| 2018-12-27 14:39:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | |
| | 1) THERE IS AN INDICATION OF THE ACCESS PANEL LOCATION |
| | TO BE INSTALLED IN THE ELEVATOR CONTROL ROOM. |
| | |
| | THERE SHOULD BE NO EQUIPMENT THAT IS NOT INVOLVED WITH |
| | ELEVATOR CONTROL INSTALLED WITHIN THE ELEVATOR CONTROL |
| | ROOM. |
| | |
| | PLEASE REFER TO THE ELEVATOR COMPANY/INSTALLER FOR |
| | APPLICABLILITY. |
| | |
| | PLEASE REVIEW AND PROVIDE AN ALTERNATIVE LOCATION. |
| | |
| | |
| | |
| | 2) THERE IS A SPEC SHEET FOR REQUEST TO EXIT SENSOR |
| | WIRE, HOWEVER, THER IS NO REQUEST TO EXIT DEVICE |
| | INDICATED ON THE PLAN SHEET. |
| | |
| | PLEASE REVIEW AND PROVIDE CLARIFICATIONS OR CORRECT. |
| | |
| | |
| | |
| | 3) THE PROVIDED SPEC SHEETS INDICATE THE 17532 PROJECT |
| | AS PBC RADIO TOWER ACCESS CONTROL. IS THIS ACCURATE? |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE CLARIFICATION. |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF FREE EGRESS AND/OR |
| | COMPLAINCE WITH THE APPLICABLE REQUIRMENTS OF NFPA 101, |
| | CHAPER 7 MEANS OF EGRESS. |
| | |
| | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| | ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 5) THERE ARE NO INDICATIONS ON THE PLAN SHEET OF THE |
| | LOCATION OF THE ROOM, ROOM # AND/OR FLOOR LEVEL. |
| | |
| | PLEASE REVIEW AND PROVIDE ACCURATE LOCATIONAL |
| | INFORMATION OF THE PROJECT ROOM. |
| | |
| | |
| | |
| | 6) IS THERE A KNOX BOX PROVIDED WITH THIS BUILDING? |
| | |
| | WILL A CARD READER BE PROVIDED WITHIN THE KNOX BOX TO |
| | THIS ROOM? |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NNOTE. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |