| 2019-01-02 13:06:12 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18120758 |
| | ADD: 250 S AUSTRALIAN AVE/ 17TH & 18TH FLOORS/ DEMO |
| | ONLY |
| | CONT: TURNER CONSTRUCTION |
| | TEL: 786-621-9000 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 02/2019 |
| | ACTION: DENIED |
| | |
| | 1) ON BOTH SHEETS FOR THE 17TH & 18TH FLOORS THERE IS A |
| | SPECIFIC DEMOLITION NOTE STATING ALL WALLS, DOOR AND |
| | FIXTURES SHOWN IN SOLID LINES ARE EXISTING TO REMAIN. |
| | THE AREA OF CONCERN IS THE ELEVATOR LOBBY FOR BOTH |
| | FLOORS. THERE IS NO NOTES STATING THAT THIS BUILDING |
| | HAS PRESSURIZED ELEVATOR SHAFTWAYS IN COMPLIANCE WITH |
| | THE 2017 FBC-B 3006.3 HOISTWAY OPENING PROTECTION. ONE |
| | OF 4 METHODS. YOU ARE REMOVING THE ENCLOSED ELEVATOR |
| | LOBBY. |
| | |
| | IN THE 2017 EXISTING BUILDING CODE SEE SECTION 803.2.2 |
| | SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE |
| | REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS |
| | 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE |
| | REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO VERTICAL |
| | OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR. |
| | |
| | WITH THE REMOVAL OF THE ELEVATOR LOBBY A VIOLATION IS |
| | BEING CREATED. CREATION OR EXTENSION OF NONCONFORMITY. |
| | 2017 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| | OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| | NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| | STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| | OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | 2) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |