| 2018-12-28 14:13:39 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18120427 |
| | REVIEWED: DECEMBER 28, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | [FBC 1017.3]MEASUREMENT. EXIT ACCESS TRAVEL DISTANCE |
| | SHALL BE MEASURED FROM THE MOST REMOTE POINT WITHIN A |
| | STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH OF |
| | HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE ENTRANCE |
| | TO AN EXIT. |
| | |
| | 1. [FBC AMENDED 107.3.5.1] |
| | A) STATE THE MAXIMUM TRAVEL DISTANCE |
| | B) ADJUST LIFE SAFETY PLAN TO SHOW EGRESS FOR OCCUPANTS |
| | TO THE EXIT STAIRWAY DOOR. |
| | C) ADJUST OCCUPANT LOAD TO 27 OCCUPANTS. |
| | |
| | 2. [FBC EXISTING 501]STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. THIS IS A LEVEL 2 ALTERATION. |
| | ALSO, STATE OCCUPANCY AS NO CHANGE FROM PREVIOUS. THIS |
| | WILL SATISFY THE IMPACT STOP THAT WAS INCLUDED WITH |
| | THIS PERMIT REVIEW. |
| | |
| | 4. [FBC 806.4]ACCEPTANCE CRITERIA AND REPORTS. WHERE |
| | REQUIRED TO EXHIBIT IMPROVED FIRE PERFORMANCE, |
| | CURTAINS, DRAPERIES, FABRIC HANGINGS AND SIMILAR |
| | COMBUSTIBLE DECORATIVE MATERIALS SUSPENDED FROM WALLS |
| | OR CEILINGS SHALL BE TESTED BY AN APPROVED AGENCY AND |
| | MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF TEST |
| | 1 OR 2, AS APPROPRIATE, OF NFPA 701, OR EXHIBIT A |
| | MAXIMUM HEAT RELEASE RATE OF 100 KW WHEN TESTED IN |
| | ACCORDANCE WITH NFPA 289, USING THE 20 KW IGNITION |
| | SOURCE. REPORTS OF TEST RESULTS SHALL BE PREPARED IN |
| | ACCORDANCE WITH THE TEST METHOD USED AND FURNISHED TO |
| | THE BUILDING OFFICIAL UPON REQUEST. |
| | PROVIDE SUBMITTAL PRIOR TO INSTALLATION OF ROOM DIVIDER |
| | TO MEET CRITERIA IN 806.4. |
| | |
| | 3. [FBC 305.1]GENERAL. CLEAR FLOOR OR GROUND SPACE |
| | SHALL COMPLY WITH 305. |
| | SHOW CLEAR FLOOR SPACE AT KITCHEN SINK FOR SIDE |
| | APPROACH, OR PROVIDE FOR FORWARD APPROACH (SEE BELOW) |
| | [FBC 606.2]CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |