| 2019-01-31 10:51:07 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18120609 |
| | REVIEWED: JANUARY 31, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | -PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS |
| | LOOKS LIKE ADDITION AND LEVEL 3 ALTERATION SINCE MORE |
| | THAN 50% AFFECTED AREA. |
| | |
| | 2. 301.4 FBC[R] DEAD LOAD. THE ACTUAL WEIGHTS OF |
| | MATERIALS AND CONSTRUCTION SHALL BE USED FOR |
| | DETERMINING DEAD LOAD WITH CONSIDERATION FOR THE DEAD |
| | LOAD OF FIXED SERVICE EQUIPMENT. |
| | |
| | 3. R301.5 FBC[R] LIVE LOAD. THE MINIMUM UNIFORMLY |
| | DISTRIBUTED LIVE LOAD SHALL BE AS PROVIDED IN TABLE |
| | R301.5. |
| | |
| | 4. R301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED |
| | FOR THE LIVE LOAD INDICATED IN TABLE R301.6 |
| | -PLEASE PROVIDE LIVE AND DEAD LOADS TO DESIGN DATA. |
| | |
| | 5. 107.5.3 FBC[AMENDED] SHEETS REFER TO SEE STRUCTURAL, |
| | BUT THERE ARE NO STRUCTURAL SHEET(S). IS THERE A |
| | STRUCTURAL SHEET TO SHOW FOOTER SIZES, LOADS AND SLAB |
| | DETAILS? |
| | A. 506.2.3 FBC[R] VAPOR RETARDER. A 6-MIL (0.006 INCH) |
| | POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS |
| | LAPPED NOT LESS THAN 6 INCHES (152 MM) SHALL BE PLACED |
| | BETWEEN THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR |
| | THE PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS. |
| | EXCEPTION: THE VAPOR RETARDER IS NOT REQUIRED FOR THE |
| | FOLLOWING: |
| | B. 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION |
| | SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING |
| | SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND |
| | PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS |
| | OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE |
| | TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202, |
| | ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE |
| | APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A |
| | CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE |
| | BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| | COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| | PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| | FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| | SERVICES.? |
| | C. 506.2.4.2 FBC[R] CRACK CONTAINMENT MEASURES |
| | COMPLYING WITH ONE OF THE FOLLOWING: SEE 506.2.4.2 |
| | |
| | |
| | 6. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS. |
| | |
| | 7. 301.2.1.2 FBC[R] PROTECTION OF OPENINGS. |
| | -PROVIDE NOTES/DETAILS FOR PROTECTION FROM WINDBORNE |
| | DEBRIS TO ALL EXTERIOR OPENINGS INCLUDING WINDOWS, |
| | ENTRY DOORS AND GARAGE DOORS. |
| | |
| | 8. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS, WINDOW MULL, DOORS AND SLIDERS, OR INDICATE |
| | THAT YOU WOULD LIKE THEM DEFERED. |
| | -NUMBERS ARE LISTED ON SHEET A-003. IF THOSE THE |
| | PRODUCT APPROVALS PLEASE PROVIDE TWO COPIES OF EACH. |
| | |
| | 9. 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| | REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| | THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| | INDEX AND SMOKE DEVELOPED INDEX. |
| | A. IS THE WHOLE ATTIC GETTING NEW SPRAY INSULATION? |
| | B. WILL THE WHOLE ATTIC BE UNVENTED AS STATED IN ENERGY |
| | CALCULATIONS? |
| | C. PLEASE MAKE SURE THE ENERGY CALCULATIONS MATCH THE |
| | INSULATION, VENTING AND TYPE BEING PROVIDED AND HAVE |
| | THE OWNER OR AGENT SIGN THE ENERGY CALCULATION BELOW |
| | WHERE THE PREPARER SIGNED. (CURRENTLY THE ENERGGY CALCS |
| | SHOW BLOWN IN INSULATION) |
| | |
| | 10. 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE |
| | ATTIC AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR |
| | FOLLOW R805.5 FOR UNVENTED. |
| | |
| | 11. 807 FBC[R] BUILDINGS WITH COMBUSTIBLE CEILING OR |
| | ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO |
| | ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES |
| | (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30 |
| | SQUARE FEET (2.8 M2). |
| | -SHOW ATTIC ACCESS ON PLANS |
| | |
| | 12. 315.1 FBC[R] CARBON MONOXIDE PROTECTION. EVERY |
| | SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, **AN ATTACHED GARAGE**, OR |
| | OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON |
| | MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN |
| | OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 |
| | FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| | EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING |
| | BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR |
| | UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN |
| | SECTION R315.1.3. |
| | |
| | 13. 315.1.1 FBC[R] CARBON MONOXIDE ALARM. THE |
| | REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY |
| | PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS: |
| | 1. A HARD-WIRED CARBON MONOXIDE ALARM. |
| | 2. A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| | 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| | ALARM. |
| | 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| | SMOKE ALARM. |
| | |
| | 14. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERED. |
| | |
| | 15. 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS |
| | TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | -THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |