Plan Review Details - Permit 18120736
Plan Review Stops For Permit 18120736
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By pvalenti Date 2019-01-24 Time 12:06 Rev Time 0.00
Received By pvalenti Date 2019-01-24 Time 12:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jwitmer Date 2019-01-03 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2019-01-03 Time 07:28 Sent To  
Notes
2019-01-03 13:49:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120736
 ADD: 3701 S. FLAGLER DR. SUITE B-201
 CONT: THE CASTILLA & GODOY COMPANIES
 TEL: 561-723-4144
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 03/19
 ACTION: DENIED
  
 1) SHEET 101.1B IN THE UPPER LEFT CORNER OF THE PLAN
 SHOWS A NEW FLOOR TILE 8X64 INCH PORCELAIN FLOOR TILE.
 NO PRODUCT INFORMATION WAS PROVIDED ON THE FLOOR
 INSULATION REQUIRED.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-21 Cont ID  
Sent By jpearson Date 2019-01-21 Time 10:45 Rev Time 0.00
Received By jpearson Date 2019-01-21 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 13:18 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 13:18 Sent To  
Notes
2018-12-23 13:18:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-18 Cont ID  
Sent By pleduc Date 2019-01-18 Time   Rev Time 0.00
Received By pleduc Date 2019-01-18 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-26 Cont ID  
Sent By pleduc Date 2018-12-26 Time   Rev Time 0.00
Received By pleduc Date 2018-12-26 Time 15:24 Sent To  
Notes
2018-12-26 15:28:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE NO INDICATIONS OF FIRE SPRINKLER HEAD
 PROTECTION WITHIN THE PROPOSED PROJECT AREA. ANY
 RECONSTRUCTION OF AREAS REQUIRES A REVIEW OF THE FIRE
 SPRINKLER PROTECTION.
  
  
 2) ANY WORK AFFECTING A FIRE SPRINKLER HEAD OR
 SPRINKLER COVERAGE SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-24 Cont ID  
Sent By pvalenti Date 2019-01-24 Time 12:06 Rev Time 0.00
Received By pvalenti Date 2019-01-16 Time 15:32 Sent To  
Notes
2019-01-17 15:32:29B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-10 Cont ID  
Sent By jesmith Date 2019-01-10 Time 15:45 Rev Time 0.00
Received By jesmith Date 2019-01-10 Time 15:45 Sent To  
Notes
2018-12-20 13:29:00B30

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jesmith Date 2019-01-24 Time 10:54 Rev Time 0.00
Received By jesmith Date 2019-01-24 Time 10:53 Sent To  
Notes
2019-01-24 10:53:54APPROVED
 PLUMBING PROVISO
 NEW SHOWER DRAIN CAST IRON OR COPPER PLUMBING SHALL
 CONNECT TO EXISTING CAST IRON OR COPPER PIPING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-10 Cont ID  
Sent By jesmith Date 2019-01-10 Time 15:42 Rev Time 0.00
Received By jesmith Date 2019-01-10 Time 14:58 Sent To  
Notes
2019-01-10 15:42:22CODES IN EFFECT:
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
  
 1. RE: PLAN SHEET 101.0; TYPICAL SHOWER DETAILS. THE
 DETAIL SHOWER PAN AND CURB DETAIL SHALL SHOW COMPLIANCE
 WITH FBC PL SECTION 417 INCLUDING THE REQUIRED 2% PITCH
 REQUIRED FOR THE MEMBRANE PER WPB FBC 107.2.1. SHOW
 TYPE OF MATERIAL OF SHOWER DRAIN PIPE. PROVIDE ASSEMBLY
 HAVING A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR
 TO BE USED FOR DEALING WITH THE SHOWER FLOOR
 PENETRATION AND THE ELIMINATED TUB DRAIN OPENING AS
 REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC
 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  