By jpearson Date 2019-01-07 Time 15:11 Sent To  
Notes
2019-01-07 16:37:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3606.3
 4. BLOCK NOTE STATES THAT THERE IS NO LOW VOLTAGE
 WIRING IN BUILDING, BUT THE LAUNDRY ROOM SHOWS A MEDIA
 BOX, AND ANOTHER NOTE STATES THERE IS CAT 5E WIRING FOR
 PHONES. PROVIDE CLARIFICATION AND/OR CORRECTION. WPB
 FBC 107.2.1
 5. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 8. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 9. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED(IF APPLICABLE) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2019-05-02 Cont ID  
Sent By rsklarew Date 2019-05-02 Time 12:03 Rev Time 0.00
Received By rsklarew Date 2019-05-02 Time 12:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-29 Cont ID  
Sent By jgomez Date 2019-04-29 Time 14:58 Rev Time 0.00
Received By jgomez Date 2019-04-25 Time 15:57 Sent To I
Notes
2019-04-26 15:57:21RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-28 Cont ID  
Sent By jgomez Date 2019-03-28 Time 14:00 Rev Time 0.00
Received By jgomez Date 2019-03-18 Time 14:39 Sent To  
Notes
2019-03-19 14:39:22RESUB ROUTED TO HMOSER'S OFFICE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-15 Cont ID  
Sent By cmontell Date 2019-03-15 Time 14:21 Rev Time 0.00
Received By cmontell Date 2019-03-15 Time 14:21 Sent To  
Notes
2019-02-22 13:33:07R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-25 Cont ID  
Sent By jgomez Date 2019-01-25 Time 17:13 Rev Time 0.00
Received By jgomez Date 2018-12-21 Time 15:42 Sent To I
Notes
2018-12-26 15:42:57R24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2019-05-01 Cont ID  
Sent By jduprey Date 2019-05-01 Time 16:18 Rev Time 0.00
Received By jduprey Date 2019-05-01 Time 16:12 Sent To  
Notes
2019-05-01 16:18:03MU-2019-013341-0000
 TOTAL PAID $9,766.49

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-03-28 Cont ID  
Sent By jgomez Date 2019-03-28 Time 13:59 Rev Time 0.00
Received By jgomez Date 2019-03-28 Time 13:59 Sent To  
Notes
2019-03-28 13:59:59IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-03-11 Cont ID  
Sent By jgomez Date 2019-03-11 Time 16:04 Rev Time 0.00
Received By jgomez Date 2019-03-11 Time 16:04 Sent To  
Notes
2019-03-11 16:05:31IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By jgomez Date 2019-01-25 Time 17:13 Rev Time 0.00
Received By jgomez Date 2019-01-25 Time 17:06 Sent To  
Notes
2019-01-25 17:07:30IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-04-29 Cont ID  
Sent By jgomez Date 2019-04-29 Time 14:57 Rev Time 0.00
Received By jgomez Date 2019-04-29 Time 14:57 Sent To  
Notes
2019-04-29 14:08:54REVISED LOAD CALCULATIONS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-25 Cont ID  
Sent By hmoser Date 2019-03-25 Time 10:26 Rev Time 0.00
Received By hmoser Date 2019-03-25 Time 10:07 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-15 Cont ID  
Sent By cmontell Date 2019-03-15 Time 14:21 Rev Time 0.00
Received By cmontell Date 2019-03-15 Time 14:20 Sent To I
Notes
2019-03-15 14:20:58MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED RETURN AIR IN MASTER BEDROOM PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL M1602.3 BALANCED RETURN
 AIR.
  
 2- CANNOT TAKE RETURN AIR FROM CLOSET PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL M1602.2 RETURN AIR
 OPENINGS.
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By cmontell Date 2019-01-04 Time 09:22 Rev Time  
Received By cmontell Date 2019-01-04 Time   Sent To  
Notes
2019-01-04 09:22:21MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED RETURN AIR IN MASTER BEDROOM PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL M1602.3 BALANCED RETURN
 AIR.
  
 2- CANNOT TAKE RETURN AIR FROM CLOSET PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL M1602.2 RETURN AIR
 OPENINGS.
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-12 Cont ID  
Sent By thunt Date 2019-03-12 Time 14:49 Rev Time 0.00
Received By thunt Date 2019-03-12 Time 14:49 Sent To  
Notes
2019-03-12 14:49:47PLUMBING PROVISO: (1)HAMMER ARRESTORS REQUIRED AT QUICK
 CLOSING
 VALVES FBC-R P2903.5.(2) BATH TUBS/ ROMAN TUBS SHALL BE
 TEMPERED
 BY A 1070 DEVICE TO 120F FBC-R P2713.3. (3) HOT WATER
 PIPING SHALL COMPLY
 WITH FBC-EFFICIENCY R403.5.3 AND BE INSULATED TO R-3
 VALUE. (4) SEWER CLEAN
 OUT SHALL BE 3"/ SAME SIZE AS THE PIPING IT SERVES.
 FBC-R P3005.2.5
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By jesmith Date 2019-01-15 Time 16:08 Rev Time 0.00
Received By jesmith Date 2019-01-15 Time 16:07 Sent To  
Notes
2019-01-15 16:08:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET 5 OF 7; PLUMBING RISER DIAGRAM
 A. PER FBC RES P3108.1, "EACH WET VENTED FIXTURE DRAIN
 SHALL CONNECT DIRECTLY TO THE HORIZONTAL WET VENT." IN
 THE CASE OF THE MASTER BATH, THE TUB DRAIN AND WATER
 CLOSET DRAIN SHALL NOT CONNECT TO EACHG OTHER BEFORE
 CONNECTING TO THE VENT.
 B. PER FBC RES P3104.4 AND 3104.5 THE DRY VENT SHALL
 RISE VERTICALLY ABOVE THE FLOOD LEVEL RIM OF HIGHEST
 TRAPPED FIXTURE BEING VENTED BEFORE OFFSETTING AND
 CONNECTING TO ANOTHER VENT. THE LAVATORY IN THE IN BATH
 #2 DOES NOT COMPLY.
 C. PER WPB FBC 107.2.1, INCLUDE THE WASTE AND VENT
 PIPING FOR THE HALF BATH ON THE PLUMBING RISER DIAGRAM.
 D. PER FBC P2717.2 SINK AND DISHWASHER, THE COMBINED
 DISCHARGE FROM A DISHWASHER AND A ONE- OR
 TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE
 DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN
 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER
 DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF
 THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT
 POSITION BEFORE CONNECTING TO THE HEAD OF THE
 FOOD-WASTE DISPOSER OR TO A WYE FITTING IN THE SINK
 TAILPIECE
 2. PER WPB FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By jgomez Date 2019-03-11 Time 16:06 Rev Time 0.00
Received By jgomez Date 2019-03-11 Time 16:06 Sent To  
Notes
2019-03-11 16:07:27SHINGLES CERTAIN TEED NOA 16-1109.18

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By jgomez Date 2019-01-25 Time 17:06 Rev Time 0.00
Received By jgomez Date 2019-01-25 Time 17:06 Sent To  
Notes
2019-01-25 17:06:51ALL PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE
 THE DESIGN PRESSURES ARE REVISED/CLARIFIED. SEC. R301.1
 FBC-RESIDENTIAL.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-05 Cont ID  
Sent By llouie Date 2019-03-05 Time   Rev Time 0.00
Received By llouie Date 2019-03-05 Time   Sent To  
Notes
2019-03-05 15:48:50- SEPERATE PERMIT REQUIRED FOR DRIVEWAY/WALKWAY AND
 LANDSCAPING PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY (C.O.).
  
 - CONDITIONAL APPROVAL FOR LANDSCAPING ATTACHED.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-09 Cont ID  
Sent By llouie Date 2019-01-09 Time   Rev Time  
Received By llouie Date 2019-01-09 Time   Sent To  
Notes
2019-01-09 08:40:18** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DISTANCE OF THE A/C UNIT COMPRESSOR IN
 THE SITE PLAN. PLEASE NOTE THAT ANY MECHANICAL
 EQUIPMENT CANNOT PROJECT MORE THAN 4 FT. INTO A
 SETBACK. [ZLDR S.94-305(B)(4)]
  
 2.) HOW HIGH IS THE STOOP ON THE SIDE OF THE PROPERTY?
 A STOOP LESS THAN 3 FT. ABOVE GRADE MAY ENCROACH INTO A
 SETBACK TO A POINT NO CLOSER THAN 2 FT. TO THE PROPERTY
 LINE. STOOPS GREATER THAN 3 FT. ABOVE GRADE SHALL
 COMPLY WITH THE SETBACK REQUIREMENTS FOR THE PRIMARY
 STRUCTURE. PLEASE DEMONSTRATE COMPLIANCE BY SHOWING
 ADDITIONAL DRAWINGS AND SETBACK DISTANCE FROM THE
 PROPERTY LINE(S). [ZLDR S.94-305(B)(7)]
  
 3.) SHOW DIMENSIONS FOR THE PROPOSED DRIVEWAY IN THE
 SITE PLAN. THE DRIVEWAY CANNOT EXCEED 20 FT. IN WIDTH.
 [ZLDR S.94-312(1)]
  
 4.) THE REQUIRED FRONT YARD (AREA WITHIN THE FIRST 25
 FT. OF SOUTH MANGONIA CIRCLE) SHALL HAVE A MINIMUM OF
 1,000 SQ. FT. OF LANDSCAPED AREA. PLEASE PROVIDE THE
 CALCULATIONS FOR THE FRONT YARD TO DEMONSTRATE
 COMPLIANCE. [ZLDR S.94-482]
  
 5.) THE CONDITIONAL APPROVAL FORM FOR LANDSCAPING AND
 IRRIGATION MUST BE COMPLETED PRIOR TO ZONING SIGN-OFF.
 [NOTE: THE CONDITIONAL APPROVAL FORM WAS SENT TO
 MICHAEL DIACZUN OF RJM CUSTOM HOMES TO PROVIDE TO THE
 OWNER OF THE PROPERTY ON 1/9/19 VIA EMAIL.]
  
  
 NOTES:
  
 * SEPARATE PERMIT REQUIRED FOR DRIVEWAY AND WALKWAYS,
 LANDSCAPING
  
 * A TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO
 THE REMOVAL OF ANY TREES/PALMS ON THE PROPERTY. PLEASE
 CONTACT THE CITY'S LANDSCAPE PLANNER, RAY CARANCI, AT
 (561) 822-1462.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  