Plan Review Details - Permit 18120538
Plan Review Stops For Permit 18120538
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-28 Cont ID  
Sent By shill Date 2019-02-28 Time 17:11 Rev Time 0.00
Received By pvalenti Date 2019-02-28 Time 17:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-23 Cont ID  
Sent By shill Date 2019-01-23 Time 08:39 Rev Time 0.00
Received By shill Date 2019-01-22 Time 09:16 Sent To  
Notes
2019-01-23 08:40:49****CORRECTIONS****
 PLAN REVIEW IN PROGESS
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, CHANGES MADE ARE NOT CLEAR. IN COMPARING
 WITH THE ISSUED PERMIT DOCUMENTS, IT APPEARS THAT THE
 DELTA DATE WAS CHANGED BUT NO ADDITIONAL CHANGES MADE
 ON MOST SHEETS. SOME PAGES APPEAR TO BE NEW, BUT
 NOTHING ON THE PAGE INDICATES THAT THEY ARE NEW SHEETS.
 THE NARRATIVE DESCRIBES CHANGES WHICH I WAS UNABLE TO
 LOCATE.
  
 A. FBC 107, REMOVE PAGES WHICH WERE NOT REVISED.
  
 B. REVISE NARRATIVE TO ACCURATELY DESCRIBE CHANGES MADE
 TO THE PLAN.
  
 C. ANY NEW SHEETS SHOULD HAVE A CLOUD AROUND THE SHEET,
 DELTA TO STATE "NEW SHEET".
  
 D. OTHER CHANGES SHOULD BE SHOWN WITH CLOUDS AND A
 DELTA 2 FOR ALL PAGES WHICH WERE ISSUED WITH A DELTA 1.
  
 2. FBC B 703.2, SHEETS A9.2, A9.3, PENETRATION AND
 FIRESTOPPING DETAILS WERE PROVIDED, SOME WITH THE TITLE
 "ENGINEERING JUDGEMENT FIRESTOP DETAIL".
  
 A. PER FS471, REVISE LANGUAGE OR HAVE PAGES PREPARED,
 SIGNED AND SEALED BY AN ENGINEER (PER FLORIDA STATUTE,
 AN ARCHITECT CANNOT USE THE WORD "ENGINEERING").
  
 B. SEE FBC B 703.2, FBC B 714.3,1.1, 714.4.1.2, TESTED
 ASSEMBLIES ARE REQUIRED (APPLICABLE TO ALL DETAILS
 WHICH ARE NOT TESTED ASSEMBLIES). FBC 104.11,
 ALTERNATIVE MATERIALS, DESIGN AND METHODS CAN BE
 PROPOSED AND ARE TO BE APPROVED BY THE BUILDING
 OFFICIAL. AN ALTERNATIVE MATERIAL, DESIGN OR METHOD OF
 CONSTRUCTION SHALL BE APPROVED WHERE THE BUILDING
 OFFICIAL FINDS THAT THE PROPOSED DESIGN IS SATISFACTORY
 AND COMPLIES WITH THE INTENT OF THE PROVISIONS OF THIS
 CODE, AND THAT THE MATERIAL, METHOD OR WORK OFFERED IS,
 FOR THE PURPOSE INTENDED, AT LEAST THE EQUIVALENT OF
 THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY.
  
 SEE FBC 1044.11.1 AND .2 FOR DOCUMENTS REQUIRED:
  
 WHEN ALTERNATE LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO PERFORMANCE-
 BASED FIRE PROTECTION ANALYSIS AND DESIGN OF BUILDINGS,
 OR OTHER METHODS APPROVED BY THE
 BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL
 SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF
 BE SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATIVE.
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL
 OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY PROVIDED
 FOR IN THIS CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE, OR EVIDENCE THAT A MATERIAL OR METHOD
 DOES NOT CONFORM TO THE REQUIREMENTS
 OF THIS CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR
 ALTERNATIVE MATERIALS OR METHODS, THE
 BUILDING OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE
 TESTS AS EVIDENCE OF COMPLIANCE TO BE
 MADE AT NO EXPENSE TO THE JURISDICTION. TEST METHODS
 SHALL BE AS SPECIFIED IN THIS CODE OR
 BY OTHER RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF
 RECOGNIZED AND ACCEPTED TEST
 METHODS, THE BUILDING OFFICIAL SHALL APPROVE THE
 TESTING PROCEDURES. TESTS SHALL BE PERFORMED
 BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS SHALL BE
 RETAINED BY THE BUILDING OFFICIAL FOR
 THE PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-26 Cont ID  
Sent By jpearson Date 2018-12-26 Time 10:48 Rev Time 0.00
Received By jpearson Date 2018-12-26 Time 09:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-04 Cont ID  
Sent By bwoods Date 2019-03-04 Time 11:29 Rev Time 0.00
Received By scaldero Date 2019-03-04 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-14 Cont ID  
Sent By bwoods Date 2019-01-14 Time 00:00 Rev Time 0.00
Received By bwoods Date 2019-01-14 Time 00:00 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-04 Time 06:44 Rev Time 0.00
Received By shill Date 2019-02-07 Time 14:11 Sent To  
Notes
2019-02-08 14:12:06C27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-23 Cont ID  
Sent By shill Date 2019-01-23 Time 08:40 Rev Time 0.00
Received By shill Date 2018-12-14 Time 10:48 Sent To  
Notes
2018-12-18 10:48:41C27

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By pgreilic Date 2019-02-27 Time   Rev Time 0.00
Received By pgreilic Date 2019-02-22 Time 16:16 Sent To  
Notes
2019-02-27 09:18:01PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2018-12-28 Time   Rev Time 0.00
Received By pgreilic Date 2018-12-28 Time 14:15 Sent To  
Notes
2018-12-28 14:16:14INCLUDE APPROVED SITE PLAN IN PLAN SET
  