Plan Review Details - Permit 18120237
Plan Review Stops For Permit 18120237
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2019-02-15 Cont ID  
Sent By jduprey Date 2019-02-15 Time 15:39 Rev Time 0.00
Received By jduprey Date 2019-02-15 Time 15:38 Sent To  
Notes
2019-02-15 15:40:33PERMIT NOT REQUIRED PER FBC 3103.1.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-01-31 Cont ID  
Sent By jduprey Date 2019-01-31 Time 08:28 Rev Time 0.00
Received By jduprey Date 2019-01-31 Time 08:02 Sent To  
Notes
2019-01-31 08:06:56BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE GAZEBO PRODUCT DATA SUBMITTED STATES THE GAZEBO
 IS NOT INTENTED FOR USED IN STRUCTURES THAT TRAP WIND
 OR RAIN THAT WOULD CREATE EXTRA LOAD ON THE PRODUCT.
 THE FLORIDA RESIDENTIAL CODE CHAPTER R301.1 INDICATES
 THAT BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW
 LOADS, WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY
 THIS CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES
 CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO
 COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
  
 2. PLEASE PROVIDE A DIFFERENT PRODUCT TO MEET THE LOAD
 REQUIREMENTS OF FLORIDA RESIDENTIAL CODE OR HAVE THE
 GAZEBO SUBMITTED EVALUATED BY A FLORIDA LICENSE DESIGN
 PROFESSIONAL. WE WANT TO SEE A GAZEBO THAT MEET THE
 WIND LOADS REQUIREMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-14 Cont ID  
Sent By jduprey Date 2019-01-14 Time 15:12 Rev Time 0.00
Received By jduprey Date 2019-01-14 Time 15:11 Sent To  
Notes
2019-01-14 15:12:43BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PLEASE PROVIDE GAZEBO INFORMATION FBC107
  
 1.FOR PRE-ENGINEERED GAZEBO:
 A.PROVIDE FOUNDATION PLAN.
 B.PROVIDE PRE-ENGINEERED DESIGN.
 C.IDENTIFY TYPE OF TIE-DOWN TO FOUNDATION.
  
  
 2.FOR SITE BUILT GAZEBO:
 A.PROVIDE FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING
 B.PROVIDE BUILDING PLANS
 1.FLOOR
 2.WALLS
 3.ROOF FRAMING
 C.WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND
 DESIGN WIND LOADS.
 D.PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR
 DOORS. >720 SQ. FT.
  
  
 2. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE
 CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR,
 MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE. CITY OF
 WPB CHAPTER 1 VALUE 109.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-02 Cont ID  
Sent By jduprey Date 2019-01-02 Time 09:28 Rev Time 0.00
Received By jduprey Date 2019-01-02 Time 09:25 Sent To  
Notes
2019-01-02 09:28:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PLEASE PROVIDE GAZEBO INFORMATION FBC107
  
 1.FOR PRE-ENGINEERED GAZEBO:
 A.PROVIDE FOUNDATION PLAN.
 B.PROVIDE PRE-ENGINEERED DESIGN.
 C.IDENTIFY TYPE OF TIE-DOWN TO FOUNDATION.
  
  
 2.FOR SITE BUILT GAZEBO:
 A.PROVIDE FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING
 B.PROVIDE BUILDING PLANS
 1.FLOOR
 2.WALLS
 3.ROOF FRAMING
 C.WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND
 DESIGN WIND LOADS.
 D.PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR
 DOORS. >720 SQ. FT.
  
  
 2. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE
 CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR,
 MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHAPTER 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By jduprey Date 2018-12-13 Time 08:53 Rev Time 0.00
Received By jduprey Date 2018-12-13 Time 08:50 Sent To  
Notes
2018-12-13 08:53:03BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PLEASE PROVIDE GAZEBO INFORMATION FBC107
  
 1.FOR PRE-ENGINEERED GAZEBO:
 A.PROVIDE FOUNDATION PLAN.
 B.PROVIDE PRE-ENGINEERED DESIGN.
 C.IDENTIFY TYPE OF TIE-DOWN TO FOUNDATION.
  
  
 2.FOR SITE BUILT GAZEBO:
 A.PROVIDE FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING
 B.PROVIDE BUILDING PLANS
 1.FLOOR
 2.WALLS
 3.ROOF FRAMING
 C.WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND
 DESIGN WIND LOADS.
 D.PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR
 DOORS. >720 SQ. FT.
  
  
 2. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE
 CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR,
 MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHAPTER 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2019-02-14 Cont ID  
Sent By aborngra Date 2019-02-14 Time 11:03 Rev Time 0.00
Received By aborngra Date 2019-02-14 Time 11:03 Sent To PC
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status F Date 2019-01-29 Cont ID  
Sent By aborngra Date 2019-01-29 Time 16:00 Rev Time 0.00
Received By aborngra Date 2019-01-29 Time 16:00 Sent To PC
Notes
2019-01-29 16:00:23THE PERMIT #18120237 HAS BEEN FAILED WITH THE FOLLOWING
 REASON(S):
  
 1. THE PROPOSED GAZEBO SHALL NOT NEED 6 FEET BUILDING
 SEPARATION AS PREVIOUSLY MENTIONED. TO ENSURE
 COMPLIANCE WITH SETBACKS, STAFF RECOMMENDS PLACING THE
 PROPOSED GAZEBO RIGHT UP TO THE PRIMARY STRUCTURE.
 2. THE GAZEBO MUST MEET THE FOLLOWING SETBACK
 REQUIREMENTS:
 A. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 B. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 C. CORNER SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10
 FEET.
 3. PLEASE ENSURE GAZEBO WIDTH, FRONT YARD SETBACK, AND
 GAZEBO-PRIMARY STRUCTURE BUILDING SEPARATION TOTALS
 50.7 FEET AS ILLUSTRATE ON THE SUPPLIED SURVEY.
 4. THE PROVIDED PRIVACY WALL IS 12 FEET WIDE, WHILE THE
 PROPOSED GAZEBO IS 20 FEET WIDE. PLEASE CLARIFY IF THIS
 12 FOOT WIDE PRIVACY WALL IS AN EXAMPLE OF WHAT IS TO
 BE BUILT OR IS TO BE ACTUALLY PURCHASED.
 5. PLEASE PROVIDE GAZEBO SPECIFIC INFORMATION THAT
 MATCHES THE SITE PLAN DIMENSIONS OF 19 FEET BY 20 FEET.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2019-01-14 Cont ID  
Sent By aborngra Date 2019-01-14 Time 08:41 Rev Time 0.00
Received By aborngra Date 2019-01-14 Time 08:40 Sent To B
Notes
2019-01-14 08:41:37THE PERMIT #18120237 HAS BEEN FAILED WITH THE FOLLOWING
 REASON(S):
  
 1. THE PROPOSED GAZEBO SHALL NOT NEED 6 FEET BUILDING
 SEPARATION AS PREVIOUSLY MENTIONED. TO ENSURE
 COMPLIANCE WITH SETBACKS, STAFF RECOMMENDS PLACING THE
 PROPOSED GAZEBO RIGHT UP TO THE PRIMARY STRUCTURE.
 2. PLEASE RECONCILE INCONSISTENT DIMENSIONS OF PROPOSED
 GAZEBO ON APPLICATION DESCRIPTION AND SITE PLAN.
 3. THE GAZEBO MUST MEET THE FOLLOWING SETBACK
 REQUIREMENTS:
 A. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 B. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 C. SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10 FEET.
 4. THE PROVIDED PRODUCT INFORMATION PROVIDES
 INFORMATION REGARDING A PRIVACY WALL, NOT A GAZEBO.
 PLEASE PROVIDE GAZEBO SPECIFIC INFORMATION.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2018-12-21 Cont ID  
Sent By aborngra Date 2018-12-21 Time 12:13 Rev Time 0.00
Received By aborngra Date 2018-12-21 Time 12:13 Sent To B
Notes
2018-12-21 12:13:27THE PERMIT HAS FAILED, PLEASE ADDRESS THE FOLLOWING
 COMMENTS:
 1. PROVIDE DIMENSIONS OF GAZEBO, BUILDING SEPARATION,
 AND DISTANCE FROM PROPERTY LINES (SOUTH, WEST, AND
 EAST) TO SCALE.
 2. PROVIDE A PHOTOGRAPH, SKETCH OR OTHER GRAPHIC FOR
 THE APPERANCE OF THE GAZEBO.
 3. THE GAZEBO MUST MEET THE FOLLOWING REQUIREMENTS:
 A. MINIMUM BUILDING SEPERATION OF 6 FEET (IF GAZEBO IS
 ROOFED).
 B. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 C. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 D. SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10 FEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON
 BORNGRABER AT [email protected] OR CALL 561-822-1428.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By jduprey Date 2018-12-13 Time 08:53 Rev Time 0.00
Received By aborngra Date 2018-12-11 Time 11:50 Sent To PC
Notes
2018-12-11 11:50:54THE PERMIT HAS FAILED, PLEASE ADDRESS THE FOLLOWING
 COMMENTS:
 1. PROVIDE DIMENSIONS OF GAZEBO, BUILDING SEPARATION,
 AND DISTANCE FROM PROPERTY LINES (SOUTH, WEST, AND
 EAST) TO SCALE.
 2. PROVIDE A PHOTOGRAPH, SKETCH OR OTHER GRAPHIC FOR
 THE APPERANCE OF THE GAZEBO.
 3. THE GAZEBO MUST MEET THE FOLLOWING REQUIREMENTS:
 A. MINIMUM BUILDING SEPERATION OF 6 FEET (IF GAZEBO IS
 ROOFED).
 B. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 C. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 D. SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10 FEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON
 BORNGRABER AT [email protected] OR CALL 561-822-1428.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-02-15 Cont ID  
Sent By jduprey Date 2019-02-15 Time 15:40 Rev Time 0.00
Received By jduprey Date 2019-02-12 Time 11:26 Sent To  
Notes
2019-02-13 11:27:04RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-31 Cont ID  
Sent By jduprey Date 2019-01-31 Time 08:28 Rev Time 0.00
Received By jduprey Date 2019-01-23 Time 16:49 Sent To  
Notes
2019-01-24 16:49:16RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-14 Cont ID  
Sent By jduprey Date 2019-01-14 Time 15:12 Rev Time 0.00
Received By jduprey Date 2019-01-09 Time 12:45 Sent To  
Notes
2019-01-10 12:45:19RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-02 Cont ID  
Sent By jduprey Date 2019-01-02 Time 09:29 Rev Time 0.00
Received By jduprey Date 2018-12-19 Time 11:42 Sent To  
Notes
2018-12-20 11:42:32RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-13 Cont ID  
Sent By jduprey Date 2018-12-13 Time 08:53 Rev Time 0.00
Received By jduprey Date 2018-12-07 Time 11:04 Sent To HIST
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2019-02-14 Cont ID  
Sent By aborngra Date 2019-02-14 Time 11:03 Rev Time 0.00
Received By aborngra Date 2019-02-14 Time 11:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2019-01-29 Cont ID  
Sent By aborngra Date 2019-01-29 Time 15:59 Rev Time 0.00
Received By aborngra Date 2019-01-29 Time 15:59 Sent To B
Notes
2019-01-29 15:59:54THE PERMIT #18120237 HAS BEEN FAILED WITH THE FOLLOWING
 REASON(S):
  
 1. THE PROPOSED GAZEBO SHALL NOT NEED 6 FEET BUILDING
 SEPARATION AS PREVIOUSLY MENTIONED. TO ENSURE
 COMPLIANCE WITH SETBACKS, STAFF RECOMMENDS PLACING THE
 PROPOSED GAZEBO RIGHT UP TO THE PRIMARY STRUCTURE.
 2. THE GAZEBO MUST MEET THE FOLLOWING SETBACK
 REQUIREMENTS:
 A. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 B. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 C. CORNER SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10
 FEET.
 3. PLEASE ENSURE GAZEBO WIDTH, FRONT YARD SETBACK, AND
 GAZEBO-PRIMARY STRUCTURE BUILDING SEPARATION TOTALS
 50.7 FEET AS ILLUSTRATE ON THE SUPPLIED SURVEY.
 4. THE PROVIDED PRIVACY WALL IS 12 FEET WIDE, WHILE THE
 PROPOSED GAZEBO IS 20 FEET WIDE. PLEASE CLARIFY IF THIS
 12 FOOT WIDE PRIVACY WALL IS AN EXAMPLE OF WHAT IS TO
 BE BUILT OR IS TO BE ACTUALLY PURCHASED.
 5. PLEASE PROVIDE GAZEBO SPECIFIC INFORMATION THAT
 MATCHES THE SITE PLAN DIMENSIONS OF 19 FEET BY 20 FEET.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2019-01-14 Cont ID  
Sent By aborngra Date 2019-01-14 Time 08:42 Rev Time 0.00
Received By aborngra Date 2019-01-14 Time 08:41 Sent To PC
Notes
2019-01-14 08:42:09THE PERMIT #18120237 HAS BEEN FAILED WITH THE FOLLOWING
 REASON(S):
  
 1. THE PROPOSED GAZEBO SHALL NOT NEED 6 FEET BUILDING
 SEPARATION AS PREVIOUSLY MENTIONED. TO ENSURE
 COMPLIANCE WITH SETBACKS, STAFF RECOMMENDS PLACING THE
 PROPOSED GAZEBO RIGHT UP TO THE PRIMARY STRUCTURE.
 2. PLEASE RECONCILE INCONSISTENT DIMENSIONS OF PROPOSED
 GAZEBO ON APPLICATION DESCRIPTION AND SITE PLAN.
 3. THE GAZEBO MUST MEET THE FOLLOWING SETBACK
 REQUIREMENTS:
 A. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 B. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 C. SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10 FEET.
 4. THE PROVIDED PRODUCT INFORMATION PROVIDES
 INFORMATION REGARDING A PRIVACY WALL, NOT A GAZEBO.
 PLEASE PROVIDE GAZEBO SPECIFIC INFORMATION.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-21 Cont ID  
Sent By aborngra Date 2018-12-21 Time 12:12 Rev Time 0.00
Received By aborngra Date 2018-12-21 Time 12:12 Sent To PC
Notes
2018-12-21 12:13:06THE PERMIT HAS FAILED, PLEASE ADDRESS THE FOLLOWING
 COMMENTS:
 1. PROVIDE DIMENSIONS OF GAZEBO, BUILDING SEPARATION,
 AND DISTANCE FROM PROPERTY LINES (SOUTH, WEST, AND
 EAST) TO SCALE.
 2. PROVIDE A PHOTOGRAPH, SKETCH OR OTHER GRAPHIC FOR
 THE APPERANCE OF THE GAZEBO.
 3. THE GAZEBO MUST MEET THE FOLLOWING REQUIREMENTS:
 A. MINIMUM BUILDING SEPERATION OF 6 FEET (IF GAZEBO IS
 ROOFED).
 B. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 C. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 D. SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10 FEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON
 BORNGRABER AT [email protected] OR CALL 561-822-1428.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By aborngra Date 2018-12-11 Time 11:51 Rev Time 0.00
Received By aborngra Date 2018-12-11 Time 11:51 Sent To B
Notes
2018-12-11 11:51:25THE PERMIT HAS FAILED, PLEASE ADDRESS THE FOLLOWING
 COMMENTS:
 1. PROVIDE DIMENSIONS OF GAZEBO, BUILDING SEPARATION,
 AND DISTANCE FROM PROPERTY LINES (SOUTH, WEST, AND
 EAST) TO SCALE.
 2. PROVIDE A PHOTOGRAPH, SKETCH OR OTHER GRAPHIC FOR
 THE APPERANCE OF THE GAZEBO.
 3. THE GAZEBO MUST MEET THE FOLLOWING REQUIREMENTS:
 A. MINIMUM BUILDING SEPERATION OF 6 FEET (IF GAZEBO IS
 ROOFED).
 B. FRONT YARD SETBACK (SOUTH PROPERTY LINE) OF 25 FEET.
 C. SIDE YARD SETBACK (EAST PROPERTY LINE) OF 5 FEET.
 D. SIDE YARD SETBACK (WEST PROPERTY LINE) OF 10 FEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON
 BORNGRABER AT [email protected] OR CALL 561-822-1428.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]