Plan Review Details - Permit 18120817
Plan Review Stops For Permit 18120817
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-04-22 Cont ID  
Sent By jgomez Date 2021-04-22 Time 15:50 Rev Time 0.00
Received By jgomez Date 2021-04-22 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-03-17 Cont ID  
Sent By jgomez Date 2020-03-17 Time 13:20 Rev Time 0.00
Received By jgomez Date 2020-03-17 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-11-20 Cont ID  
Sent By jgomez Date 2019-11-20 Time 14:54 Rev Time 0.00
Received By jgomez Date 2019-11-20 Time 11:25 Sent To  
Notes
2019-11-20 14:54:53NOTE:
 BUILDING REVIEW WILL BE APPROVED WITH PROVISO ONCE THE
 OWNER SIGNS AND DATE THE ENERGY CALCULATIONS AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION TO
 ISSUE THE PERMIT.
  
  
 ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE REQUIRED
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1)ENGINEER TO REVISE WINDOWS DESIGN PRESSURES: DESIGN
 PRESSURES SHOWN FOR THE HORIZONTAL ROLLING WINDOWS
 SEEMS TO BE TOO LOW BASED ON THE BUILDING EXPOSURE.
 PROVIDE CALCULATIONS SHOWING WHY THEY ARE SO LOW. SEC.
 107.2.1.2 CITY AMENDMENTS. ALSO, CLARIFY WHY THE DESIGN
 PRESSURES FOR HORIZONTAL ROLLING WINDOW LOCATED IN
 BEDROOM #2 ARE THE SAME IF THIS WINDOW SEEMS TO BE
 LOCATED IN ZONE 5. (NOTE: ACCORDING TO FIGURE R301.2(7)
 THE MINIMUM DISTANCE FOR ZONE 5 IS 4'-0")
  
  
 2-PROVIDE PRODUCT APPROVAL (2 COPIES) REVIEWED BY
 ENGINEER OF RECORD FOR:
 A)GARAGE DOORS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD.
  
 B)HORIZONTAL SLIDING WINDOWS THAT WILL MEET THE REVISED
 DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
  
 C)SINGLE HUNG WINDOWS THAT WILL MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD FOR ALL
 SIZES SHOWN ON PLANS.
  
 D)EXTERIOR SWING DOORS. PROVIDE COMPLETE PRODUCT
 APPROVAL. MISSING THE DOOR DRAWINGS.
  
 3- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION
 SCHEDULE (SEE CITY SAMPLE) FOR REVIEW PRIOR TO
 INSPECTION TO AVOID CONFLICTS/DELAYS.
  
 4-ENGINEER TO PROVIDE CALCULATIONS FOR THE FASTENING OF
 THE GARAGE STRUCTURAL BUCK. SPECIFICATIONS SHOWN ON
 STRUCTURAL BUCK DETAIL ON SHEET S.3 DON'T MATCH
 SPECIFICATIONS SHOWN ON THE GARAGE DOOR PRODUCT
 APPROVAL AND THE STRUCTURAL BUCK IS ATTACHED TO FILLED
 CONCRETE BLOCK CELL NOT TO CONCRETE. SEC. 107.2.1.2
 CITY AMENDMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-21 Cont ID  
Sent By jgomez Date 2019-05-21 Time 15:20 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 10:55 Sent To  
Notes
2019-05-21 15:21:02NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 NOTE: DRAINAGE PLAN SHOWN ON SHEET SP-1 IS INCOMPLETE.
 IT DOESN'T SHOW THE PROPOSED DRAINAGE FOR ENTIRE LOT
 AND THE ELEVATIONS SHOWN ON SECTION/DETAILS A-A AND B-B
 ON SAME SHEET DON'T MATCH ELEVATIONS SHOWN ON THE
 REVISED SURVEY SUBMITTED. REVISE AS REQUIRED AND
 PROVIDE COMPLETE DRAINAGE PLAN.
  
 RESPONSE:
 ENGINEER OF RECORD WAS CHANGED. NO DRAINAGE PLAN
 SUBMITTED AT THIS TIME.
  
 ORIGINAL COMMENT.
 2- COMPONENT & CLADDING DESIGN PRESSURES SHOWN ON SHEET
 CVR AND DESIGN PRESSURES SHOWN ON SHEET A2 DON'T MATCH.
 IN ADDITION, IT LOOKS LIKE THE DESIGN PRESSURES ON
 SHEET CVR ARE GIVEN IN NOMINAL DESIGN WIND SPEEDS
 (ASD), WHILE THE DESIGN PRESSURES ON SHEET A2 ARE GIVEN
 IN ULTIMATE DESIGN WIND SPEEDS (VULT). REVISE AS
 REQUIRED TO MATCH AND PROVIDE ALL DESIGN PRESSURES IN
 NOMINAL WIND SPEEDS (ASD) AS REQUIRED BY SEC.
 R301.2.1.3 FBC-RESIDENTIAL. THIS WILL AVOID CONFLICTS
 ALSO.
  
 RESPONSE:
 A)ENGINEER OF RECORD WAS CHANGED.DESIGN PRESSURES SHOWN
 FOR THE HORIZONTAL ROLLING WINDOWS SEEMS TO BE TOO LOW
 BASED ON THE BUILDING EXPOSURE. PROVIDE CALCULATIONS
 SHOWING WHY THEY ARE SO LOW. SEC. 107.2.1.2 CITY
 AMENDMENTS. ALSO, CLARIFY WHY THE DESIGN PRESSURES FOR
 HORIZONTAL ROLLING WINDOW LOCATED IN BEDROOM #2 ARE THE
 SAME IF THIS WINDOW SEEMS TO BE LOCATED IN ZONE 5.
 (NOTE: ACCORDING TO FIGURE R301.2(7) THE MINIMUM
 DISTANCE FOR ZONE 5 IS 4'-0")
  
 B)NEW ENGINEER OF RECORD TO PROVIDE CALCULATIONS TO
 CLARIFY WHY THE DESIGN PRESSURES FOR THE HORIZONTAL
 ROLLING WINDOWS ARE DIFFERENT THAN DESIGN PRESSURES FOR
 THE SINGLE HUNG WINDOWS?. DESIGN PRESSURES ARE BASED ON
 EFFECTIVE WIND AREA NOT TYPE OF WINDOW. SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 C) DESIGN PRESSURES FOR OVERHEAD GARAGE DOOR ARE NOT
 LEGIBLE. REVISE AS REQUIRED AND COORDINATE WITH ITEMS
 @(A) AND 2(B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- REVISE DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS ON SHEET A1 AND A2 FOR LIVING
 ROOM WINDOW AND BEDROOM #2 WINDOW. THEY ARE LOCATED IN
 END ZONE "B" NOT INTERIOR ZONE "A". FIGURE R301.2(7)
 FBC-RESIDENTIAL REQUIRES 4-MIN FOR END ZONE. REVISE AS
 REQUIRED.
  
 RESPONSE:
 COORDINATE WITH RESPONSES TO ITEM #2 ABOVE.
  
 4- OK.
  
 5- OK.
  
 6- OK.
  
 7- OK.
  
 ORIGINAL COMMENT:
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 SIZE OF ATTIC ACCESS WAS NOT SPECIFIED. SPECIFY SIZE.
  
 9-OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
 16- OK.
  
 17- ENERGY CALCULATIONS SUBMITTED:
  
 ORIGINAL COMMENT:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. OWNER OR LEGALLY
 AUTHORIZED AGENT TO CERTIFY AT THE BOTTOM OF FORM.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT DONE AND NOW IS MISSING MORE INFORMATION LIKE
 PERMIT OFFICE, JURISDICTION NUMBER. PROVIDE COMPLETE
 INFORMATION.
  
 C) OK.
  
 ORIGINAL COMMENT:
 D) REVISE ITEM #9(B). THE MATERIAL OF ADJACENT WALL
 FRAME IS NOT WOOD. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT DONE.
  
 E)OK.
  
 ORIGINAL COMMENT:
 F)WINDOWS FRAME MATERIAL SPECIFIED ON PAGE 3 OF 4
 DOESN'T MATCH PLANS AND PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT DONE.
  
 NEW COMMENTS:
 G)NUMBER OF BEDROOMS SHOWN ON PAGE 1 OF 4 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 H)DUCTS R-VALUE SPECIFIED ON PAGE 1 OF 4 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I)NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 OF 4 NEED TO
 BE REVISED. COORDINATE WITH REVISE NUMBER OF BEDROOMS
 SHOWN ON PLANS. COORDINATE WITH ITEM #17(G) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 ORIGINAL COMMENT:
 18- PRODUCT APPROVALS WILL BE REVIEWED ONCE THE DESIGN
 PRESSURES ARE CLARIFIED. SEE COMMENT #2 ABOVE. NOTE:
 ENGINEER OF RECORD TO REVIEW AND APPROVE THEM PRIOR TO
 SUBMITTAL.
 NOTE: SHUTTERS NEED COMPLETE INSTALLATION SCHEDULE. SEE
 CITY SAMPLE.
  
 RESPONSE:
 DESIGN PRESSURES NEED TO BE REVISED AGAIN. SEE COMMENT
 #2.
 NOTE: IT LOOKS LIKE HORIZONTAL ROLLING WINDOWS FLORIDA
 PRODUCT APPROVAL FL14994-R4 SUBMITTED DON'T MEET THE
 REQUIRED DESIGN PRESSURES. SAME THING APPLIES FOR SOME
 SINGLE HUNG WINDOWS. SEE ALL WINDOW SIZES SPECIFIED ON
 PLANS AND DESIGN PRESSURES SHOWN ON THE PRODUCT
 APPROVAL PRIOR TO SUBMITTAL. ENGINEER TO REVIEW AND
 APPROVE PRIOR TO SUBMITTAL.
  
 19- OK.
  
 NEW COMMENTS:
 20- PROVIDE OVERHEAD GARAGE DOOR STRUCTURAL BUCK
 DETAIL. SEC. 301.2.1 FBC-RESIDENTIAL. PLANS DON'T SHOW
 ANY DETAIL.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By jgomez Date 2019-01-18 Time 17:40 Rev Time 0.00
Received By jgomez Date 2019-01-18 Time 09:52 Sent To  
Notes
2019-01-18 17:41:11NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 NOTE: DRAINAGE PLAN SHOWN ON SHEET SP-1 IS INCOMPLETE.
 IT DOESN'T SHOW THE PROPOSED DRAINAGE FOR ENTIRE LOT
 AND THE ELEVATIONS SHOWN ON SECTION/DETAILS A-A AND B-B
 ON SAME SHEET DON'T MATCH ELEVATIONS SHOWN ON THE
 REVISED SURVEY SUBMITTED. REVISE AS REQUIRED AND
 PROVIDE COMPLETE DRAINAGE PLAN.
  
 2- COMPONENT & CLADDING DESIGN PRESSURES SHOWN ON SHEET
 CVR AND DESIGN PRESSURES SHOWN ON SHEET A2 DON'T MATCH.
 IN ADDITION, IT LOOKS LIKE THE DESIGN PRESSURES ON
 SHEET CVR ARE GIVEN IN NOMINAL DESIGN WIND SPEEDS
 (ASD), WHILE THE DESIGN PRESSURES ON SHEET A2 ARE GIVEN
 IN ULTIMATE DESIGN WIND SPEEDS (VULT). REVISE AS
 REQUIRED TO MATCH AND PROVIDE ALL DESIGN PRESSURES IN
 NOMINAL WIND SPEEDS (ASD) AS REQUIRED BY SEC.
 R301.2.1.3 FBC-RESIDENTIAL. THIS WILL AVOID CONFLICTS
 ALSO.
  
 3- REVISE DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS ON SHEET A1 AND A2 FOR LIVING
 ROOM WINDOW AND BEDROOM #2 WINDOW. THEY ARE LOCATED IN
 END ZONE "B" NOT INTERIOR ZONE "A". FIGURE R301.2(7)
 FBC-RESIDENTIAL REQUIRES 4-MIN FOR END ZONE. REVISE AS
 REQUIRED.
  
 4- MASTER BEDROOM EMERGENCY ESCAPE AND RESCUE OPENING
 IS NOT CLEAR. INFORMATION SHOWN ON DOOR SCHEDULE, FLOOR
 PLAN AND PROPOSED SOUTH ELEVATION DON'T MATCH. REVISE
 AS REQUIRED TO COMPLY WITH SEC. R310.2 FBC-RESIDENTIAL.
  
 5- IT LOOKS LIKE WINDOWS FOR BEDROOM #2, #3 AND #4
 DON'T COMPLY WITH THE EMERGENCY ESCAPE AND RESCUE
 OPENING AS REQUIRED BY SEC. R310.2.1 FBC-RESIDENTIAL.
 IT LOOKS LIKE A 47.5" X 47.5" HORIZONTAL SLIDING WINDOW
 DOESN'T PROVIDE THE 20" MIN. CLEAR WIDTH OPENING.
 PROVIDE WINDOW MANUFACTURER'S CUT SHEETS SHOWING THAT
 PROPOSED WINDOW SIZE WILL MEET ALL THE EGRESS
 REQUIREMENTS.
  
 6- PROVIDE CARBON MONOXIDE ALARMS IN THE LOCATIONS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 7- PROVIDE DOOR THAT PROVIDES A 29" CLEAR DOOR OPENING
 IN THE BATHROOM WITH MAXIMUM POSSIBLY PRIVACY.
 AS REQUIRED BY SEC. R320 FBC-RESIDENTIAL. NOTE: IT
 LOOKS LIKE THE MASTER BATHROOM IS THE BATHROOM WITH
 MAXIMUM PRIVACY. THE DOOR SIZE SPECIFIED IN THIS
 BATHROOM DOESN'T PROVIDE A 29" CLEAR OPENING. REVISE AS
 REQUIRED.
  
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 9-PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO THE
 INTERIOR OF THE HOUSE SHOWING COMPLIANCE WITH THE FIRE
 RESISTANT REQUIREMENTS OF SEC. R302.5 FBC-RESIDENTIAL.
  
 10- ALUMINUM HINGED COLONIAL SHUTTER DETAILS ON SHEET
 A2. PROVIDE ATTACHMENT DETAIL/SPECIFICATIONS THAT MATCH
 PROPOSED INSTALLATION AND LOCATION. ALSO, CLARIFY IF
 THESE SHUTTERS ARE GOING TO BE FIXED OR OPERABLE.
 PROVIDE PRODUCT APPROVAL IF OPERABLE SHUTTERS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 11- TYPICAL 1 STORY WALL SECTION A/A3:
 A) ROOF SHEATHING NAILING SPECIFICATIONS ARE NOT CLEAR.
 REVISE AS REQUIRED. SEC. R803.2.3.1 FBC-RESIDENTIAL.
  
 B) REVISE "EXTERIOR FINISH GRADE NOTE". NEED 12" MIN
 NOT 8". SEC. R403.1.4 FBC-RESIDENTIAL.
 NOTE: REVISE DIMENSIONS ON EXTERIOR FOOTING
 ACCORDINGLY. NOTE: COORDINATE WITH SIZE OF FOOTING
 SHOWN ON SHEET S1.
  
 C) SHOW THE 6" CLEARANCE BETWEEN FINISH GRADE AND
 EXTERIOR WALL COVERING AS REQUIRED BY SEC. R318.7
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM ABOVE.
  
 12- REVISE ALL WINDOWS AND DOORS STRUCTURAL BUCK
 DETAILS ON SHEET A3 TO COMPLY WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. NOTE: BEVELED BUCKS ARE NOT ALLOWED
 AND STRUCTURAL BUCKS NEED TO PROVIDE FULL SUPPORT TO
 THE DOOR AND WINDOW FRAME.
  
 13- FOUNDATION PLAN SHOWN ON SHEET S1 AND FLOOR PLAN
 SHOWN ON SHEET A1 DON'T MATCH. REVISE AS REQUIRED.
 NOTE: LAYOUT OF BATHROOMS DON'T MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 14- ROOF SHEATHING SPECIFICATIONS ON "ROOF SHEATHING
 NOTE", "DIAPHRAGM SCHEDULE", "NAILING ZONES" AND
 ""FASTENER SCHEDULE" ON SAME SHEET S2 DON'T MATCH.
 REVISE AS REQUIRED TO MATCH. SEE SEC. R803.2.3.1
 FBC-RESIDENTIAL AND REVISE AS REQUIRED TO MATCH.
  
 15- REVISE "DEPT. PRODUCT SUBMITTAL AFFIDAVIT" ON SHEET
 CVR. COORDINATE PRODUCT APPROVAL OR NOA WITH ONES
 SUBMITTED. CLARIFY/REVISE THE "ATTACHMENT METHOD
 REQUIRED TO MAKE SURE IT APPLIES TO SPECIFIC PRODUCT.
 CHECK EXPIRATION DATES, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 16- ENGINEER OF RECORD TO SPECIFY INSULATION BETWEEN
 GARAGE AREA AND A/C AREA AS REQUIRED BY SEC. R103.2
 FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH THE
 ENERGY CALCULATION TO AVOID CONFLICTS/DELAYS.
  
 17- ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING?S OWNER, THE OWNER?S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) REVISE ITEM #9(A). THE EXTERIOR WALL INSULATION
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE ITEM #9(B). THE MATERIAL OF ADJACENT WALL
 FRAME IS NOT WOOD. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE DOORS INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED. WHICH ONE IS THE INSULATED DOOR
 AND WHICH ONE IS THE WOOD DOOR? ALSO, SEE PLANS FOR
 ORIENTATION OF DOORS. DOORS WITH GLAZING NEED TO BE
 CONSIDERED IN THE GLAZING AREA. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)WINDOWS FRAME MATERIAL DOESN'T MATCH PLANS AND
 PRODUCT APPROVALS SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THE
 U-FACTOR AND SHGC SPECIFIED ON ITEM #7 AS REQUIRED BY
 SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 18- PRODUCT APPROVALS WILL BE REVIEWED ONCE THE DESIGN
 PRESSURES ARE CLARIFIED. SEE COMMENT #2 ABOVE. NOTE:
 ENGINEER OF RECROD TO REVIEW AND APPROVE THEM PRIOR TO
 SUBMITTAL.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $232,590. THE
 PERMIT FEE BALANCE IS $4618.61.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-04-25 Cont ID  
Sent By jleahy Date 2021-04-25 Time 16:23 Rev Time 0.00
Received By jleahy Date 2021-04-25 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2020-03-20 Cont ID  
Sent By jpearson Date 2020-03-20 Time 11:02 Rev Time 0.00
Received By jpearson Date 2020-03-20 Time 11:02 Sent To  
Notes
2020-03-20 11:02:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED(AND SEALED WHERE
 APPLICABLE) BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL SIGNATURE ON A PAPER PLAN IS NOT ACCEPTABLE.
 THE PLAN APPEARS TO BE SIGNED BY HUMBERTO DIAZ. IS THIS
 AN ENGINEER OR ARCHITECT DESIGNING THESE PLANS? PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.1; FS
 471/481 (4TH REVIEW: NOT ADDRESSED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-11-20 Cont ID  
Sent By jpearson Date 2019-11-20 Time 08:02 Rev Time 0.00
Received By jpearson Date 2019-11-20 Time 07:03 Sent To  
Notes
2019-11-20 08:02:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED(AND SEALED WHERE
 APPLICABLE) BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL SIGNATURE ON A PAPER PLAN IS NOT ACCEPTABLE.
 THE PLAN APPEARS TO BE SIGNED BY HUMBERTO DIAZ. IS THIS
 AN ENGINEER OR ARCHITECT DESIGNING THESE PLANS? PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-06 Cont ID  
Sent By ppetty Date 2019-05-06 Time 11:58 Rev Time 0.00
Received By ppetty Date 2019-05-06 Time 11:58 Sent To  
Notes
2019-05-06 11:58:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2.OK
 3. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI AND AFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9), 210.12; FBC RE E3902
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-07 Cont ID  
Sent By jpearson Date 2019-01-07 Time 14:57 Rev Time 0.00
Received By jpearson Date 2019-01-07 Time 10:34 Sent To  
Notes
2019-01-07 14:57:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PANEL SCHEDULE, CIRCUIT 13, SHOWS KITCHEN
 RECEPTACLES ON A 15 AMP CIRCUIT. ALL RECEPTACLES IN
 KITCHEN AREA ARE REQUIRED TO BE ON A 20 AMP SMALL
 APPLIANCE CIRCUIT. EACH SMALL APPLIANCE CIRCUIT SHOULD
 BE INCLUDED IN LOAD CALCULATION AS 1500 VA. PROVIDE
 CORRECTION. NEC 210.11(C), 210.52(B), 220; FBC RE
 E3602.2, E3703.2
 3. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI AND AFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9), 210.12; FBC RE E3902
 4. PANEL SCHEDULE, CIRCUIT 30, SHOWS GUEST BATH GFI ON
 15 AMP CIRCUIT. ALL BATHROOM GFCI RECEPTACLE OUTLETS
 MUST BE ON A 20 AMP CIRCUIT. PROVIDE CORRECTION. NEC
 210.11(C), FBC RE E3703.4
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 7. RISER DIAGRAM QUOTES THE 2011 NEC FOR INSTALLATION
 OF THE INTERSYSTEM BONDING TERMINATION POINT. THE 2011
 NEC IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-04-25 Cont ID  
Sent By jleahy Date 2021-04-25 Time 16:23 Rev Time 0.00
Received By jleahy Date 2021-04-16 Time 10:25 Sent To  
Notes
2021-04-22 10:26:43CHANGED INCOMING DATE TO THE DATE IT WAS RESUBMITTED
 AND APPROVED BY ROBERT BROWN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-24 Cont ID  
Sent By lmarchan Date 2020-03-24 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2020-02-28 Time 13:43 Sent To  
Notes
2020-03-02 13:43:41R34

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-20 Cont ID  
Sent By jgomez Date 2019-11-20 Time 14:56 Rev Time 0.00
Received By jgomez Date 2019-10-31 Time 14:15 Sent To I
Notes
2019-11-01 14:15:27R29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-21 Cont ID  
Sent By jgomez Date 2019-05-21 Time 15:21 Rev Time 0.00
Received By jgomez Date 2019-05-02 Time 16:14 Sent To I
Notes
2019-05-02 16:14:56R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-18 Cont ID  
Sent By jgomez Date 2019-01-18 Time 17:43 Rev Time 0.00
Received By jgomez Date 2018-12-21 Time 15:45 Sent To I
Notes
2018-12-26 15:45:45R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2020-03-17 Cont ID  
Sent By jgomez Date 2020-03-17 Time 10:52 Rev Time 0.00
Received By jgomez Date 2020-03-17 Time 10:48 Sent To  
Notes
2020-03-17 10:53:35$180.65 PAID. MU-2020-000479.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-11-20 Cont ID  
Sent By jgomez Date 2019-11-20 Time 14:55 Rev Time 0.00
Received By jgomez Date 2019-11-20 Time 14:55 Sent To  
Notes
2019-11-20 14:56:36IMPACT FEES -
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-05-21 Cont ID  
Sent By jgomez Date 2019-05-21 Time 15:18 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 15:18 Sent To  
Notes
2019-05-21 15:19:26IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By jgomez Date 2019-01-18 Time 17:42 Rev Time 0.00
Received By jgomez Date 2019-01-18 Time 17:41 Sent To  
Notes
2019-01-18 17:42:39IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-10 Cont ID  
Sent By cmontell Date 2019-05-10 Time 14:24 Rev Time 0.00
Received By cmontell Date 2019-05-10 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-01-04 Cont ID  
Sent By cmontell Date 2019-01-04 Time 08:57 Rev Time 0.00
Received By cmontell Date 2019-01-04 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-06 Cont ID  
Sent By thunt Date 2019-05-06 Time 14:58 Rev Time 0.00
Received By thunt Date 2019-05-06 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By jesmith Date 2019-01-15 Time 15:41 Rev Time 0.00
Received By jesmith Date 2019-01-15 Time 15:13 Sent To  
Notes
2019-01-15 15:41:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-1; PLUMBING RISER
 A. PER FBC RES P3108.1, "EACH WET VENTED FIXTURE DRAIN
 SHALL CONNECT DIRECTLY TO THE HORIZONTAL WET VENT." IN
 THE CASE OF THE MASTER BATH, CONNECT THE SHOWER DRAIN
 TO THE HORIZONTAL WET VENT DOWN STREAM OF THE VERTICAL
 PORTION OF THE WET VENT. IN THE CASE OF BATH #2,
 CONNECT THE WATER CLOSET TO THE HORIZONTAL WET VENT
 DOWNSTREAM FROM THE VERTICAL PORTION OF THE WET VENT.
 B. THE HORIZONTAL BRANCH SERVICING THE CLOTHES WASHER
 SHALL BE 3" WHEN VENTED BY A STUDOR AIR ADMITTANCE
 VALVE IN ACCORDANCE WITH THE MANUFACTURER'S DESIGN
 CRITERIA AND INSTALLATION INSTRUCTIONS.
 2. RE: PLAN SHEET P-1; WATER HEATER DETAIL
 A. PROVIDE PAN WITH DRAIN IN ACCORDANCE WITH FBC RES
 P2801.6, P2801.6.1 AND P2801.6.2.
 B. PROVIDE THERMAL EXPANSION CONTROL DEVICE IN COLD
 WATER SUPPLY TO WATER HEATER PER FBC RES P2903.4
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By jgomez Date 2019-05-21 Time 15:19 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 15:19 Sent To  
Notes
2019-05-21 15:20:06SHINGLES NOA 16-0811.11

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By jgomez Date 2019-01-18 Time 17:42 Rev Time 0.00
Received By jgomez Date 2019-01-18 Time 17:42 Sent To  
Notes
2019-01-18 17:43:09NEED SHINGLES PRODUCT APPROVAL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-19 Cont ID  
Sent By medwards Date 2021-04-19 Time 17:12 Rev Time 0.00
Received By medwards Date 2021-04-19 Time 17:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-03-23 Cont ID  
Sent By rfalcone Date 2020-03-23 Time 16:42 Rev Time 0.00
Received By rfalcone Date 2020-03-23 Time 16:42 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2019-11-12 Cont ID  
Sent By rfalcone Date 2019-11-12 Time 14:49 Rev Time 0.00
Received By rfalcone Date 2019-11-08 Time 16:21 Sent To I
Notes
2019-11-12 14:54:0811/12/19 FAILED.
  
 PURSUANT ZLDR SEC. 94-72(A)(2)(A), THE REQUIRED FRONT
 SETBACK IS 25 FEET. PLEASE REVISE THE PLANS TO COMPLY
 WITH THE ZONING REGULATIONS.
  
 PRIOR TO ZONING APPROVAL AND ISSUANCE OF A CERTIFICATE
 OF OCCUPANCY, ONE OF THE FOLLOWING CONDITIONS SHALL BE
 ADDRESSED:
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
 3. A CONDITIONAL APPROVAL FORM FOR THE LANDSCAPE PERMIT
 AND IRRIGATION PERMIT. (SEE ATTACHED PDF).
 A.THE SIGNATURE OF THE OWNER AND CONTRACTOR ARE
 REQUIRED ON THIS FORM. ONCE IT IS NOTARIZED, IT CAN BE
 DROPPED OFF TO ME IN THE PLANNING AND ZONING DEPARTMENT
 FOR SIGNATURES FORM THE ZONING AND BUILDING OFFICIAL.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME
 NTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-15 Cont ID  
Sent By mcruz Date 2019-05-15 Time 15:20 Rev Time 0.00
Received By mcruz Date 2019-05-15 Time 15:20 Sent To PC
Notes
2019-05-15 15:20:12ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 REPEAT COMMENT:
 1) NEW CONSTRUCTION APPLICANTS MUST SUBMIT A SEPARATE
 PERMIT FOR LANDSCAPING. PLEASE REMOVE LANDSCAPE PLANS
 IN CURRENT PERMIT AND SUBMIT SEPARATELY. ONCE SEPARATE
 LANDSCAPE PERMIT IS PULLED, THIS EXISTING PERMIT CAN
 PASS ZONING REVIEW. PLEASE DIRECT LANDSCAPE QUESTIONS
 TO RAY CARANCI, LANDSCAPE PLANNER AT 822-1462.
  
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-09 Cont ID  
Sent By mcruz Date 2019-01-09 Time 14:28 Rev Time 0.00
Received By mcruz Date 2019-01-09 Time 14:15 Sent To PC
Notes
2019-01-09 14:28:19ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) NEW CONSTRUCTION APPLICANTS MUST SUBMIT A SEPARATE
 PERMIT FOR LANDSCAPING. PLEASE REMOVE LANDSCAPE PLANS
 IN CURRENT PERMIT AND SUBMIT SEPARATELY. ONCE SEPARATE
 LANDSCAPE PERMIT IS PULLED, THIS EXISTING PERMIT CAN
 PASS ZONING REVIEW. PLEASE DIRECT LANDSCAPE QUESTIONS
 TO RAY CARANCI, LANDSCAPE PLANNER AT 822-1462.
  
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  