| 2018-12-20 11:33:13 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | JOSEAN A. DUPREY |
| | PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6716 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | 1.PLEASE SPECIFY HOW THE NEW HORIZONTAL 2X6 WILL BE |
| | ATTACHED TO THE EXISTING WALL. FBCR CHAPTER 6 |
| | 2.THE DRAWINGS INDICATE THE SCOPE IS CEILING |
| | REMODELING. HOWEVER, THE DRAWING SHOWS A NEW OPENING ON |
| | THE EXISTING WALL. PER PROPERTY APPRAISAL THIS IS A 2 |
| | UNIT RESIDENCE. PLEASE PROVIDE MORE INFORMATION FOR |
| | WHAT WILL BE THE USE OF THIS OPENING AND A FLOOR PLAN |
| | WHERE SHOW ALL EXISTING DOORS. |
| | 504.1SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. |
| | 504.2APPLICATION. LEVEL 2 ALTERATIONS SHALL COMPLY WITH |
| | THE PROVISIONS OF CHAPTER 7 FOR LEVEL 1 ALTERATIONS AS |
| | WELL AS THE PROVISIONS OF CHAPTER 8. |
| | 3.THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| | OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE |
| | CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR, |
| | MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE. FBC |
| | 109.3 |
| | |