| 2018-12-19 08:19:38 | RESIDENTIAL (R3) FOUNDATION ONLY PERMIT, BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- FOUNDATION PLAN WAS NOT SUBMITTED. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 2- FLOOD ZONE AE WITH BASE FLOOD ELEVATION OF 7'-0" |
| | (NAVD OF 1988). POWDER ROOM LOCATED IN THE GARAGE NEEDS |
| | TO BE ELEVATED TO 9'-0". |
| | CITY ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR |
| | ELEVATION NEEDS TO BE TWO FEET FREEBOARD ABOVE THE BASE |
| | FLOOD ELEVATION. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | NOTE: MAIN HOUSE AND FOUNDATION PERMITS WERE |
| | SIMULTANEOUSLY REVIEWED. MAIN HOUSE PERMIT WAS APPROVED |
| | WITH PROVISO. CONTRACTOR TO COORDINATE THIS TWO PERMITS |
| | TO AVOID CONFLICTS/DELAYS. SEE PROVISO BELOW: |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-SHOW ATTIC ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN |
| | THE 1ST & 2ND FLOOR. |
| | 2-PROVIDE PRODUCT APPROVAL FOR: A)WINDOW MULLIONS AND |
| | SPECIFY MULLION SIZE. B)DOORS PRODUCT APPROVAL |
| | FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE SHUTTERS |
| | PRODUCT APPROVAL AND COMPLETE INSTALLATION SCHEDULE. |
| | C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK |
| | WHICH ASSEMBLY L IS GOING TO BE USED. D) SHUTTERS SHOWN |
| | ON EXTERIOR ELEVATIONS AND PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. E) WATER PROOFING AT TERRACE. |
| | PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE |
| | MATERIAL SPECIFIED BY THE DESIGNER OF RECORD. F) |
| | DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT |
| | APPROVALS. |
| | 3-ALUMINUM TRELLIS UNDER SEPARATE PERMIT PER |
| | ARCHITECT'S RESPONSE LETTER. |
| | 4-REVISE ENTRY FOYER FINISH ELEVATION IN ALL PLANS. PER |
| | JOHN MELHORN, THE ELEVATION WILL BE 9'-0" (NAVD OF |
| | 1988) NOT 8'-6". |
| | 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS. |
| | PROVIDE PRODUCT APPROVAL AND REVISE PLANS SHOWING |
| | LOCATION. ALSO, POWDER ROOM LOCATED IN THE GARAGE NEEDS |
| | TO BE ELEVATED TO 9'-0". |
| | |