Plan Review Details - Permit 18120199
Plan Review Stops For Permit 18120199
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By cthroop Date 2019-02-14 Time 10:19 Rev Time 0.00
Received By cthroop Date 2019-02-14 Time 10:13 Sent To E
Notes
2019-02-14 10:20:32RETURNED TO ELECTRICAL (FG) FOR SECOND LOOK. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By fgiaquin Date 2018-12-22 Time 10:59 Rev Time 0.00
Received By cthroop Date 2018-12-19 Time 14:23 Sent To E
Notes
2018-12-19 15:42:31BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SHOW COMPLIANCE WITH THE FBC SECTION 3113, LIGHTING,
 MIRRORS AND LANDSCAPING.
  
 SECTION3113
 LIGHTING, MIRRORS, LANDSCAPING
 3113.1
 EACH OPERATOR OF AN AUTOMATED TELLER MACHINE THAT
 CONTROLS THE ACCESS AREA OR DEFINED PARKING AREA TO BE
 LIGHTED SHALL COMPLY WITH SECTIONS (2), (3), AND (4) NO
 LATER THAN ONE YEAR AFTER OCTOBER 1, 1994. IF THE
 ACCESS AREA OR DEFINED PARKING AREA TO BE LIGHTED IS
 CONTROLLED BY A PERSON OTHER THAN THE OPERATOR, SUCH
 OTHER PERSON SHALL COMPLY WITH SECTIONS (2), (3), AND
 (4) NO LATER THAN ONE YEAR AFTER OCTOBER 1, 1994.
 3113.2
 EACH OPERATOR, OR OTHER PERSON RESPONSIBLE FOR AN
 AUTOMATED TELLER MACHINE PURSUANT TO SECTIONS 655.960
 THROUGH 655.965, SHALL PROVIDE LIGHTING DURING THE
 HOURS OF DARKNESS WITH RESPECT TO AN OPEN AND OPERATING
 AUTOMATED TELLER MACHINE AND ANY DEFINED PARKING AREA,
 ACCESS AREA AND THE EXTERIOR OF AN ENCLOSED AUTOMATED
 TELLER MACHINE INSTALLATION, AS FOLLOWS:
 1.THERE SHALL BE A MINIMUM OF 10 FOOTCANDLE (108 LUX)
 POWER AT THE FACE OF THE AUTOMATED TELLER MACHINE AND
 EXTENDING IN AN UNOBSTRUCTED DIRECTION OUTWARD 5 FEET
 (1.5 M).
 2.THERE SHALL BE A MINIMUM OF 2 FOOTCANDLE (21.5 LUX)
 POWER WITHIN 50 FEET (15.25 M) IN ALL UNOBSTRUCTED
 DIRECTIONS FROM THE FACE OF THE AUTOMATED TELLER
 MACHINE. IF THE AUTOMATED TELLER MACHINE IS LOCATED
 WITHIN 10 FEET (3 M) OF THE CORNER OF THE BUILDING AND
 THE AUTOMATED TELLER MACHINE IS GENERALLY ACCESSIBLE
 FROM THE ADJACENT SIDE, THERE SHALL BE A MINIMUM OF 2
 FOOTCANDLE (21.5 LUX) POWER ALONG THE FIRST 40
 UNOBSTRUCTED FEET (12 M) OF THE ADJACENT SIDE OF THE
 BUILDING.
 3.THERE SHALL BE A MINIMUM OF 2 FOOTCANDLE (12.5 LUX)
 POWER IN THAT PORTION OF THE DEFINED PARKING AREA
 WITHIN 60 FEET (18 M) OF THE AUTOMATED TELLER MACHINE.
 4.THE OPERATOR SHALL PROVIDE REFLECTIVE MIRRORS OR
 SURFACES AT EACH AUTOMATED TELLER MACHINE WHICH PROVIDE
 THE CUSTOMER WITH A REAR VIEW WHILE THE CUSTOMER IS
 ENGAGED IN USING THE AUTOMATED TELLER MACHINE.
 5.THE OPERATOR, OR OTHER PERSON RESPONSIBLE PURSUANT TO
 SECTIONS 655.960 THROUGH 655.965 FOR AN AUTOMATED
 TELLER MACHINE, SHALL ENSURE THAT THE HEIGHT OF ANY
 LANDSCAPING, VEGETATION OR OTHER PHYSICAL OBSTRUCTIONS
 IN THE AREA REQUIRED TO BE LIGHTED PURSUANT TO SECTION
 (2) FOR ANY OPEN AND OPERATING AUTOMATED TELLER MACHINE
 SHALL NOT EXCEED 3 FEET (914 MM), EXCEPT THAT TREES
 TRIMMED TO A HEIGHT OF 10 FEET (3 M) AND WHOSE
 DIAMETERS ARE LESS THAN 2 FEET (610 MM) AND MANMADE
 PHYSICAL OBSTRUCTIONS REQUIRED BY STATUTE, LAW, CODE,
 ORDINANCE OR OTHER GOVERNMENTAL REGULATION SHALL NOT BE
 AFFECTED BY THIS SECTION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-15 Cont ID  
Sent By fgiaquin Date 2019-02-15 Time 05:32 Rev Time 0.00
Received By fgiaquin Date 2019-02-15 Time 05:12 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-13 Cont ID  
Sent By fgiaquin Date 2019-02-12 Time 06:49 Rev Time 0.00
Received By fgiaquin Date 2019-02-12 Time 06:30 Sent To B
Notes
2019-02-13 06:47:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL COMMENTS HAVE BEEN SATISFIED BUT ONLY ONE SET OF
 NEW ELECTRICAL PLAN HAS BEEN SUBMITTED. PLEASE SUBMIT 2
 SETS OF NEW DRAWING. FBC 107, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-22 Cont ID  
Sent By fgiaquin Date 2018-12-22 Time 10:59 Rev Time 0.00
Received By fgiaquin Date 2018-12-22 Time 10:18 Sent To I
Notes
2018-12-22 10:33:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. ELECTRICAL
 PLAN HAS VERY LITTLE INFORMATION. MUST INCLUDE WIRE
 SIZE, CONDUIT SIZE, OCP, PANEL SCHEDULE, ETC. PLEASE
 REVIEW THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. PROVIDE UL OR OTHER NRTL LISTING FOR MATERIALS AND
 EQUIPMENT. (NEW ATM MACHINE, KIOSK, ETC). FBC 107.2.1
 NEC 90.7, 110.2, 110.3B
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-15 Cont ID  
Sent By lmarchan Date 2019-02-15 Time 08:39 Rev Time 0.00
Received By lmarchan Date 2019-02-05 Time 14:19 Sent To  
Notes
2019-02-06 14:19:48RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-22 Cont ID  
Sent By fgiaquin Date 2018-12-22 Time 10:59 Rev Time 0.00
Received By fgiaquin Date 2018-12-06 Time 15:10 Sent To B
Notes
2018-12-07 15:10:43ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-11 Cont ID  
Sent By mcruz Date 2019-02-11 Time 14:02 Rev Time 0.00
Received By mcruz Date 2019-02-11 Time 13:58 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-14 Cont ID  
Sent By mcruz Date 2018-12-14 Time 10:58 Rev Time 0.00
Received By mcruz Date 2018-12-14 Time 10:02 Sent To PC
Notes
***NONE***