Plan Review Details - Permit 18120162
Plan Review Stops For Permit 18120162
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By jwitmer Date 2019-01-02 Time 07:22 Rev Time 0.75
Received By jwitmer Date 2019-01-02 Time 06:46 Sent To  
Notes
2019-01-02 07:22:362017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120162
 ADD: 343 SOUTHERN BLVD.
 CONT: VERICON CONSTRUCTION
 TEL: 305-202-1145
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 02/2019
 ACTION: DENIED
  
 1) PLEASE NOTE NOT ENOUGH INFORMATION WAS GIVEN ON THE
 PERMIT APPLICATION UNDER THE SCOPE OF WORK. FURTHER
 WORK DESCRIPTION: TEMP. TRAILER. IT IS NOTED AT THIS
 ADDRESS IS CHASE BANK, IS THIS MODULAR BUILDING TO BE
 USED BY THE BANK EMPLOYEES? IF SO THEN COMPLIANCE WITH
 SECTION 553.501-553.513 PART II OF THE FLORIDA STATUTES
 WOULD BE REQUIRED. IF A TEMPORARY CONSTRUCTION TRAILER
 PLEASE STATE SO ON THE PERMIT APPLICATION. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED. IF THIS IS TO BE AN
 OFFICE USED BY THE BANK EMPLOYEES THEN DETAILS ON THE
 ACCESSIBLE RAMP, GUARDRAIL, HANDRAIL, & LANDINGS WILL
 BE REQUIRED.
  
 2) PLEASE NOTE THE SUBMITTED 8X11 ALLIED TRAILER TIE
 DOWN IS SMALLER THAN THE 1/8 INCH SCALE. IT HAS BEEN
 REDUCED IN SIZE, ILLEGIBLE. 107.2.1.3 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 3) PLEASE NOTE THAT ON ALL MODULAR BUILDING PLANS
 APPROVED BY THE STATE, ONLY THE BUILDING PLANS ARE
 APPROVED. FOUNDATION PLANS ARE APPROVED ON A SITE
 SPECIFIC BASES AND NEED A DESIGN PROFESSIONALS SEAL AND
 SIGNATURE. PLEASE ALSO NOTE THE SIGNATURE IS A COPY AND
 THE SEAL IS REDUCED IN SIZE.
  
 61 G 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000. THE
 PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 SHALL APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD?
  
 SIZE OF ARCHITECTS SEAL. FLORIDA ADMINISTRATIVE CODE
 RULE 61G1-16.002 AN ARCHITECTS SEAL SHALL BE
 APPROXIMATELY 2 INCHES IN DIAMETER.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-20 Cont ID  
Sent By jpearson Date 2018-12-20 Time 13:38 Rev Time 0.00
Received By jpearson Date 2018-12-20 Time 11:22 Sent To  
Notes
2018-12-20 13:38:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-07 Cont ID  
Sent By pleduc Date 2018-12-07 Time   Rev Time 0.00
Received By pleduc Date 2018-12-07 Time 11:47 Sent To  
Notes
2018-12-07 11:51:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NO INDICATION OF A SITE PLAN WITH THIS
 SUBMITTAL.
  
 A SITE PLAN IS REQUIRED THAT SHOWS THE LOCATION OF TEMP
 TRAILER INCLUDING DIMENSIONS TO PROPERTY LINES,
 EXISTING OR PROPOSED BUILDING.
  
 DISTANCES SHALL COMPLY WITH NFPA 241.
  
 4.2 TEMPORARY OFFICES AND SHEDS; TABLE 4.2.1 SEPARATION
 DISTANCES, FIRE SPRINKLERS ARE REQUIRED IN EACH
 TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 PLEASE PROVIDE A SITE PLAN IN COMLIANCE WITH THE ABOVE.
  
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-10 Cont ID  
Sent By jesmith Date 2019-01-10 Time 14:10 Rev Time 0.00
Received By jesmith Date 2019-01-10 Time 14:10 Sent To  
Notes
2018-12-06 14:46:29B02

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-01-10 Cont ID  
Sent By jesmith Date 2019-01-10 Time 14:10 Rev Time 0.00
Received By jesmith Date 2019-01-10 Time 14:07 Sent To  
Notes
2019-01-10 14:10:29PERMIT APPLICATION IS FOR TEMPORARY TRAILER
 NO PLUMBING IN SCOPE OF WORK

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-17 Cont ID  
Sent By llouie Date 2018-12-17 Time   Rev Time  
Received By llouie Date 2018-12-17 Time   Sent To  
Notes
2018-12-17 08:26:09** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SITE PLAN, SHOWING THE PROPOSED LOCATION AND
 SETBACK DISTANCE OF THE TRAILER FROM THE PROPERTY LINES
 IS REQUIRED. TRAILER SHALL COMPLY WITH THE SETBACK
 REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).
  
 2.) PROVIDE ADDITIONAL INFORMATION ON THE HEIGHT OF THE
 PROPOSED STRUCTURE.
  
  
 NOTES:
  
 * TRAILER SHALL BE REMOVED WITHIN 7 DAYS OF THE FINAL
 CONSTRUCTION INSPECTION BY THE CITY PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.).
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  