| 2019-01-23 13:25:53 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18120675 |
| | ADD: 2500 S. DIXIE HWY. TENANT A MERCANTILE/ TENANT B |
| | BUSINESS |
| | CONT: DLP CONSTRUCTION INC. |
| | TEL: 770-887-3573 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 23/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 002-A0-10 THE LIFE SAFETY SHEET. PLEASE NOTE |
| | UNDER THE SCOPE OF WORK TENANT A MERCANTILE HAS 4265 |
| | SQ. FT. THE SQUARE FOOTAGE TAKEN PER OCCUPANT IS 30 SQ. |
| | FT. PLEASE NOTE UNDER THE 2017 FBC-B TABLE 1004.1.2 FOR |
| | MERCANTILE WAS CHANGED IN THE 2017 CODE TO 60 SQ. FT. |
| | PER OCCUPANT. 4265/60 = 72 OCCUPANTS. |
| | |
| | 2) SHEET 002-A0-10 THE LIFE SAFETY SHEET THE TOTAL |
| | OCCUPANT LOAD WILL ALSO CHANGE 72+10= 82 OCCUPANTS. |
| | 2017 FBC-B TABLE 1004.1.2. |
| | |
| | 3) SHEET 009-A1-02 SHOWS 2 ADA RESTROOMS 104 & 105. |
| | NEITHER RESTROOM PROVIDES THE WIDTH OF THE ROOM, PLEASE |
| | PROVIDE THE WIDTH OF BOTH RESTROOMS TO SHOW CODE |
| | COMPLIANCE WITH 604.3.1 OF THE 2017 FBC ACCESSIBILITY |
| | CODE. |
| | |
| | 4A) SHEET 009-A1-02 SHOWS TRELLIS IN THE RETAIL AREA. |
| | THIS SHEET SHOWS A DETAIL 1/ A6.03. SHEET 015-A6.03 |
| | SHOWS VARIOUS SECTIONS OF THE TRELLIS AND INDICATES |
| | THAT THE MANUFACTURER MODULO IS THE PREFERRED VENDOR. |
| | PLEASE PROVIDE ADDITIONAL INFORMATION ON THE PROPOSED |
| | TRELLIS WHAT TYPE OF MATERIAL WILL THE TRELLIS BE MADE |
| | OF? DOES THE SIDE WALLS OF THE TRELLIS SIT AGAINST THE |
| | WALLS? DOES THE CEILING IN THE TRELLIS SIT TIGHT |
| | AGAINST THE CEILING OR WILL IT BE SET OUT FROM THE |
| | CEILING? THIS REVIEW CYCLE WE ARE LOOKING AT CALLING |
| | THIS SYSTEM INTERIOR TRIM AND NEEDING TO SHOW |
| | COMPLIANCE WITH: |
| | |
| | 2017 FBC-B SECTION 806.7 INTERIOR TRIM. MATERIAL, OTHER |
| | THAN FOAM PLASTIC USED AS INTERIOR TRIM, SHALL HAVE A |
| | MINIMUM CLASS C FLAME SPREAD AND SMOKE-DEVELOPED INDEX |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723, AS |
| | DESCRIBED IN SECTION 803.1.1. COMBUSTIBLE TRIM, |
| | EXCLUDING HANDRAILS AND GUARDRAILS, SHALL NOT EXCEED 10 |
| | PERCENT OF THE SPECIFIC WALL OR CEILING AREA TO WHICH |
| | IT IS ATTACHED. |
| | |
| | 4B) ON THE CEILING PANEL OF THE TRELLIS IF FABRIC IS TO |
| | BE WOVEN THROUGH THE VARIOUS HORIZONTAL SLATS THEN |
| | COMPLIANCE WITH SECTION 806.3 OF THE FBC-B. [F] 806.3 |
| | COMBUSTIBLE DECORATIVE MATERIALS. |
| | |
| | IN OTHER THAN GROUP I-3, CURTAINS, DRAPERIES, FABRIC |
| | HANGINGS AND SIMILAR COMBUSTIBLE DECORATIVE MATERIALS |
| | SUSPENDED FROM WALLS OR CEILINGS SHALL COMPLY WITH |
| | SECTION 806.4 AND SHALL NOT EXCEED 10 PERCENT OF THE |
| | SPECIFIC WALL OR CEILING AREA TO WHICH SUCH MATERIALS |
| | ARE ATTACHED. |
| | |
| | 5) THE FLOOR PLAN 009-A1-02 SHOWS A ALCOVE BETWEEN THE |
| | 2 RESTROOMS 104 & 105. THIS AREA DOES NOT HAVE A ROOM |
| | IDENTIFICATION NUMBER. THE PLAN DOES SHOW A HIGH/ LOW |
| | DRINKING FOUNTAIN IN THE ALCOVE AND A SQUARE BOXED |
| | FIGURE. THERE IS A DETAIL, DETAIL 12/ A6.02 WHICH SHOWS |
| | THIS ITEM REFERRED TO AS T.9. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION I COULD ONLY FIND A T-1 IN THE FINISH |
| | SCHEDULE FOR PORCELAIN TILE. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THIS MAY |
| | INFRINGE ON ACCESSIBILITY TO THE DRINKING FOUNTAINS? |
| | |
| | 6) PLEASE NOTE THE FLOOR PLAN FOUND ON SHEET 009-A1-02 |
| | DOES NOT MATCH THE SECURITY FLOOR PLAN ON SHEET |
| | 012-A3-02. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED, DISCREPANCY IN PLANS. |
| | |
| | 7A) THE MECHANICAL SHEET 021-M1 SHOWS NEW WALL TYPE |
| | LOUVERS AND GRAVITY VENTILATORS. PLEASE SHOW COMPLIANCE |
| | WITH: |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31(C) WALL LOUVERS, |
| | (G) GREENHECK ROOF TOP VENTILATORS MODEL GRSR-12. |
| | |
| | 7B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 7C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 8) FOR THE ROOF TOP VENTILATORS PLEASE PROVIDE THE WIND |
| | DESIGN CRITERIA IN ACCORDANCE WITH: |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 8.2. RISK CATEGORY. |
| | |
| | 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |