| 2018-12-10 07:15:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. INDIVIDUAL LEVELS OF PARKING GARAGE NOT LABELED ON |
| | PLANS. PROVIDE CORRECTION. FBC 107.2.1 |
| | |
| | 2. PROVIDE EXTERIOR LIGHTING CONTROL ON PLANS FOR |
| | EXTERIOR MONUMENT SIGNS AT ENTRANCES TO PARKING GARAGE. |
| | ( A NOTE ON THE PLAN WILL SUFFICE) FBC EC 405.2.4 |
| | |
| | 3. PROVIDE DISCONNECTS (120V) FOR EXTERIOR MONUMENT |
| | SIGNS AS PER NEC 600.6A1 |
| | |
| | 4. PROVIDE WIRING DIAGRAMS FOR EXTERIOR MONUMENT SIGNS. |
| | FBC 107.2.1 |
| | |
| | 5. PROVIDE UL OR OTHER NRTL LISTING/CUT SHEETS OF |
| | EXTERIOR MONUMENT SIGNS FOR PRODUCT APPROVAL. FBC |
| | 107.2.1 NEC, 90.7, 110.2, 110.3B |
| | |
| | 6. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |