Plan Review Details - Permit 18120106
Plan Review Stops For Permit 18120106
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By jduprey Date 2019-01-14 Time 16:39 Rev Time 0.00
Received By jduprey Date 2019-01-14 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By cthroop Date 2018-12-19 Time 14:20 Rev Time 0.00
Received By cthroop Date 2018-12-19 Time 07:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-09 Cont ID  
Sent By jleahy Date 2019-01-09 Time 17:35 Rev Time 0.00
Received By jleahy Date 2019-01-09 Time 17:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By jleahy Date 2018-12-19 Time 17:14 Rev Time 0.00
Received By jleahy Date 2018-12-19 Time 17:14 Sent To  
Notes
2018-12-19 17:34:59FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NOT ENOUGH ELECTRICAL DETAIL TO REVIEW.
  
 NEED TO SHOW DISCONNECTS PER 600.6(A)(1)
  
 CONTROLS PER FBC EC 405.2.4
  
 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC CE 405.2.4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-14 Cont ID  
Sent By jduprey Date 2019-01-14 Time 16:40 Rev Time 0.00
Received By jduprey Date 2019-01-02 Time 13:28 Sent To  
Notes
2019-01-14 09:23:561/14 TO JD DESK
  
  
2019-01-03 13:28:12RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-19 Cont ID  
Sent By jleahy Date 2018-12-19 Time 17:35 Rev Time 0.00
Received By jleahy Date 2018-12-10 Time 13:07 Sent To  
Notes
2018-12-11 13:08:10ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-04 Cont ID  
Sent By hmtribou Date 2019-01-04 Time 08:59 Rev Time 0.00
Received By hmtribou Date 2019-01-04 Time 08:59 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-12 Cont ID  
Sent By hmtribou Date 2018-12-12 Time 15:44 Rev Time 0.00
Received By hmtribou Date 2018-12-12 Time 15:44 Sent To B
Notes
***NONE***