Plan Review Details - Permit 18120801
Plan Review Stops For Permit 18120801
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-15 Cont ID  
Sent By pvalenti Date 2019-02-15 Time 11:30 Rev Time 0.00
Received By pvalenti Date 2019-02-15 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-12 Cont ID  
Sent By pvalenti Date 2019-02-12 Time 16:52 Rev Time 0.00
Received By pvalenti Date 2019-02-12 Time 16:52 Sent To  
Notes
2019-02-12 16:55:54PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING APPROVED WITH PROVISO:
  
 PRIOR TO INSPECTION PLEASE PROVIDE:
  
 1. WELD PROCEDURE SPECIFICATIONS AND WELDERS
 CERTIFICATIONS.
  
 2. STEEL SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-11 Cont ID  
Sent By pvalenti Date 2019-02-11 Time 17:11 Rev Time 0.00
Received By pvalenti Date 2019-02-11 Time 15:54 Sent To  
Notes
2019-02-11 17:22:34****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
  
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. MISSING INFORMATION FOR THE TUBE STEEL BEAM
  CONNECTIONS AT ROOF EXPANSION JOINTS FOUND ON PAGES
  (CEA 161) AND (CES 101). (COMPLIED)
  
 2. WE NEED TO REVIEW/AUDIT THE APPROVED STEEL SHOP
 DRAWINGS. (NOT COMPLIED, PLEASE SUBMIT STEEL SHOP
 DRAWINGS)
  
 3. WE NEED AN APPROVED CLARIFICATION THAT THE WIND LOAD
  DESIGN (RISK CATEGORY 2) AS INDICATED ON PAGE (CES
 001)
  IS ACCURATE. IT APPEARS THAT THIS MAY ACTUALLY BE A
  RISK CATEGORY 3. (COMPLIED)
  
 4. WE NEED TO REVIEW/AUDIT THE STEEL ERECTORS WELD
  PROCEDURE SPECIFICATIONS AS PER THE FBC B REFERENCED
  STANDARDS AND THE REQUIREMENTS INDICATED ON PAGE (CES
 004) REFERENCING THE AMERICAN WELDING SOCIETY. (NOT
 COMPLIED, PLEASE SUBMIT THE WELD PROCEDURE
 SPECIFICATIONS)
  
  
  
  PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
  RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-28 Cont ID  
Sent By pvalenti Date 2019-01-28 Time 15:22 Rev Time 0.00
Received By pvalenti Date 2019-01-28 Time 14:34 Sent To  
Notes
2019-01-28 15:16:49****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. MISSING INFORMATION FOR THE TUBE STEEL BEAM
 CONNECTIONS AT ROOF EXPANSION JOINTS FOUND ON PAGES
 (CEA 161) AND (CES 101).
 2. WE NEED TO REVIEW/AUDIT THE APPROVED STEEL SHOP
 DRAWINGS.
 3. WE NEED AN APPROVED CLARIFICATION THAT THE WIND LOAD
 DESIGN (RISK CATEGORY 2) AS INDICATED ON PAGE (CES 001)
 IS ACCURATE. IT APPEARS THAT THIS MAY ACTUALLY BE A
 RISK CATEGORY 3.
 4. WE NEED TO REVIEW/AUDIT THE STEEL ERECTORS WELD
 PROCEDURE SPECIFICATIONS AS PER THE FBC B REFERENCED
 STANDARDS AND THE REQUIREMENTS INDICATED ON PAGE (CES
 004) REFERENCING THE AMERICAN WELDING SOCIETY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-01-21 Cont ID  
Sent By jpearson Date 2019-01-21 Time 08:30 Rev Time 0.00
Received By jpearson Date 2019-01-21 Time 08:25 Sent To  
Notes
2019-01-21 08:25:06PRIVATE PROVIDER REVIEW CONFIRMED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-09 Cont ID  
Sent By pleduc Date 2019-01-09 Time   Rev Time 0.00
Received By pleduc Date 2019-01-07 Time 12:03 Sent To  
Notes
2019-01-09 15:56:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FIRE SPRINKLERS ARE INDICATED AND SHOP DRAWINGS ARE
 REQUIRED UNDER SEPARATE PERMIT.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-08 Cont ID  
Sent By lmarchan Date 2019-03-08 Time 11:52 Rev Time 0.00
Received By lmarchan Date 2019-02-22 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-21 Cont ID  
Sent By lmarchan Date 2019-02-21 Time 15:33 Rev Time 0.00
Received By lmarchan Date 2019-02-14 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-13 Cont ID  
Sent By lmarchan Date 2019-02-13 Time 08:01 Rev Time 0.00
Received By lmarchan Date 2019-02-07 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-28 Cont ID  
Sent By pvalenti Date 2019-01-28 Time 15:18 Rev Time 0.00
Received By pvalenti Date 2019-01-04 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-22 Cont ID  
Sent By gjohnson Date 2019-01-22 Time 10:19 Rev Time 0.00
Received By gjohnson Date 2019-01-22 Time 10:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By pvalenti Date 2019-02-15 Time 11:30 Rev Time 0.00
Received By pvalenti Date 2019-02-15 Time 11:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-01-21 Cont ID  
Sent By jpearson Date 2019-01-21 Time 08:24 Rev Time 0.00
Received By jpearson Date 2019-01-21 Time 08:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2019-03-07 Cont ID  
Sent By eschneid Date 2019-03-07 Time 16:28 Rev Time 0.25
Received By eschneid Date 2019-03-07 Time 16:15 Sent To PC
Notes
2019-03-07 16:29:03THE CANOPY LAYOUT DOES NOT MATCH THE CANOPY APPROVED BY
 THE CITY COMMISSION. THE COLUMNS ARE NOT IN THE SAME
 LOCATIONS; THEREFORE, THE CANOPY IS LARGER. A MINOR
 AMENDMENT SHOWING THE FINAL CONDITIONS IS REQUIRED
 PRIOR TO C.O.

Review Stop Z ZONING
Rev No 3 Status F Date 2019-02-21 Cont ID  
Sent By eschneid Date 2019-02-21 Time 15:23 Rev Time 0.25
Received By eschneid Date 2019-02-21 Time 14:49 Sent To  
Notes
2019-02-21 15:27:33FAILED
  
 1) REPEAT COMMENT: THE TYPICAL CANOPY COLUMN -
 ELEVATION, DETAIL 7 ON SHEET CEA 160 DOES NOT MATCH THE
 COLUMNS SHOWN ON CEA 150. DETAIL 7 FROM SHEET CEA160
 SHOWS THE NARROW BANDS AND THE BASE AS RUBY GRANITE AND
 THE WIDER BANDS AS JERUSALEM STONE. SHEET CEA150 SHOWS
 THE NARROW BANDS AS AE35, JERUSALEM STONE ON THE
 LEGEND, AND THE WIDER BANDS AS AE36, RUBY GRANITE ON
 THE LEGEND. ALL FOUR OF THE CANOPY ELEVATION DRAWINGS
 SHOW THIS SAME LABELING OF THE NARROW AND WIDE BANDS
 AND NONE OF THE ELEVATION DRAWINGS CALL OUT THE BASE
 MATERIAL. ALL PLANS MUST SHOW THE SAME CONDITIONS.
  
  
 CONDITION: THE CANOPY LAYOUT DOES NOT MATCH THE CANOPY
 APPROVED BY THE CITY COMMISSION. THE COLUMNS ARE NOT IN
 THE SAME LOCATIONS; THEREFORE, THE CANOPY IS LARGER. A
 MINOR AMENDMENT SHOWING THE FINAL CONDITIONS IS
 REQUIRED PRIOR TO C.O.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-02-12 Cont ID  
Sent By eschneid Date 2019-02-12 Time 16:57 Rev Time 0.25
Received By eschneid Date 2019-02-12 Time 16:57 Sent To  
Notes
2019-02-12 17:12:59FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE TYPICAL CANOPY COLUMN -
 ELEVATION, DETAIL 7 ON SHEET CEA 160 DOES NOT MATCH THE
 COLUMNS SHOWN ON CEA 150. ***** ALL PLANS MUST SHOW THE
 SAME CONDITIONS, SO IF DETAIL DETAIL 7 ON SHEET CEA 160
 IS THE CORRECT INSTALLATION, THEN THE COLUMNS, WITH THE
 CORRESPONDING LABELS, ON SHEET CEA 150 NEED TO BE
 CORRECTED SO THAT ALL PLANS SHOW THE SAME CONDITIONS.
 *****
  
 CONDITION: THE CANOPY LAYOUT DOES NOT MATCH THE CANOPY
 APPROVED BY THE CITY COMMISSION. THE COLUMNS ARE NOT IN
 THE SAME LOCATIONS; THEREFORE, THE CANOPY IS LARGER. A
 MINOR AMENDMENT SHOWING THE FINAL CONDITIONS IS
 REQUIRED PRIOR TO C.O.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-24 Cont ID  
Sent By eschneid Date 2019-01-24 Time 14:25 Rev Time 0.50
Received By eschneid Date 2019-01-24 Time 13:54 Sent To  
Notes
2019-01-24 14:25:18FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) THE CANOPY LAYOUT DOES NOT MATCH THE CANOPY APPROVED
 BY THE CITY COMMISSION. THE COLUMNS ARE NOT IN THE SAME
 LOCATIONS; THEREFORE, THE CANOPY IS LARGER. A MINOR
 AMENDMENT SHOWING THE FINAL CONDITIONS IS REQUIRED
 PRIOR TO C.O.
  
 2) PROVIDE THE SITE PLAN THAT SHOWS THE ACCURATE
 SETBACK FROM SAPODILLA AVENUE. PLEASE ENSURE THAT THE
 CHANGED SIZE, REVERENCED IN COMMENT NO. 1, ABOVE, HAVE
 BEEN FACTORED IN ON THE SITE PLAN WITH THE SETBACKS.
  
 3) THE TYPICAL CANOPY COLUMN - ELEVATION, DETAIL 7 ON
 SHEET CEA 160 DOES NOT MATCH THE COLUMNS SHOWN ON CEA
 150.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]