Plan Review Details - Permit 18120793
Plan Review Stops For Permit 18120793
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By jleahy Date 2019-01-23 Time 15:37 Rev Time 0.00
Received By jleahy Date 2019-01-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jleahy Date 2019-01-03 Time 12:26 Rev Time 0.00
Received By jleahy Date 2019-01-03 Time 12:26 Sent To  
Notes
2019-01-03 12:27:05FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLANS NEED TO BE SIGNED BY CONTRACTOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-17 Cont ID  
Sent By pleduc Date 2019-01-17 Time   Rev Time 0.00
Received By pleduc Date 2019-01-17 Time 15:52 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-27 Cont ID  
Sent By pleduc Date 2018-12-27 Time   Rev Time 0.00
Received By pleduc Date 2018-12-27 Time 13:59 Sent To E
Notes
2018-12-27 14:08:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS A SPEC SHEET FOR REQUEST TO EXIT SENSOR
 WIRE, HOWEVER, THER IS NO REQUEST TO EXIT DEVICE
 INDICATED ON THE PLAN SHEET.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATIONS OR CORRECT.
  
  
 2) THERE ARE NO INDICATIONS OF FREE EGRESS AND/OR
 COMPLAINCE WITH THE APPLICABLE REQUIRMENTS OF NFPA 101,
 CHAPER 7 MEANS OF EGRESS.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 COMPLIANCE.
  
  
  
 3) IS THERE A KNOX BOX PROVIDED WITH THIS BUILDING?
  
 WILL A CARD READER BE PROVIDED WITHIN THE KNOX BOX?
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NNOTE.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-23 Cont ID  
Sent By jleahy Date 2019-01-23 Time 15:37 Rev Time 0.00
Received By jleahy Date 2019-01-15 Time 15:27 Sent To  
Notes
2019-01-16 15:27:27RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-03 Cont ID  
Sent By jleahy Date 2019-01-03 Time 12:50 Rev Time 0.00
Received By jleahy Date 2018-12-21 Time 14:24 Sent To  
Notes
2018-12-26 14:24:44ROUTED TO FIRE INBOX