Plan Review Details - Permit 18120669
Plan Review Stops For Permit 18120669
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-02-24 Cont ID  
Sent By jgomez Date 2020-02-24 Time 18:13 Rev Time 0.00
Received By jgomez Date 2020-02-24 Time 17:49 Sent To  
Notes
2020-02-24 18:12:5901/14/2020 RETURNED CALL TO DARREL GRAZIANI(WATER PLANT
 MANAGER). HE SAID OK TO PASS BUILDING WITH A PROVISO.
 JG.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- WATER TREATMENT PLANT ADMINISTRATION BUILDING
 -CHEMICAL CONTAINMENT AREAS ENGINEERING SUBMITTED FROM
 DARREL J. GRAZIANI, P.E (WATER PLAN MANAGER):
 NOTES 1 THRU 3 STATES THAT THE WATER PLANT WILL
 INITIATE OPERATIONAL CONTROLS TO LIMIT STORAGE OF
 GALLONS IN THE CONTAINMENT AREAS UNTIL MODIFICATIONS TO
 THE CONTAINMENT AREAS CAN BE DESIGNED, PERMITTED AND
 INSTALLED. PLEASE FOLLOW UP.
  
 2- ARCHITECT OF RECORD TO REVISE THE STRUCTURAL DESIGN
 CRITERIA & CODES INFORMATION ON SHEET A4.0.
 (A) ESSENTIAL FACILITY, ULTIMATE DESIGN WIND SPEED IS
 180 NOT 170. SEE FIGURE 1609.3(2) FBC AND CITY
 AMENDMENTS SEC. 120 CITY AMENDMENTS. NOTE: THIS
 BUILDING IS IN EXPOSURE D NOT C. REVISE AS REQUIRED.
 (B) REVISE THE DOORS DESIGN PRESSURES TO CORRESPOND TO
 THE REVISION REQUIRED ABOVE.
 (C) REVISE THE REFERENCED ASCE-7. THE CORRECT REFERENCE
 IS THE ASCE 7-10 NOT ASCE 7-16. REVISE AS REQUIRED.
  
 3- ALL EXIT DOORS NEED TO HAVE PANIC HARDWARE. SEC.
 1010.1.10 FBC. ARCHITECT TO REVISE DOOR HARDWARE
 SCHEDULE (INCLUDING THE EXISTING DOOR E1).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-01-14 Cont ID  
Sent By jgomez Date 2020-01-14 Time 10:22 Rev Time 0.00
Received By jgomez Date 2020-01-14 Time 08:56 Sent To  
Notes
2020-01-14 08:56:5401/14/2020 RETURNED CALL TO DARREL GRAZIANI(WATER PLANT
 MANAGER). HE SAID OK TO PASS BUILDING WITH A PROVISO.
 JG.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- WATER TREATMENT PLANT ADMINISTRATION BUILDING
 -CHEMICAL CONTAINMENT AREAS ENGINEERING SUBMITTED FROM
 DARREL J. GRAZIANI, P.E (WATER PLAN MANAGER):
 NOTES 1 THRU 3 STATES THAT THE WATER PLANT WILL
 INITIATE OPERATIONAL CONTROLS TO LIMIT STORAGE OF
 GALLONS IN THE CONTAINMENT AREAS UNTIL MODIFICATIONS TO
 THE CONTAINMENT AREAS CAN BE DESIGNED, PERMITTED AND
 INSTALLED. PLEASE FOLLOW UP.
  
 2- ARCHITECT OF RECORD TO REVISE THE STRUCTURAL DESIGN
 CRITERIA & CODES INFORMATION ON SHEET A4.0.
 (A) ESSENTIAL FACILITY, ULTIMATE DESIGN WIND SPEED IS
 180 NOT 170. SEE FIGURE 1609.3(2) FBC AND CITY
 AMENDMENTS SEC. 120 CITY AMENDMENTS. NOTE: THIS
 BUILDING IS IN EXPOSURE D NOT C. REVISE AS REQUIRED.
 (B) REVISE THE DOORS DESIGN PRESSURES TO CORRESPOND TO
 THE REVISION REQUIRED ABOVE.
 (C) REVISE THE REFERENCED ASCE-7. THE CORRECT REFERENCE
 IS THE ASCE 7-10 NOT ASCE 7-16. REVISE AS REQUIRED.
  
 3- ALL EXIT DOORS NEED TO HAVE PANIC HARDWARE. SEC.
 1010.1.10 FBC. ARCHITECT TO REVISE DOOR HARDWARE
 SCHEDULE (INCLUDING THE EXISTING DOOR E1).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-12-19 Cont ID  
Sent By jgomez Date 2019-12-19 Time 14:04 Rev Time 0.00
Received By jgomez Date 2019-12-19 Time 10:41 Sent To I
Notes
2019-12-19 10:41:25ALTERATION/CHANGE OF OCCUPANCY, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- THRU 3. OK
  
 4- WATER TREATMENT PLANT ADMINISTRATION BUILDING
 -CHEMICAL CONTAINMENT AREAS ENGINEERING SUBMITTED FROM
 DARREL J. GRAZIANI, P.E :
 NOTES 1 THRU 3 STATES THAT THE WATER PLANT WILL
 INITIATE OPERATIONAL CONTROLS TO LIMIT STORAGE OF
 GALLONS IN THE CONTAINMENT AREAS UNTIL MODIFICATIONS TO
 THE CONTAINMENT AREAS CAN BE DESIGNED, PERMITTED AND
 INSTALLED. PLEASE PROVIDE LETTER FROM WATER TREATMENT
 PLANT DIRECTOR ACKNOWLEDGING THAT THE OPERATING
 CONTROLS SPECIFIED BY THE ENGINEER WILL BE INITIATED.
 THIS LETTER OF ACKNOWLEDGMENT IS REQUESTED FOR CITY
 FILE TO MAKE SURE THE QUANTITIES OF THE HAZARDOUS
 MATERIALS IN THE CONTAINMENT AREAS WILL NOT EXCEED THE
 QUANTITIES STATED BY THE ENGINEER OF RECORD AND TABLE
 307.1(2) FBC-BUILDING. OTHERWISE, THE BUILDING WILL BE
 CONSIDERED HIGH HAZARD GROUP H-4 AND MIXED OCCUPANCIES
 WILL NOT ALLOWED AND ADDITIONAL REQUIREMENTS WILL
 APPLY.
  
  
 5- THRU 10. OK
  
 11- REPEAT COMMENT. REVISE THE STRUCTURAL DESIGN
 CRITERIA & CODES INFORMATION ON SHEET A4.0.
 (A) THIS IS AN ESSENTIAL FACILITY, THEN THE ULTIMATE
 DESIGN WIND SPEED IS 180 NOT 170. SEE FIGURE 1609.3(2)
 FBC AND CITY AMENDMENTS SEC. 120 CITY AMENDMENTS. NOTE:
 THIS BUILDING IS IN EXPOSURE D NOT C. REVISE AS
 REQUIRED.
  
 (B) REVISE THE DOORS DESIGN PRESSURES TO CORRESPOND TO
 THE REVISION REQUIRED ABOVE.
  
 (C) REVISE THE REFERENCED ASCE-7. THE CORRECT REFERENCE
 IS THE ASCE 7-10 NOT ASCE 7-16. REVISE AS REQUIRED.
  
 12- REPEAT COMMENT. ALL EXIT DOORS NEED TO HAVE PANIC
 HARDWARE AS REQUIRED BY SEC. 1010.1.10 FBC. REVISE DOOR
 HARDWARE SCHEDULE AS REQUIRED (INCLUDING THE EXISTING
 DOOR E1). THERE ARE NOT SPECIFICATIONS FOR PANIC
 HARDWARE ON EXISTING DOOR E1. PLEAE PROVIDE
 INFORMATION.
  
 13- 16 OK
  
 17- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-08 Cont ID  
Sent By jgomez Date 2019-05-08 Time 13:14 Rev Time 0.00
Received By jgomez Date 2019-05-06 Time 15:46 Sent To  
Notes
2019-05-06 18:48:10ALTERATION/CHANGE OF OCCUPANCY, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- OK
  
 2- OK
  
 3- OK.
  
 4- OCCUPANCY LOADS ON SHEET A0 INDICATES OCCUPANCY
 FACTORY (F) AND CONFERENCE AREA. CLEARLY SPECIFY TYPE
 OF FACTORY. F1 OR F2. SEE SEC. 306 FBC.
  
 RESPONSE:
 REVISED OCCUPANCY STATES:
 MAIN OCCUPANCY: FACTORY GROUP F-1 (ORIGINAL
 DESIGNATION).
 ACCESSORY USES: B-BUSINESS; USED ON 2ND LEVEL.
 S- STORAGE: USED ON 1ST LEVEL
 A-1 NEW ASSEMBLY USE (CONFERENCE ROOM).
  
 NEW ACCESSORY OCCUPANCY LOAD: CONFERENCE AREA 1/15 X
 +/-836SF=56 OCCUPANTS.
  
 THE OCCUPANCY OF THIS BUILDING NEEDS TO BE
 REVISED/CLARIFIED.
 (A)ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10
 PERCENT OF THE FLOOR AREA OF THE STORY IN WHICH THEY
 ARE LOCATED. SEE SEC. 508.2.3 FBC-BUILDING AND REVISE
 AS REQUIRED.
 ALSO, ASSEMBLY IS NOT AN ACCESSORY FOR STORAGE. THIS IS
 A SEPARATE OCCUPANCY GROUP. SEE SEC. 302.1
 FBC-BUILDING. USE
  
 (B) BASED ON REVISED FLOOR PLANS ON SHEET A1.0 THE
 FIRST FLOOR MAY NOT BE CLASSIFIED AS STORAGE . IT MAY
 BE CLASSIFIED AS HIGH-HAZARD GROUP H. SEE SEC. 307.1
 FBC-BUILDING.
 PROVIDE THE MSDS SHEETS FOR ALL CHEMICALS AND ALL
 QUANTITIES TO VERIFY IF QUANTITIES ARE IN EXCESS OF
 THOSE ALLOWED IN CONTROL AREAS. (SEE SEC. 414.2 FOR
 CONTROL AREAS REQUIREMENTS).
 NOTE: IF HIGH HAZARD GROUP H IS DETERMINED, THEN MIXED
 OCCUPANCIES ARE NOT ALLOWED AND ADDITIONAL REQUIREMENTS
 MAY APPLY.
  
 (C)CONFERENCE ROOM IS NOT ASSEMBLY A-1. SINCE THERE IS
 NOT SPECIFIC ASSEMBLY FOR A CONFERENCE ROOM, THEN IT
 FALLS MORE IN THE ASSEMBLY GROUP A-3. SEE SEC. 303.4
 FBC-BUILDING AND REVISE AS REQUIRED.
  
  
 5- OK
  
 6- A)FACTORY USE AND ASSEMBLY USE ARE MIXED
 OCCUPANCIES. SEE 2017 FBC-B 508.1. EACH PORTION OF A
 BUILDING SHALL BE INDIVIDUALLY CLASSIFIED IN ACCORDANCE
 WITH SECTION 302.1. WHERE A BUILDING CONTAINS MORE THAN
 ONE OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 508.2, 508.3 OR 508.4, OR A COMBINATION OF THESE
 SECTIONS.
  
 B) CLARIFY WHY COVER SHEET AND TITLE BLOCK ON ALL PLANS
 INDICATE THAT THIS IS "ADMINISTRATION BLDG. CONFERENCE
 ROOM". THIS BUILDING DOESN'T SEEM TO BE THE
 ADMINISTRATION BUILDING. IS THERE A FACTORY IN THE
 ADMINISTRATION BUILDING?. COORDINATE WITH ITEM ABOVE
 AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH ITEM #4 ABOVE.
  
 7- THE DESIGNER OF RECORD WILL ALSO NEED TO INDICATE IF
 THE NEW CONFERENCE ROOM WILL MEET WHICH SECTION OF THE
 2017 FBC-B CODE:
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.1 CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 RESPONSE:
 (A)COORDINATE WITH ITEM #4 ABOVE.
  
 (B) IF THE OCCUPANCY SEPARATION IS ALLOWED, THEN THE
 REQUIRED SEPARATION SHALL BE FIRE BARRIERS. NEED TO
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 APPROVED FIRE BARRIER WALL AND APPROVED HORIZONTAL FIRE
 RATED ASSEMBLY AS REQUIRED BY SEC. 508.4.4.1
 FBC-BUILDING.
 NOTE: EXISTING CONCRETE BLOCK WALL DOESN'T NECESSARILY
 MAKES A TWO HOUR FIRE RATED WALL. NEED TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR TYPE OF
 CONCRETE BLOCK USED ON THE WALL TO VERIFY THAT IT MEETS
 THE FIRE RATING STATED. SAME APPLIES TO THE EXISTING
 FLOOR /CEILING ASSEMBLY.
  
 8- OK.
  
 9- 2017 FBC-EXIT. BLDG. CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 EXIST. BLDG. CODE. 1012.8 ACCESSIBILITY EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 A) PLEASE SHOW HOW COMPLIANCE WITH SEC. 202.4 FLORIDA
 ACCESSIBILITY CODE ( 2012 EDITION). SHOW PATH OF TRAVEL
 TO THE ALTERED AREA, INCLUDING THE RESTROOMS, ETC. SEE
 SEC. 202.4 FAC.
  
 RESPONSE:
 CLARIFY WHAT IS THE ACCESSIBLE ROUTE TO ENTER THE NEW
 CONFERENCE ROOM. ONLY THRU THE CORRIDOR DOOR OR ALSO
 THRU THE NEW EXTERIOR DOUBLE DOORS. PLANS DON'T SHOW
 ANY INFORMATION OF THE DOORS THRESHOLD. ARE THE NEW
 EXTERIOR DOORS PART OF THE ACCESSIBLE ROUTE TO THE NEW
 CONFERENCE ROOM? I APOLOGIZE, I SHOULD OF CLARIFY AND
 ASK FOR THE ACCESSIBLE ROUTE TO ENTER THE NEW
 CONFERENCE ROOM. SEE SEC. 206.2.1 FBC-ACCESSIBILITY.
  
  
 B) FLOOR PLAN SHOWS WHAT APPEARS TO BE A SINK AND
 CABINETRY MAYBE A BREAK AREA. THE PLANS DO NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION 606
 SINKS.
 606.2 CLEAR FLOOR SPACE.
 606.3HEIGHT.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 RESPONSE:
 SINK HEIGHT DOESN'T COMPLY WITH SEC. 606.3.
 THERE IS NOT INFORMATION FOR EXPOSED PIPES AND SURFACE
 PROTECTION AS REQUIRED BY SEC. 606.5.
  
 10- OK.
  
 11- PROVIDE COMPLETE WIND DESIGN DATA AS REQUIRED BY
 SEC. 1603.1.4 FBC.
 NOTE: CHECK TABLE 1604.5 FBC. THIS BUILDING LOOKS LIKE
 IS ESSENTIAL FACILITY. AND REVISE EXTERIOR DOORS DESIGN
 PRESSURES SHOWN ON SHEET A4.0.
  
 RESPONSE:
 REVISE THE STRUCTURAL DESIGN CRITERIA & CODES
 INFORMATION ON SHEET A4.0.
 (A) ASCE REFERENCED IN THE 2017 FBC IS THE ASCE 7-10
 NOT ASCE 7-16. REVISE AS REQUIRED.
  
 (B) IF THIS IS AN ESSENTIAL FACILITY, THEN THE ULTIMATE
 DESIGN WIND SPEED IS 180 NOT 170. SEE FIGURE 1609.3(2)
 FBC AND CITY AMENDMENTS SEC. 120 CITY AMENDMENTS. NOTE:
 THIS BUILDING IS IN EXPOSURE D NOT C. REVISE AS
 REQUIRED.
  
 (C) REVISE THE DOORS DESIGN PRESSURES TO CORRESPOND TO
 THE REVISION REQUIRED ABOVE.
  
 12- ALL EXIT DOORS NEED TO HAVE PANIC HARDWARE AS
 REQUIRED BY SEC. 1010.1.10 FBC. REVISE DOOR HARDWARE
 SCHEDULE AS REQUIRED (INCLUDING THE EXISTING DOOR E1).
  
 RESPONSE:
 THERE ARE NOT SPECIFICATIONS FOR PANIC HARDWARE ON
 EXISTING DOOR E1.
  
 13- OK
  
 14- OK
  
 15- OK
  
 16 VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS
 TO BE LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON
 PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE AS REQUIRED OR PROVIDE COPIES OF
 SIGNED CONTRACTS FOR BUILDING OFFICIAL APPROVAL.
  
 17- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-10 Cont ID  
Sent By jgomez Date 2019-01-16 Time 12:33 Rev Time 0.00
Received By jgomez Date 2019-01-15 Time 16:59 Sent To  
Notes
2019-01-10 12:34:19ALTERATION/CHANGE OF OCCUPANCY, BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- UNDER THE 2017 FBC-EXISTING BUILDING CODE, THE
 DESIGNER OF RECORD HAS NOT LISTED WHICH METHOD THE
 PLANS WERE CREATED. 2017 FBC-EXISTING BUILDING CODE
 SECTION 301.1. THE ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER. PLEASE NOTE FOR THIS
 ROOM IT IS CONSIDERED A CHANGE OF OCCUPANCY.
  
 2- THERE ARE MANY BUILDINGS IN THIS PROPERTY. PROVIDE
 PLOT PLAN SHOWING LOCATION OF BUILDING WHERE WORK IS
 TAKEN PLACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- REVISE PROJECT DATA INFORMATION ON SHEET A0: THIS IS
 NOT ALTERATION LEVEL II. THIS IS CHANGE OF OCCUPANCY.
 SEC. 506 FBC-EXISTING BUILDING.
 APPLICABLE SECTIONS OF CHAPTER 10 WILL APPLY. REVISE AS
 REQUIRED.
  
 4- OCCUPANCY LOADS ON SHEET A0 INDICATES OCCUPANCY
 FACTORY (F) AND CONFERENCE AREA. CLEARLY SPECIFY TYPE
 OF FACTORY. F1 OR F2. SEE SEC. 306 FBC.
  
 5- PROJECT DATA ON SHEET AO DOESN'T SPECIFY IF THIS
 BUILDING IS SPRINKLERED OR NOT. SEC. 107.3.5.1 CITY
 AMENDMENTS.
  
 6- A)FACTORY USE AND ASSEMBLY USE ARE MIXED
 OCCUPANCIES. SEE 2017 FBC-B 508.1. EACH PORTION OF A
 BUILDING SHALL BE INDIVIDUALLY CLASSIFIED IN ACCORDANCE
 WITH SECTION 302.1. WHERE A BUILDING CONTAINS MORE THAN
 ONE OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 508.2, 508.3 OR 508.4, OR A COMBINATION OF THESE
 SECTIONS.
  
 B) CLARIFY WHY COVER SHEET AND TITLE BLOCK ON ALL PLANS
 INDICATE THAT THIS IS "ADMINISTRATION BLDG. CONFERENCE
 ROOM". THIS BUILDING DOESN'T SEEM TO BE THE
 ADMINISTRATION BUILDING. IS THERE A FACTORY IN THE
 ADMINISTRATION BUILDING?. COORDINATE WITH ITEM ABOVE
 AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- THE DESIGNER OF RECORD WILL ALSO NEED TO INDICATE IF
 THE NEW CONFERENCE ROOM WILL MEET WHICH SECTION OF THE
 2017 FBC-B CODE:
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.1 CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 8- RENOVATED FLOOR PLAN SHOWS TWO SINGLE IN-SWING DOORS
 INTO THE CONFERENCE ROOM FROM THE INTERIOR EXIT ACCESS
 CORRIDOR. PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-B SECTION 1010.1.2.1 DIRECTION OF SWING. PIVOT
 OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 9- 2017 FBC-EXIT. BLDG. CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 EXIST. BLDG. CODE. 1012.8 ACCESSIBILITY EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 A) PLEASE SHOW HOW COMPLIANCE WITH SEC. 202.4 FLORIDA
 ACCESSIBILITY CODE ( 2012 EDITION). SHOW PATH OF TRAVEL
 TO THE ALTERED AREA, INCLUDING THE RESTROOMS, ETC. SEE
 SEC. 202.4 FAC.
  
 B) FLOOR PLAN SHOWS WHAT APPEARS TO BE A SINK AND
 CABINETRY MAYBE A BREAK AREA. THE PLANS DO NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION 606
 SINKS.
 606.2 CLEAR FLOOR SPACE.
 606.3HEIGHT.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 10- BUILDING THERMAL ENVELOPE. IT IS NOT CLEAR IF
 BUILDING IS AIR CONDITIONED OR NOT.
 A) DESIGNER OF RECORD TO REPRESENT THE BUILDING'S
 THERMAL ENVELOPE ON PLANS AS REQUIRED BY SEC. C103.2.1
 FBC-ENERGY CONSERVATION.
 NOTE: SEE BUILDING THERMAL ENVELOPE DEFINITION ON
 CHAPTER 2 OF FBC.
  
 B) PROVIDE COMPLETE INFORMATION ON PLANS INCLUDING BUT
 NOT LIMITED TO INSULATION R VALUES ON ALL WALLS,
 CEILING, ETC. AS REQUIRED BY SEC. C103.2 FBC-ENERGY
 CONSERVATION.
  
 C) ENERGY FORM SUBMITTED IS MISSING THE BUILDING
 ENVELOPE INFORMATION. AND, DESIGNER OF RECORD TO SIGN
 AND PROVIDE PROFESSIONAL REGISTRATION NUMBER ON THE
 ENERGY CODE FORM AS REQUIRED BY SEC. C103.1.1.1.2
 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE COMPLETE WIND DESIGN DATA AS REQUIRED BY
 SEC. 1603.1.4 FBC.
 NOTE: CHECK TABLE 1604.5 FBC. THIS BUILDING LOOKS LIKE
 IS ESSENTIAL FACILITY. AND REVISE EXTERIOR DOORS DESIGN
 PRESSURES SHOWN ON SHEET A4.0.
  
 12- ALL EXIT DOORS NEED TO HAVE PANIC HARDWARE AS
 REQUIRED BY SEC. 1010.1.10 FBC. REVISE DOOR HARDWARE
 SCHEDULE AS REQUIRED (INCLUDING THE EXISTING DOOR E1).
  
 13-DETAIL 1/A4.0 DOOR JAMB OF NEW STOREFRONT. PROVIDE
 COMPLETE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS.
 SPECIFY BUCK SIZE AND FASTENER TYPE AND SPACING. SEC.
 1609.1 FBC.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) NEW STORE FRONT DOORS.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 16 VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS
 TO BE LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON
 PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE AS REQUIRED OR PROVIDE COPIES OF
 SIGNED CONTRACTS FOR BUILDING OFFICIAL APPROVAL.
  
 17- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-01-02 Cont ID  
Sent By jpearson Date 2019-01-02 Time 13:40 Rev Time 0.00
Received By jpearson Date 2019-01-02 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By pleduc Date 2019-04-16 Time   Rev Time 0.00
Received By pleduc Date 2019-04-16 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By pleduc Date 2018-12-20 Time   Rev Time 0.00
Received By pleduc Date 2018-12-20 Time 11:03 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By fmittner Date 2019-05-09 Time 09:11 Rev Time 0.00
Received By fmittner Date 2019-05-09 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-24 Cont ID  
Sent By jgomez Date 2020-02-24 Time 18:17 Rev Time 0.00
Received By jgomez Date 2020-02-13 Time 13:48 Sent To I
Notes
2020-02-24 11:40:41RESUB ROUTED TO JGOMEZ
2020-02-14 13:48:48RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-19 Cont ID  
Sent By jgomez Date 2019-12-19 Time 14:57 Rev Time 0.00
Received By jgomez Date 2019-12-06 Time 14:54 Sent To I
Notes
2019-12-10 14:27:54ROUTE TO JGOMEZ; REVISIT PLUMBING ON 12/12/2019
2019-12-09 14:54:39RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-09 Cont ID  
Sent By cpuell Date 2019-05-09 Time 11:43 Rev Time 0.00
Received By cpuell Date 2019-04-10 Time 15:42 Sent To  
Notes
2019-04-11 15:42:41B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-16 Cont ID  
Sent By jesmith Date 2019-01-15 Time 10:00 Rev Time 0.00
Received By jgomez Date 2019-01-15 Time 10:00 Sent To I
Notes
2018-12-19 14:36:19B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-10 Cont ID  
Sent By jgomez Date 2019-01-10 Time 10:01 Rev Time 0.00
Received By jgomez Date 2019-01-10 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By ccole Date 2019-04-25 Time 11:33 Rev Time 0.00
Received By ccole Date 2019-04-25 Time 11:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-07 Cont ID  
Sent By hmoser Date 2019-01-07 Time 14:22 Rev Time 0.00
Received By hmoser Date 2019-01-07 Time 13:02 Sent To  
Notes
2019-01-07 14:22:42PLAN DENIED
 PROVIDE EQUIPMENT SCHEDULE ON PLAN
 PER SECTION 107 FBC 2017
 REFER TO SECTION 603 2017
 FBC (M) HEAT LOADS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-02-24 Cont ID  
Sent By jesmith Date 2020-02-24 Time 11:34 Rev Time 0.00
Received By jesmith Date 2020-02-24 Time 11:34 Sent To  
Notes
2020-02-24 11:34:50PLUMBING COMMENTS: APPROVED W/PROVISO
 PROVIDE DISPENSER W/FLAT BOTTOM CUPS. DISPENSER SHALL
 BE LOCATED ADJACENT TO THE WATER DISPENSER AND SHALL
 COMPLYWITH FBC ACC SECTION 308 FOR REACH RANGE.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-12-12 Cont ID  
Sent By jesmith Date 2019-12-10 Time 14:06 Rev Time 0.00
Received By jesmith Date 2019-12-10 Time 14:01 Sent To  
Notes
2019-12-10 14:06:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1. SECOND REQUEST: WATER DISPENSER/TAG R15 ON PLAN
 SHEET A2.0. A BACKFLOW PREVENTION DEVICE IS REQUIRED ON
 THE POTABLE WATER SUPPLY IN ORDER TO COMPLY WITH FBC PL
 608.3. SPECIFY TYPE OF DEVICE AND INDICATE ON WATER
 RISER. SEE COMMENT 1(B) ON REVIEW 1 DATED 1/15/19 AND
 COMMENT 1 ON REVIEW 2, 4/18/19.
 2. ADDITIONAL COMMENT: WATER DISPENSER/TAG R15
 (WATERLOGIC WL800 MAX II) ON PLAN SHEET A2.0. PROVIDE
 INDIRECT WASTE FOR DRAIN(S) FROM MEMBRANE FILTER #2 AND
 HOT AND COLD WATER TANK DRAINS TO A TRAPPED AND VENTED
 WASTE RECEPTACLE THROUGH AN AIR GAP PER FBC PL 802.2.
 INDICATE ON SANITARY RISER. PER WPB FBC 107.2.1, SUBMIT
 THE WL800 OPERATING, INSTALLATION AND SERVICE MANUAL HT
 TPS://WWW.WATERLOGIC.COM/EN-US/MEDIA/USA/RESOURCES/WL80
 0OPERATINGMANUAL.PDF
 3. SECOND REQUEST: HAND SINK/TAG R19-SINK ON PLAN SHEET
 A2.0; PER FBC ACC 804.3.2 AND 606.3, THE WORK SURFACE
 AND FIXTURE RIM SHALL BE 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. ARCHITECT DID NOT
 RESPOND TO REQUEST FOR SINK SPECIFICATION; A SINK AND
 FAUCET SHALL BE SUBMITTED SHOWING COMPLIANCE WITH FBC
 ACC 308, 309 AND 606. ADDITIONALLY, THE INTERIOR
 ELEVATIONS ON A2.0 INDICATE 3'-0" TO TOP OF
 CABINET/SINK RIM.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 18120669 1009 BANYAN BLVD
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By jesmith Date 2019-04-18 Time 13:03 Rev Time 0.00
Received By jesmith Date 2019-04-18 Time 13:03 Sent To  
Notes
2019-04-18 13:03:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
 PLUMBING COMMENTS:
 1. A REVIEW OF A2.0 FIXTURE TAG R15 WATER DISPENSER
 INDICATES THAT A BACKFLOW PREVENTION DEVICE IS REQUIRED
 ON THE POTABLE WATER SUPPLY IN ORDER TO COMPLY WITH FBC
 PL 6018.3. SPECIFY TYPE OF DEVICE INCLUDING ASSA
 STANDARD AND INDICATE ON WATER RISER. SEE PREVIOUS
 COMMENT 1 (B).
 2. TAG R19-SINK; ARCHITECT DID NOT RESPOND TO REQUEST
 FOR SINK SPECIFICATION; A SINK AND FAUCET SHALL BE
 SUBMITTED SHOWING COMPLIANCE WITH FBC ACC 308, 309 AND
 606. ADDITIONALLY, THE INTERIOR ELEVATIONS ON A2.0
 INDICATE 3'-0" TO TOP OF CABINET/SINK RIM. PER FBC ACC
 804.3.2 AND 606.3, THE WORK SURFACE AND FIXTURE RIM
 SHALL BE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By jesmith Date 2019-01-15 Time 09:56 Rev Time 0.00
Received By jesmith Date 2019-01-15 Time 09:20 Sent To  
Notes
2019-01-15 09:48:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET A2.0; KITCHENETTE
 A. TAG R19-SINK: SINK SHALL COMPLY WITH THE
 REQUIREMENTS OF FBC ACC SECTION 606 PER FBC ACC 212.3;
 PLANS SHALL PROVIDE THE APPROPRIATE INFORMATION SHOWING
 COMPLIANCE PER WPB FBC 107.2.1.PROVIDE SPECIFICATION
 FOR SINK PER WPB FBC 107.2.1.
 B. TAG R15-WATER DISPENSER: ON PLUMBING PLAN SHEET
 P1.1, THERE IS NO PROVISION FOR WATER SUPPLY TO THE
 WATER DISPENSER OR WASTE. PROVIDE THE APPROPRIATE
 INFORMATION ON THE PLANS, INCLUDING ANY REQUIREMENTS
 FOR BACKFLOW PREVENTION AS OUTLINED IN FBC PL SECTION
 608 AND PROVIDE SPECIFICATION FOR WATER DISPENSER PER
 WPB FBC 107.2.1.
 2. RE: PLAN SHEET P1.1; DETAIL #1 SPECIFIES 3/4" HOT
 WATER TO FIXTURES AND RISER #2 SPECIFIES 1/2" HOT
 WATER. PLEASE CLARIFY PER WPB FBC 107.2.1
 3. RE: PLAN SHEET A0; THE RENOVATION IS TAKING PLACE IN
 A 12,000+ SQ FT FACILITY FACTORY (F) OCCUPANCY. THE
 EXISTING PLUMBING COUNT NOTES BATHROOM FIXTURES AND THE
 EXISTING BATHROOMS ARE LOCATED ON PLAN SHEET D1 FLOOR
 PLANS;THERE IS NO INDICATION OF A SERVICE SINK OR A
 DRINKING FOUNTAIN AS REQUIRED BY FPC PL TABLE 403.1.
 P:LEASE CLARIFY PER WPB FBC 107.2.1.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  