Plan Review Details - Permit 18120609
Plan Review Stops For Permit 18120609
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By dbattles Date 2019-02-26 Time 16:44 Rev Time 0.00
Received By dbattles Date 2019-02-26 Time 16:17 Sent To  
Notes
2019-02-26 16:42:07PROVISOS:
 PROVIDE PRODUCT APPROVALS FOR WINDOWS, WINDOW MULL,
 DOORS AND SLIDERS,

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-31 Cont ID  
Sent By dbattles Date 2019-01-31 Time 10:30 Rev Time 0.00
Received By dbattles Date 2019-01-30 Time 15:45 Sent To  
Notes
2019-01-31 10:51:07****CORRECTIONS****
 W.P.B. PERMIT: 18120609
 REVIEWED: JANUARY 31, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  -PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS
 LOOKS LIKE ADDITION AND LEVEL 3 ALTERATION SINCE MORE
 THAN 50% AFFECTED AREA.
  
 2. 301.4 FBC[R] DEAD LOAD. THE ACTUAL WEIGHTS OF
 MATERIALS AND CONSTRUCTION SHALL BE USED FOR
 DETERMINING DEAD LOAD WITH CONSIDERATION FOR THE DEAD
 LOAD OF FIXED SERVICE EQUIPMENT.
  
 3. R301.5 FBC[R] LIVE LOAD. THE MINIMUM UNIFORMLY
 DISTRIBUTED LIVE LOAD SHALL BE AS PROVIDED IN TABLE
 R301.5.
  
 4. R301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED
 FOR THE LIVE LOAD INDICATED IN TABLE R301.6
  -PLEASE PROVIDE LIVE AND DEAD LOADS TO DESIGN DATA.
  
 5. 107.5.3 FBC[AMENDED] SHEETS REFER TO SEE STRUCTURAL,
 BUT THERE ARE NO STRUCTURAL SHEET(S). IS THERE A
 STRUCTURAL SHEET TO SHOW FOOTER SIZES, LOADS AND SLAB
 DETAILS?
 A. 506.2.3 FBC[R] VAPOR RETARDER. A 6-MIL (0.006 INCH)
 POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS
 LAPPED NOT LESS THAN 6 INCHES (152 MM) SHALL BE PLACED
 BETWEEN THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR
 THE PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS.
 EXCEPTION: THE VAPOR RETARDER IS NOT REQUIRED FOR THE
 FOLLOWING:
 B. 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
 C. 506.2.4.2 FBC[R] CRACK CONTAINMENT MEASURES
 COMPLYING WITH ONE OF THE FOLLOWING: SEE 506.2.4.2
  
  
 6. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS.
  
 7. 301.2.1.2 FBC[R] PROTECTION OF OPENINGS.
  -PROVIDE NOTES/DETAILS FOR PROTECTION FROM WINDBORNE
 DEBRIS TO ALL EXTERIOR OPENINGS INCLUDING WINDOWS,
 ENTRY DOORS AND GARAGE DOORS.
  
 8. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS AND SLIDERS, OR INDICATE
 THAT YOU WOULD LIKE THEM DEFERED.
  -NUMBERS ARE LISTED ON SHEET A-003. IF THOSE THE
 PRODUCT APPROVALS PLEASE PROVIDE TWO COPIES OF EACH.
  
 9. 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
 A. IS THE WHOLE ATTIC GETTING NEW SPRAY INSULATION?
 B. WILL THE WHOLE ATTIC BE UNVENTED AS STATED IN ENERGY
 CALCULATIONS?
 C. PLEASE MAKE SURE THE ENERGY CALCULATIONS MATCH THE
 INSULATION, VENTING AND TYPE BEING PROVIDED AND HAVE
 THE OWNER OR AGENT SIGN THE ENERGY CALCULATION BELOW
 WHERE THE PREPARER SIGNED. (CURRENTLY THE ENERGGY CALCS
 SHOW BLOWN IN INSULATION)
  
 10. 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE
 ATTIC AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR
 FOLLOW R805.5 FOR UNVENTED.
  
 11. 807 FBC[R] BUILDINGS WITH COMBUSTIBLE CEILING OR
 ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES
 (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET (2.8 M2).
  -SHOW ATTIC ACCESS ON PLANS
  
 12. 315.1 FBC[R] CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, **AN ATTACHED GARAGE**, OR
 OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES.
 EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING
 BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR
 UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN
 SECTION R315.1.3.
  
 13. 315.1.1 FBC[R] CARBON MONOXIDE ALARM. THE
 REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
 1. A HARD-WIRED CARBON MONOXIDE ALARM.
 2. A BATTERY-POWERED CARBON MONOXIDE ALARM.
 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 14. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 15. 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS
 TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  -THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-01 Cont ID  
Sent By jpearson Date 2019-03-01 Time 14:16 Rev Time 0.00
Received By jpearson Date 2019-03-01 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By jpearson Date 2019-01-08 Time 16:55 Rev Time 0.00
Received By jpearson Date 2019-01-08 Time 13:19 Sent To  
Notes
2019-01-08 16:55:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 2. CIRCUIT 30 IN PANEL SCHEDULE SHOWS THE BATH GFI ON
 THE SAME CIRCUIT AS KITCHEN AND MECHANICAL ROOM.
 BATHROOM GFCI RECEPTACLE OUTLETS ARE REQUIRED TO BE ON
 A DEDICATED 20 AMP CIRCUITS. KITCHEN RECEPTACLE OUTLETS
 CANNOT BE USED FOR RECEPTACLE OUTLETS OUTSIDE OF THE
 KITCHEN. PROVIDE CORRECTION. NEC 210.11, 210.52; FBC RE
 E3703.2, 3703.4
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 4. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3606.3
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 6. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE AND
 CONNECTIONS FOR EACH GROUNDING ELECTRODE PRESENT TO
 MAIN SERVICE. NEC 250.50, 250.66; FBC RE E3608
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 10:34 Rev Time 0.00
Received By thunt Date 2019-02-22 Time 14:35 Sent To  
Notes
2019-03-11 07:40:373/11 TO T.HUNT
  
2019-02-25 14:35:20R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-01 Cont ID  
Sent By hmoser Date 2019-02-01 Time 09:46 Rev Time 0.00
Received By hmoser Date 2018-12-17 Time 14:56 Sent To  
Notes
2018-12-18 14:56:58R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By dbattles Date 2019-02-26 Time 16:43 Rev Time 0.00
Received By dbattles Date 2019-02-26 Time 16:43 Sent To  
Notes
2019-02-26 16:44:47PLANS STAMPED - OK
 RECEIPT PROVIDED - OK
 MU-2019-004069

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-31 Cont ID  
Sent By dbattles Date 2019-01-31 Time 11:15 Rev Time 0.00
Received By dbattles Date 2019-01-31 Time 11:14 Sent To  
Notes
2019-01-31 11:15:12109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-03-08 Cont ID  
Sent By hmoser Date 2019-03-08 Time 14:23 Rev Time 0.00
Received By hmoser Date 2019-03-08 Time 12:54 Sent To  
Notes
2019-03-08 14:23:12PASS
 HAVE A/C CONTRACTOR SIGN PLAN BEFOR ISSUING
 REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE
 FOR THE DESIGN. 2017 WEST PALM BEACH AMENDMENTS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-01 Cont ID  
Sent By hmoser Date 2019-02-01 Time 09:45 Rev Time 0.00
Received By hmoser Date 2019-01-22 Time 17:14 Sent To I
Notes
2019-02-01 09:45:07PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS FOR GARAGE MINI SPLIT
 PER SECTION R503.2 CHANGE IN SPACE CONDITIONING.
 2017 FLORIDA ENERGY CODE
 2) REFER TO SECTION M1503.4 MAKEUP AIR REQUIRED
 2017 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 10:34 Rev Time 0.00
Received By thunt Date 2019-03-11 Time 10:13 Sent To  
Notes
2019-03-11 10:32:56PLUMBING APPROVED WITH RED LINE PROVISO ON PLAN.
  
 1) HOT WATER REQUIRED AT NEW POOL BATH
  
 2) HAMMER ARRESTORS REQUIRED AT ICE MAKER, DISHWASHER,
 AND WASHING MACHINE.
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLANS EXAMINER
  
 561-805-6711 SAMANTHA HILL*CHIEF PLANS EXAMINER
  
 561-805-6724 GEORGE JOHNSON* PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-17 Cont ID  
Sent By jesmith Date 2019-01-17 Time 08:35 Rev Time 0.00
Received By jesmith Date 2019-01-17 Time 07:44 Sent To  
Notes
2019-01-17 08:20:43APPROVED
 PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. EXISTING VERTICAL WASTE/VENTS AT THE KITCHEN ARE TO
 BE ABANDONED AND CAPPED AT THE FLOOR AS REDLINED ON
 APPROVED PLANS TO COMPLY WITH FBC RES P3104.4.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-07-09 Cont ID  
Sent By rmcdouga Date 2019-07-09 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2019-07-09 Time 09:48 Sent To  
Notes
2019-07-09 09:49:09CONCRETE ROOF TILE NOA NO 16-0112.07
 MULE-HIDE SELF-ADHERED ROOFING NOA NO 17-0824.11

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-02-26 Cont ID  
Sent By dbattles Date 2019-02-26 Time 16:42 Rev Time 0.00
Received By dbattles Date 2019-02-26 Time 16:42 Sent To  
Notes
2019-02-26 16:43:16PROVIDE ROOFING PRODUCT APPROVALS WITH ROOFING SUB
 PERMIT.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-06 Cont ID  
Sent By mcruz Date 2019-03-06 Time 15:00 Rev Time 0.00
Received By mcruz Date 2019-03-06 Time 14:54 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By mcruz Date 2019-01-03 Time 16:31 Rev Time 0.00
Received By mcruz Date 2019-01-03 Time 16:27 Sent To PC
Notes
2019-01-03 16:30:32ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) ILLUSTRATE ON SURVEY THE PROPOSED WORK.
 2) INDICATE THE SETBACK DIMENSIONS FROM THE PROPOSED
 WORK TO ALL PROPERTY LINES.
 3) INDICATE THE SEPARATION DIMENSION FROM THE PROPOSED
 POOL STRUCTURE TO PRINCIPLE STRUCTURE, SHOULD BE AT
 LEAST 6 FEET.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  