| 2018-12-26 06:42:39 | 1) YOU HAVE SUBMITTED A TABLE FOR THE 10 PSI SYSTEM BUT |
| | NOT FOR THE LOW PRESSURE SYSTEM. SUBMIT TWO COPIES OF |
| | THE APPLICABLE SIZING TABLES USED TO SIZE THE GAS |
| | SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING |
| | WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER |
| | STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, |
| | 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| | 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2, |
| | & G2413.3. |
| | 2) THERE ARE EXISTING GAS APPLIANCES ON THIS SYSTEM.THE |
| | PLANS INDICATE AND CITY RECORDS SHOW AN EXISTING GAS |
| | SYSTEM FOR THIS ADDRESS. THE BTU LOAD OF THE EXISTING |
| | GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE |
| | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. |
| | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | NOTE: I AHVE INCLUDED A COPY OF THE ORIGINAL GAS PLAN |
| | IN THE PERMIT APPLICATION PACKAGE THAT CAN BE USED AS A |
| | REFERENCE ONLY. IT IS NOT TO BE USED FOR PERMITTING. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |