Plan Review Details - Permit 18120252
Plan Review Stops For Permit 18120252
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 11:08 Rev Time 0.00
Received By cthroop Date 2019-06-11 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 15:03 Rev Time 0.00
Received By cthroop Date 2019-04-30 Time 15:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-05 Cont ID  
Sent By cthroop Date 2019-01-05 Time 11:18 Rev Time 0.00
Received By cthroop Date 2019-01-04 Time 07:00 Sent To  
Notes
2019-01-05 11:22:01BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. STRUCTURE IS MIS-CLASSIFIED AS A STORAGE BUILDING.
 STRUCTURE IS DESIGNED AS A HABITABLE STRUCTURE AND WILL
 REQUIRE PALM BEACH COUNTY IMPACT FEES. CHANGE BUILDING
 DESCRIPTION ON PLANS. STATE WHAT STRUCTURE WILL BE USED
 FOR.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 2. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
 _ OR _
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
  
 3. SHOW FINISHED FLOOR ELEVATION ON SITE PLAN.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 4. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 5. ROOFING PERMIT REQUIRED.
  
 6. PROVIDE FRAMING DETAIL FOR PARAPIT WALLS. PROVIDE
 CONNECTOR SCHEDULE.
 R301.1
 STRUCTURAL CONNECTORS.
 BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD
 LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS,
 WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS
 CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES
 CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO
 COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
  
 7. DESIGNER TO REVIEW ALL PRODUCT APPROVALS AND REVIEW
 IN WRITING. (NOT SIGN AND SEAL)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-18 Cont ID  
Sent By jpearson Date 2019-07-18 Time 11:00 Rev Time 0.00
Received By jpearson Date 2019-07-18 Time 11:00 Sent To  
Notes
2019-07-18 11:00:46PHIL PETTY APPROVED REVISION 19070476 FOR THIS PROJECT.
 PROVISO ON PLAN TO SEE THAT REVISION.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-06-11 Cont ID  
Sent By jpearson Date 2019-06-11 Time 09:09 Rev Time 0.00
Received By jpearson Date 2019-06-11 Time 09:09 Sent To B
Notes
2019-06-11 09:06:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED WITH NOTE ON PLAN.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE
 NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100
 AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE
 TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT
 SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1
 (NOT PROVIDED. RISER DIAGRAM SHOWS A CIRCUIT FEEDING
 THE POOL, BUT THIS IS NOT INCLUDED IN THE PANEL
 SCHEDULE OR THE LOAD CALCULATION. NO LOAD CALCULATION
 HAS BEEN PROVIDED FOR MAIN HOUSE.)
 9. OK
  
 NEW COMMENTS:
  
 10. PER NOTE BELOW THE COMMENTS, THE CORRECTED SHEETS
 ARE REQUIRED TO BE INSERTED INTO THE PLAN WHEN
 RESUBMITTING, AND THE OLD SHEETS SHOULD BE REMOVED.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 11. LOAD CALCULATION STATES THAT A 100 AMP SERVICE WILL
 BE PROVIDED TO GUEST HOUSE. RISER DIAGRAM SHOWS # 8
 WIRE FEEDING THIS PANEL. THIS WIRE SIZE IS NOT RATED
 FOR 100 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16);
 FBC RE E3705.1
 12. PANEL SCHEDULE SHOWS CIRCUIT # 8 AS A 15 AMP
 CIRCUIT AND 14 GAUGE WIRE FOR THE BATHROOM RECEPTACLE.
 A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S).
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-10 Cont ID  
Sent By ppetty Date 2019-04-10 Time 11:29 Rev Time 0.00
Received By ppetty Date 2019-04-10 Time 11:29 Sent To  
Notes
2019-04-10 11:29:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 4. RISER DIAGRAM SHOWS A SEPARATE GROUNDING ELECTRODE
 SYSTEM FOR THE 50 AMP SERVICE. ALL GROUNDING ELECTRODES
 PRESENT ARE REQUIRED TO BE BONDED TOGETHER AT THE
 SERVICE. THE PANEL LOCATED AT THE SEPARATE STRUCTURE
 SHOULD ALSO HAVE A GROUNDING ELECTRODE CONDUCTOR
 INSTALLED TO A GROUNDING ELECTRODE. PROVIDE
 CORRECTIONS. FBC RE E3608.1, E3607.3
 5. THIS SEPARATE STRUCTURE IS REQUIRED TO HAVE A MAIN
 THAT SHUTS OFF ALL POWER TO THE STRUCTURE. PROVIDE
 EITHER A MAIN BREAKER IN THIS PANEL. OR A DISCONNECT
 AHEAD OF THE MAIN LUG PANEL THAT IS LOCATED ON THE
 SEPARATE STRUCTURE. NEC 225.31, 225.32
 6. UNGROUNDED CONDUCTORS FOR OTHER THAN DWELLING UNITS
 SHALL HAVE AN AMPACITY OF NOT LESS THAN 60 AMPERES AND
 SHALL BE SIZED AS REQUIRED FOR FEEDERS. PROVIDE
 CORRECTION. FBC RE E3603.2
 7. OK
 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE
 NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100
 AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE
 TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT
 SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1
 9. OK
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER/ CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-25 Cont ID  
Sent By jpearson Date 2018-12-25 Time 11:05 Rev Time 0.00
Received By jpearson Date 2018-12-25 Time 11:05 Sent To  
Notes
2018-12-25 11:05:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED SHOWS A NEW 50 AMP MAIN
 DISCONNECT ON THE LEFT SIDE OF METER. THIS INSTALLATION
 IS NOT PERMITTED PER FPL ELECTRICAL SERVICE STANDARDS,
 SECTION IV, PAGE 16. ADDITIONALLY, PROVIDE DETAIL OF
 TAPPING FROM METER CAN AS THEY TYPICALLY HAVE LUGS THAT
 PERMIT ONLY ONE WIRE ON EACH LUG. PROVIDE CORRECTIONS.
 WPB FBC 107.2.1; FBC RE E3605.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 4. RISER DIAGRAM SHOWS A SEPARATE GROUNDING ELECTRODE
 SYSTEM FOR THE 50 AMP SERVICE. ALL GROUNDING ELECTRODES
 PRESENT ARE REQUIRED TO BE BONDED TOGETHER AT THE
 SERVICE. THE PANEL LOCATED AT THE SEPARATE STRUCTURE
 SHOULD ALSO HAVE A GROUNDING ELECTRODE CONDUCTOR
 INSTALLED TO A GROUNDING ELECTRODE. PROVIDE
 CORRECTIONS. FBC RE E3608.1, E3607.3
 5. PANEL LOCATED AT SEPARATE STRUCTURE IS SHOWN AS A
 MAIN LUG ONLY PANEL. THIS SEPARATE STRUCTURE IS
 REQUIRED TO HAVE A MAIN THAT SHUTS OFF ALL POWER TO THE
 STRUCTURE. PROVIDE EITHER A MAIN BREAKER IN THIS PANEL.
 OR A DISCONNECT AHEAD OF THE MAIN LUG PANEL THAT IS
 LOCATED ON THE SEPARATE STRUCTURE. NEC 225.31, 225.32
 6. UNGROUNDED CONDUCTORS FOR OTHER THAN DWELLING UNITS
 SHALL HAVE AN AMPACITY OF NOT LESS THAN 60 AMPERES AND
 SHALL BE SIZED AS REQUIRED FOR FEEDERS. PROVIDE
 CORRECTION. FBC RE E3603.2
 7. ALL RECEPTACLE OUTLETS INSTALLED IN STORAGE AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. FBC RE
 E3902.2
 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE
 NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100
 AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE
 TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT
 SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1
 9. BREAKER SIZE SHOWN FOR WATER HEATER IS 30 AMP, WHICH
 IS THE TYPICAL SIZE FOR A 4500 WATT WATER HEATER. BUT
 THE LOAD CALCULATION SHOWS AN 1800 WATT LOAD. PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; FBC
 RE E3602.2
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-04-12 Cont ID  
Sent By aborngra Date 2019-04-12 Time 09:57 Rev Time 0.00
Received By aborngra Date 2019-04-12 Time 09:57 Sent To  
Notes
2019-04-12 09:57:24THE PERMIT HAS APPROVED THE PERMIT WITH THE FOLLOWING
 CONDITIONS:
  
 1. ALL WINDOWS SHALL HAVE CLEAR GLASS OR LOW-E GLASS.
 2. ALL WINDOWS SHALL HAVE AN EXTERNAL OGEE DIMENSIONAL
 MUNTIN PATTERN.
 3. ALL DOORS SHALL HAVE AN EXTERNAL OGEE DIMENSIONAL
 MUNTIN PATTERN.
 4. ALL WINDOWS SHALL BE ALUMINUM SINGLE-HUNG.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 15:38 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 15:38 Sent To  
Notes
2018-12-20 15:40:02WINDOWS DO NOT MATCH APPROVALS PER HPB CASE FOR 6/6
 WINDOWS IN CLASSIC HISTORIC PROPORTIONS. QUESTIONS,
 CONTACT FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION
 PLANNER AT (561) 822-1457 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 11:08 Rev Time 0.00
Received By cthroop Date 2019-06-04 Time 14:32 Sent To  
Notes
2019-06-05 14:32:15RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 15:03 Rev Time 0.00
Received By cthroop Date 2019-04-05 Time 12:38 Sent To  
Notes
2019-04-09 12:38:50R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 08:27 Rev Time 0.00
Received By cthroop Date 2018-12-07 Time 10:57 Sent To  
Notes
2018-12-10 10:59:13R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 11:06 Rev Time 0.00
Received By cthroop Date 2019-06-11 Time 11:02 Sent To  
Notes
2019-06-11 11:07:44MU-2019-017158-000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-05 Cont ID  
Sent By cthroop Date 2019-01-05 Time 11:18 Rev Time 0.00
Received By cthroop Date 2019-01-04 Time 07:00 Sent To  
Notes
2019-01-05 11:18:39PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-30 Cont ID  
Sent By cmontell Date 2019-04-30 Time 13:22 Rev Time 0.00
Received By cmontell Date 2019-04-30 Time 13:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-11 Cont ID  
Sent By cmontell Date 2019-04-11 Time 13:40 Rev Time 0.00
Received By cmontell Date 2019-04-11 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By cmontell Date 2019-01-03 Time 10:05 Rev Time 0.00
Received By cmontell Date 2019-01-03 Time 10:17 Sent To  
Notes
2019-01-03 10:25:01MECHANICAL PLAN REVIEW FAIL
  
 1 BUILDING APPEARS TO BE HABITABLE SPACE.
 PLEASE PROVIDE, ENERGY CALCULATION, HEAT LOAD
 CALCULATION AND MECHANICAL PLANS
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By gjohnson Date 2019-07-18 Time 10:51 Rev Time 0.00
Received By gjohnson Date 2019-07-18 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 09:21 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 08:27 Rev Time 0.00
Received By cthroop Date 2019-01-04 Time 07:00 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 15:03 Rev Time 0.00
Received By cthroop Date 2019-04-30 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-12 Cont ID  
Sent By aborngra Date 2019-04-12 Time 09:40 Rev Time 0.00
Received By aborngra Date 2019-04-12 Time 09:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 15:40 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 15:40 Sent To  
Notes
***NONE***