Plan Review Details - Permit 18120432
Plan Review Stops For Permit 18120432
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-12 Cont ID  
Sent By ccole Date 2018-12-13 Time 11:16 Rev Time 0.00
Received By pvalenti Date 2018-12-12 Time 14:48 Sent To  
Notes
2018-12-12 14:52:32PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED
  
 THE ORIGINAL APPROVED MASTER PERMIT (16111261) INCLUDED
 ALL BUILDINGS WITHIN THIS PARCEL: THE CLUB HOUSE, NORTH
 BUILDING AND SOUTH BUILDING.
  
 THIS REVISION IS THE SAME AS REVISION # 18060969 FROM
 THE NORTH BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-18 Cont ID  
Sent By skennedy Date 2018-12-18 Time 09:58 Rev Time 0.00
Received By skennedy Date 2018-12-18 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-18 Cont ID  
Sent By skennedy Date 2018-12-18 Time 09:58 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2018-12-18 10:01:02SEAL/SIGNED COPY ON FILE VIA PREVIOUS REVISION WITH
 SAME BUILDING TYPE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-12-13 Cont ID  
Sent By ccole Date 2018-12-18 Time 16:11 Rev Time 0.00
Received By skennedy Date 2018-12-12 Time 16:01 Sent To B
Notes
2018-12-13 11:21:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120432
 12/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLANS SHALL BEAR THE ORIGINAL SEALS AND
 SIGNATURES OF THE DESIGN PROFESSIONALS- SECTIONS
 61G15-16-003 & 61G15-23.002 FAC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-18 Cont ID  
Sent By skennedy Date 2018-12-18 Time 09:57 Rev Time 0.00
Received By skennedy Date 2018-12-18 Time 09:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2018-12-18 Cont ID  
Sent By skennedy Date 2018-12-18 Time 09:58 Rev Time 0.00
Received By skennedy Date 2018-12-18 Time 09:58 Sent To  
Notes
***NONE***