Plan Review Details - Permit 18120596
Plan Review Stops For Permit 18120596
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-08 Cont ID  
Sent By fgiaquin Date 2019-01-08 Time 06:22 Rev Time 0.00
Received By fgiaquin Date 2019-01-08 Time 05:43 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-03 Cont ID  
Sent By fgiaquin Date 2019-01-03 Time 06:00 Rev Time 0.00
Received By fgiaquin Date 2019-01-03 Time 05:42 Sent To I
Notes
2019-01-03 06:00:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CONTRACTOR STATES THIS IS A 3-PHASE SERVICE BUT ONLY
 SHOWS 3 CONDUCTORS FROM METER-CAN TO ATS. GROUNDED
 CONDUCTOR MUST BE BROUGHT TO SERVICE ENTRANCE
 EQUIPMENT/DISCONNECTING MEANS. NEC 250.24C 230.41,
 230.42
  
 2. ONE COPY OF PLANS SHOWS 3 PHASE CONDUCTORS TO 200
 AMP PANEL PLUS AN EGC THE OTHER PLAN SHOWS 4 PHASE
 CONDUCTORS PLUS EGC. NEC 230.41, 230.42
  
 3. GENERATOR SHOWS 3 PHASE CONDUCTORS PLUS EGC.
 GENERATOR IS NOT 3-PHASE? FBC 107.2.1 NEC 230.41,
 230.42
  
 4. PROVIDE LOAD CALCULATION OF EXISTING SERVICE. NEC
 220
  
 5. PROVIDE CUT SHEET FOR GENERATOR FOR PRODUCT
 APPROVAL. FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-21 Cont ID  
Sent By fgiaquin Date 2018-12-21 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2018-12-21 Time 06:17 Sent To I
Notes
2018-12-21 06:41:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE ON PERMIT REVISION APPLICATION STATES THERE ARE
 2 METERS ON THIS PROPERTY AND CUSTOMER HAS ELECTED TO
 ONLY DO THE 3-PHASE SERVICE, ORGINAL REVIEWED AND
 APPROVED PLAN SHOWS A 3-PHASE SERVICE WITH 5 METERS AND
 DISCONNECTS- 1X 100AMP, 4X 70AMPS. NO "EXISITNG" 200AMP
 PANEL IS SHOWN ON PREVIOUS APPROVED PLAN. PLEASE
 PROVIDE CLARIFICATION AND AN ACCURATE ONE-LINE DIAGRAM
 OF OF ACTUAL WORK TO BE PERFORMED, TO INCLUDE A LOAD
 CALCULATION FOR SERVICE AND EXISITNG PANELS. FBC
 107.2.1 NEC 220.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-08 Cont ID  
Sent By fgiaquin Date 2019-01-08 Time 06:22 Rev Time 0.00
Received By fgiaquin Date 2019-01-03 Time 11:35 Sent To  
Notes
2019-01-04 11:36:04RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-21 Cont ID  
Sent By fgiaquin Date 2018-12-21 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2018-12-17 Time 16:25 Sent To  
Notes
2018-12-18 16:26:10REVISION ROUTED TO FGIAQUINTO